Page 23
507124-04 3/2016
D-Refrigerant Charge and Check - All-Aluminum Coils
WARNING-Do not exceed nameplate charge under
any condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant,
reclaim the charge,
evacuate the system,
and
add
required nameplate charge.
NOTE - System charging is not recommended below
60
F (15
C). In temperatures below 60
F (15
C),
the
charge
must
be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in standard cooling mode.
1- Make sure outdoor coil is clean. Attach gauge
manifolds and operate unit at full CFM in cooling mode
with economizer disabled until system stabilizes
(approximately five minutes). Make sure all outdoor air
dampers are closed.
2- Check each system separately with all stages
operating. Compare the normal operating pressures
(see tables 4 - 8) to the pressures obtained from the
gauges. Check unit components if there are
significant differences.
3- Measure the outdoor ambient temperature and the
suction pressure. Refer to the appropriate circuit
charging curve on Page 26 through Page 35 to
determine a target liquid temperature.
Note - Pressures are listed for sea level applications.
4- Use the same thermometer to accurately measure the
liquid temperature (in the outdoor section).
If measured liquid temperature is higher than
the target liquid temperature, add refrigerant to
the system.
If measured liquid temperature is lower than
the target liquid temperature, recover some
refrigerant from the system.
5- Add or remove charge in increments. Allow the system
to stabilize each time refrigerant is added or removed.
6- Continue the process until measured liquid
temperature agrees with the target liquid
temperature. Do not go below the target liquid
temperature when adjusting charge. Note that
suction pressure can change as charge is adjusted.
7- Example LGH/LCH180H Circuit 1: At 95°F outdoor
ambient and a measured suction pressure of
130psig, the target liquid temperature is 96.5°F. For
a measured liquid temperature of 106°F, add charge
in increments until measured liquid temperature
agrees with the target liquid temperature.
TABLE 4
LGH/LCH156H NORMAL OPERATING PRESSURES - ALUMINUM COIL
Normal Operating Pressures
Outdoor Coil Entering Air Temperature
65
°
F
75
°
F
85
°
F
95
°
F
105
°
F
115
°
F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Circuit 1
110
241
112
279
115
321
117
367
119
419
122
472
118
245
121
282
124
324
127
370
129
420
131
474
137
255
140
292
142
333
145
378
148
431
152
484
154
266
160
304
163
346
163
392
171
441
174
496
Circuit 2
111
249
112
287
113
328
116
374
118
423
121
474
119
253
120
291
122
332
124
378
127
428
129
481
137
263
139
301
142
342
145
387
146
438
149
490
153
276
158
313
162
356
164
402
167
451
171
505
Circuit 3
115
256
116
294
118
335
120
381
122
429
124
480
123
261
125
299
128
340
130
386
132
436
133
488
140
273
143
311
146
353
149
398
152
449
154
502
157
284
162
324
166
367
169
413
171
462
174
515