Page 4
ELECTRICAL DATA
Model No.
HS29-461
HS29-463
HS29-511
HS29-513
Line voltage data 60 hz
208/230v
1ph
208/230v
3ph
460v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
575v
3ph
Rated load amps
17.5
12.8
6.4
23.4
14.0
7.1
5.8
Compressor
Power factor
.98
.93
.93
.98
.88
.88
.88
Locked rotor amps
92.0
87.0
44.0
110.0
91.0
46.0
37.0
Condenser Coil
Full load amps
1.1
1.1
0.55
1.9
1.9
0.90
0.90
Condenser Coil
Fan Motor
Locked rotor amps
1.9
1.9
1.0
4.1
4.1
2.1
2.1
Rec. maximum fuse or circuit breaker size (amps)
40
25
15
50
30
15
10
*Minimum circuit ampacity
23.0
17.1
8.6
31.2
19.4
9.8
8.2
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
ELECTRICAL DATA
Model No.
HS29-651
HS29-653
HS29-681
HS29-683
Line voltage data 60 hz
208/230v
1ph
208/230v
3ph
460v
3ph
575v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
Rated load amps
26.9
17.3
9.0
7.1
27.1
18.6
7.9
Compressor
Power factor
.98
.86
.86
.86
.97
.86
.86
Locked rotor amps
123.0
128.0
64.0
51.0
175.0
128.0
63.0
Condenser Coil
Full load amps
1.9
1.9
0.90
0.90
1.9
1.9
0.90
Condenser Coil
Fan Motor
Locked rotor amps
4.1
4.1
2.1
2.1
4.1
2.1
2.1
Rec. maximum fuse or circuit breaker size (amps)
60
40
20
15
60
40
15
*Minimum circuit ampacity
35.5
23.5
12.2
9.8
35.8
24.2
10.8
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
ELECTRICAL DATA
Model No.
HS29-012
HS29-018
HS29-024−2
HS29-024−3
HS29-030
HS29-036
Line voltage data 60 hz
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230
v
1ph
208/230v
3ph
460v
3ph
Rated load amps
4.9
8.6
7.9
12.2
14.7
16.0
10.3
5.1
Compressor
Power factor
.97
.97
.97
.96
.90
.91
.83
.83
Locked rotor amps
26.3
48.3
48.3
61.0
84.0
100.0
77.0
39.0
Condenser Coil
Full load amps
1.1
1.1
1.1
1.1
1.1
1.1
1.1
0.55
Condenser Coil
Fan Motor
Locked rotor amps
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.0
Rec. maximum fuse or circuit breaker size (amps)
15
20
15
25
30
35
20
10
*Minimum circuit ampacity
7.3
11.9
11.0
16.4
19.5
21.1
14.0
6.9
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
ELECTRICAL DATA
Model No.
HS29−042
HS29-048
HS29-060
Line voltage data 60 hz
208/230v
1ph
208/230v
3ph
460v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
575v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
575v
3ph
Rated load amps
20.3
12.4
6.4
23.7
12.8
6.4
5.1
28.8
15.4
7.6
5.9
Compressor
Power factor
.84
.93
.93
.98
.88
.88
.88
.95
0.86
0.86
0.86
Locked rotor amps
127.0
88.0
44.0
129.0
91.0
46.0
37.0
169.0
124.0
59.6
49.4
Condenser
Coil
Full load amps
1.1
1.1
.55
1.9
1.9
0.9
0.9
1.9
1.9
0.90
0.90
Coil
Fan Motor
Locked rotor amps
1.9
1.9
1.0
4.1
4.1
2.1
2.1
4.1
4.1
2.1
2.1
Rec. maximum fuse or circuit breaker
size (amps)
40
25
15
50
30
15
10
60
35
15
10
*Minimum circuit ampacity
26.4
16.6
8.6
31.5
17.9
8.9
7.3
37.9
21.2
10.4
8.3
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
Summary of Contents for HS29-012
Page 20: ...Page 20 SERVICE NOTES...