Page 6

Servicing Filter

Units are equipped with the number of filters shown in

table 1. Filters should be checked monthly and replaced

when necessary with filters of like kind and size. Take note

of air flow direction marking on filter frame when

reinstalling filters. See figure 7.

REMOVE FILTERS

PULL TO REMOVE
FILTERS

FIGURE 7

NOTE − Filters must be ULC approved or equivalent for
use in Canada.

TABLE 1

NUMBER AND SIZE OF FILTER BY UNIT

LGA/LGC Unit

Qty Filter Size − inches (mm)

036, 042, 048, 060, 072

2

16 X 25 X 2 (406 X 635 X 51)

090, 102, 120, 150

4

18 X 24 X 2 (457 X 610 X 51)

156, 180, 210, 240, 300S

6

24 X 24 X 2 (610 X 610 X 51)

248, 300H, 360

12

20 X 20 X 2 (508 X 508 X 51)

Lubrication

All motors are lubricated at the factory. No further

lubrication is required.

Blower shaft bearings are prelubricated. For extended

bearing life, relubricate at least once every two years

with a lithium base grease, such as Alvania 3 (Shell Oil),

Chevron BRB2 (Standard Oil) or Regal AFB2 (Texas

Oil). Use a hand grease gun for relubrication. Add only

enough grease to purge through the bearings so that a

bead of grease appears at the seal lip contacts.

Manifold Pressures

Manifold pressures are shown in table 2. Refer to figures

2, 3, and 4 to locate pressure ports.

TABLE 2

MANIFOLD PRESSURES 

in.wg. (kPa)

Natural Gas

Propane (LP) Gas

LGA/LGC Unit

1st Stg.+

0.2(+.05)

2nd Stg.+
0.3 (+.08)

1st Stg.+

0.2 (+.05)

2nd Stg.+
0.3 (+.08)

036, 042, 048, 060,
072 Std./High Heat

NA

3.5

(0.87)

NA

10.5

(2.61)

036, 042, 048, 060,
072 Dual Heat

1.9

(0.47)

3.5

(0.87)

5.3

(1.32)

10.5

(2.61)

090 through 360

1.6

(0.40)

3.7

(0.92)

5.5

(1.37)

10.5

(2.61)

Burners

Clean the burners as follows:

1− Turn off the electrical power and the gas supply to the

unit.

2− Open or remove the burner compartment access

panel.

3− Remove two screws securing burners to burner

support and lift the burners from the orifices. See
figure 8. Clean as necessary. Spark gap on ignition
electrode must be properly set. Refer to the Heating
Adjustment section in the installation instructions.

4− Replace burners and screws securing burner.

Replace the burner compartment access panel.

5− Turn on the electrical power and the gas supply to the

unit. Follow the operating instructions attached to the
unit and use the inspection port in the access panel
to check the flame.

BURNER BOX ASSEMBLY

FIGURE 8

GAS MANIFOLD

FLAME

SENSOR

GAS

VALVE

BURNERS

Summary of Contents for LGA042

Page 1: ...ice must be per formed by a qualified installer ser vice agency or the gas supplier D Do not try to light any appliance D Do not touch any electrical switch do not use any phone in your building D Imm...

Page 2: ...S DISCONNECT OPTIONAL ECONOMIZER OPTIONAL 120V GFCI OUTLET OPTIONAL LGA LGC090 102 120 and 150 Parts Arrangement COMBUSTION AIR INDUCER 120V GFCI OUTLET Factory installed option BLOWER MOTOR CONDENSER...

Page 3: ...UBES BLOWERS CONDENSATE DRAIN FILTERS ECONOMIZER DAMPERS OPTIONAL CONTROL BOX 120V GFCI OUTLET Factory installed option DISCONNECT Factory installed option LGA LGC248 300H and 360 Parts Arrangement CO...

Page 4: ...errors can cause improper and dangerous operation Verify proper operation after servicing WARNING Danger of electrical shock explosion and fire Improper servicing could result in dangerous operation...

Page 5: ...HONEYWELL VR8205Q VR8305Q SERIES GAS VALVE Gas valve knob is shown in OFF position FIGURE 4 LOW FIRE ADJUSTMENT HIGH FIRE ADJUSTMENT INLET PRESSURE TAP MANIFOLD PRESSURE TAP 6 Wait five 5 minutes to c...

Page 6: ...n using the inspection port provided on the burner access panel Flue Passage and Vent Inspection Annually before heating season inspect the combustion air louvers vent cap heat exchanger burners and c...

Page 7: ...bearings so that a bead of grease appears at the seal lip contacts Manifold Pressures Manifold pressures are shown in table 2 Refer to figures 2 3 and 4 to locate pressure ports TABLE 2 MANIFOLD PRESS...

Page 8: ...and combustion air inducer gasket should also be replaced during reassembly Service Reminder Call a qualified service technician if the unit is inoperative Before calling always check the following t...

Reviews: