background image

Page 79

C19 DIAGRAM AND B34 DIAGRAM AND D8 DIAGRAM

Limited Commercial Application

Basic Electromechanical or Electronic Thermostat

Connected to Residential Horizontal-Only Unit (GCS16H)

with RDE16 and Three-Position Economizer

2- C19 SECTION and B34 SECTION with D8 Section (commercial application of elec

tromechanical or electronic thermostat wired to residential unit with three-position

economizer)

GCS16H units, even though not equipped for commercial use, may be converted to commer

cial downflow use in a special limited application. The application requires use of RDE16-41

roof duct enclosure to convert the unit to downflow use. The RDE16-41 includes a factory

installed harness for connecting optional REMD16-41 or REMD16M-41 economizer.

NOTE - The RDE16-41 economizer harness is represented in diagram C19. The economiz

er harness and jack J3 are located inside the RDE16-41, not inside the unit as in other

GCS16 commercial units.  REMEMBER, this is a limited application converting a residential

unit to commercial use.

The harness (shown in diagram C19) has pigtails on the unit end and harness jack J3 on the

economizer end.  The unit end of the harness hard wires to the unit and thermostat with pigtails.

Economizer jack J3 at the end of the harness connects  directly into economizer plug P4.  Field

wiring is shown in more detail in figure 59.
This particular application connects the REMD16-41 three-position economizer to the

GCS16H.  The RDE16-41 return air side panel is removed and the REMD16-41 slides into the

side of the cabinet (same as it would into the side of a commercial GCS16).  Economizer har

ness jack is located in the return air compartment of the RDE16-41. This installation is shown

in figures 92 and 57.

Operation Sequence:

 1- Line voltage energizes transformer T1. Transformer T1 provides 24VAC power to all unit con

trols and thermostat.

 2- Heating demand initiates at W1 in the thermostat and energizes relay K13. Heating demand

also passes through high temperature limits S10 to combustion air prove switch S18.

 3- Relay K13 terminals 4-7 close to energize combustion air blower B6. Terminals 6-9 close to

energize the economizer (commercial units only). When the combustion air blower nears full

speed, prove switch S18 closes. Heating demand continues through S18 and through high

temperature limit S47 to energize ignition control terminal 1.

 4- Ignition control A3 then waits 30 to 40 seconds to allow combustion air blower B6 time to draw

exhaust gas from combustion chamber and to introduce fresh air. Combustion air blower B6

operates throughout the heating cycle.

 5- After the ignition control delay, A3 activates gas valve GV1, time delay K25 and the spark elec

trode.  When flame is sensed by the flame sensor (minimum 5 microamps) the spark electrode

stops.  If flame is not sensed after the first trial for ignition, controller A3 repeats steps 4 through

5 up to two more times (depending on controller make) before locking out.   Delay relay K25

delays 60 seconds before closing.

If the control locks out, it can be reset by breaking and remaking thermostat demand.

 6- After the 60 second delay, relay K25 closes to energize the indoor blower on heating speed.

I. Enthalpy Control in Low Position (outside air can be used for cooling).

First stage cool (all models):

 7- Initial cooling demand Y1 is sent to enthalpy control A6 terminal 1.

 8- Enthalpy control A6 has determined that outside air can be used for cooling and has switched

internal 1K and 2K internally.

 9- Cooling demand is routed through enthalpy control terminal 6 and through discharge air ther

mostat S13 to enthalpy control terminal D and damper motor terminal D.

 10- When 24VAC is applied across terminals D and T of damper motor, the damper motor ener

gizes and outdoor dampers open fully. First stage cooling is provided by outdoor air.

 11-Thermostat terminal G energizes relay K3. K3-1 closes to energize the indoor blower and K3-2

closes to energize the damper motor.

2nd stage cool (all models):

 12- Economizer outdoor air dampers remain open.

 13- Additional cooling demand is routed from thermostat Y2 through enthalpy control terminals 3

and 5 to energize contactor K1. The compressor provides all additional cooling.

 14- K1 is a single pole contactor, allowing compressor terminal R and one leg of the condenser fan

to be powered at all times.  K1-1 closes to energize compressor  terminal C, condenser fan

motor and the run capacitors for each motor. Condenser fan and compressor immediately be

gin operating.

II. Enthalpy Control in High Position (outside air cannot be used for cooling).

Cooling:

 15- Enthalpy control internal relays 1K and 2K switch.  Voltage across D & TR drops out while

voltage across X & TR continues. Outdoor air dampers close to minimum position.

 16- Cooling demand is sent from thermostat terminal Y1 through enthalpy control terminals 1 and

2 and through enthalpy control terminal 5 to energize the compressor.  The compressor han

dles all cooling demand.

 17- K1 is a single pole contactor, allowing compressor terminal R and one leg of the condenser fan

to be powered at all times.  K1-1 closes to energize compressor  terminal C, condenser fan

motor and the run capacitors for each motor. Condenser fan and compressor immediately be

gin operating.

 18- Thermostat terminal G energizes relay K3. K3-1 closes to energize the indoor blower and

K3-2 closes to energize the damper motor.

Night Setback (optional field installed-steps not shown on diagram)

 19- Optional field installed time clock (not shown), night thermostat S12 and night relay K11 must

be connected for night setback operation.

 20- Blower B3 operates only during a heating demand when night thermostat is closed.

 21- When clock contacts close (not shown), relay K11 energizes.  Contacts K11-1 open to disable

the day thermostat and contacts K11-2 open to drive the dampers full closed.

 22- (Not shown) Night thermostat S12 is typically set with setpoints below thermostat S1.  During

unoccupied periods, K11-1 opens while S1 is disabled. When S12 closes, power is supplied to

S1 and the unit operates normally. When S12's setpoint is reached, S12 opens, S1 is disabled

and unit operation stops.

 23- Shortly before the building is to be occupied, clock contacts open to de-energize relay K11.

Contacts K11-1 close to restore power the thermostat S1 and Contacts K11-2 close to restore

power to the minimum positioner. Outdoor air dampers open to mid (minimum) position during

blower operation.

Summary of Contents for GCS16 Series

Page 1: ...NG SYSTEM SERVICE CHECKS Page 31 A G A C G A Applications and Requirements Page 31 Gas Piping Page 31 Testing Gas Piping and Supply Pressure Page 31 Check and Adjust Manifold Pressure Page 31 Proper G...

Page 2: ...oof Mounting Frame used with RDE16 41 only Optional Economizer Dampers Model No 3 position Modulating Number and size of filters in Optional Ceiling Supply and Return Air Diffusers Step Down Flush Tra...

Page 3: ...0 78 0 73 1 73 1 LB 62090DA 78 000 90 000 70 000 80 5 81 0 77 1 77 1 7 8 34 400 3950 9 70 8 70 4 lbs 12 oz 10 x 8 1 2 900 1500 4 10 3 8 2 15 8 70 3 8 2 20 20 4 2200 1 6 240 1 2 1 2 7 11 3 4 45 27 0 20...

Page 4: ...13 100 GCS16 513 125 GCS16 653 75 GCS16 653 125 Data 60hz Recommended max ampacity 208 230v 1 ph 3 ph 460v 3 ph 208 230v 1 ph 3 ph 460v 3 ph 30 40 45 15 20 25 27 0 36 0 42 0 20 0 26 0 29 0 10 0 14 0 1...

Page 5: ...10 0 3 8 3 8 10 0 3 8 3 8 0 75 0 75 0 60 0 60 0 60 0 60 0 60 0 60 30 15 40 20 15 45 25 20 86 86 84 87 87 86 88 88 Where current does not exceed 60 amps HACR circuit breaker may be used in place of fu...

Page 6: ...in wg Air Volume cfm Various Speeds High Med Low 0 10 15 30 40 50 60 High Med Low 1280 915 785 1230 885 760 1210 875 745 1120 825 695 1065 770 995 710 905 05 1255 900 775 20 1180 860 730 25 1155 835...

Page 7: ...1330 1645 1525 1425 1310 1550 1440 1345 1240 1485 1380 1290 1190 1420 1320 1230 1135 1350 1260 1165 1075 05 1710 1565 1475 1350 20 1615 1490 1400 1290 25 1580 1465 1375 1265 External Static Pressure...

Page 8: ...2215 1940 1700 1465 2425 2190 1920 1675 1440 2400 2165 1900 1650 1410 2365 2140 1880 1625 1380 2335 2115 1855 1600 1345 0 10 15 30 40 50 60 05 20 25 2275 2065 1805 1550 1275 2215 2010 1750 1475 1180 2...

Page 9: ...2185 1995 1755 1440 External Static Pressure in wg Air Volume cfm Various Speeds High Medium Low Med High Med Low 2560 2280 2055 1780 1525 2540 2265 2035 1765 1510 2520 2250 2025 1745 1485 2495 2235 2...

Page 10: ...only not shown see figure 12 SHIPPING BRACKET FIGURE 2 GCS16 411 PARTS ARRANGEMENT GCS16R 411 PARTS ARRANGEMENT CONTACTOR CONTROL BOX COMPRESSOR COMPARTMENT IGNITION CONTROL GAS VALVE BURNER COMBUSTIO...

Page 11: ...6 models are factory equipped with the hardware required for installing Lennox optional thermostat control systems Lennox optional thermostat control systems are the same controls harnesses and harnes...

Page 12: ...ELAY BLOWER RELAY FIGURE 5 BLOWER LIMIT CONTROL S47 COMPRESSOR CONTACTOR INDOOR BLOWER RELAY K20 HEATING SPEED 460V 575V UNITS ONLY TERMINAL STRIP TB1 GCS16 ONLY TRANSFORMER T1 TRANSFORMER T3 GCS16R 4...

Page 13: ...circuits in the unit Transformers are rated at 45VA 208 230 P voltage transformers use two primary voltage taps as shown in figure 7 FIGURE 7 BLUE YELLOW ORANGE RED BLACK 240 VOLTS 208 VOLTS PRIMARY...

Page 14: ...mplete an internal circuit when the motor is on low or medium heating speed 8 Potential Relay K31 Relay K31 is used in single phase 510 and 650 units only and is located in the control box It is a pot...

Page 15: ...ENSOR ELECTRODE ASSEMBLY BURNER ENCLOSURE not included on all units SIGHT GLASS not included on all units BURNER PLATE GAS VALVE GAS MANIFOLD COMBUSTION AIR BLOWER IGNITION CONTROL BURNER ENCLOSURE AI...

Page 16: ...y combustion air blower B6 Combustion air blower B6 is controlled by heat ing demand from the thermostat or control system The burner is factory set and does not require adjustment Burner end caps if...

Page 17: ...sily slide off for service Each orifice and burner are sized specifically to the unit Refer to Lennox Repair Parts Listing for correct sizing in formation 3 Burner Enclosure The following units are eq...

Page 18: ...after a heating cycle due to residual heat in the heat exchange assembly Blower OFF settings above 90 F may also cause nuisance trips of secondary limit S10 Adjustment procedure is outlined in Heatin...

Page 19: ...air prove switch is factory set and is not adjustable Factory settings are shown in Table 3 COMBUSTION AIR PROVE SWITCH FACTORY SETTING TABLE 3 Unit inches w c N O closes on pressure drop GCS16H 261 G...

Page 20: ...single phase PSC motor to power the combustion air blower A single run capacitor is mounted on the motor The capacitor is rated 4mfd at 370VAC All other heat exchanger sizes use a shaded pole motor to...

Page 21: ...ignition control is energized after proving combustion air blower operation The control allows 30 to 40 seconds for the combustion air blower to vent exhaust gases from the burner The ignition contro...

Page 22: ...110 ON CLOSED OFF OPEN END OF DEMAND 1 COMBUSTION AIR PROVE SWITCH 5 5 70 FIGURE 20 RETRIALS IGNITION ATTEMPT SEQUENCE TIMINGS NOMINAL THERMOSTAT DEMAND COMBUSTION AIR BLOWER GAS VALVE IGNITION SPARK...

Page 23: ...ce figure 23 GCS16R and GCS16H series units are not equipped with crankcase heater high pressure switch or loss of charge switch All units are equipped with thermometer well for charging All models us...

Page 24: ...SER COIL EVAPORATOR COIL THERMOMETER WELL and LIQUID GAUGE PORT COMPRESSOR TERMINAL BOX COMPRESSOR TERMINAL BOX EXPANSION VALVE LIQUID LINE SUCTION LINE SUCTION LINE DISCHARGE LINE HIGH PRESSURE SWITC...

Page 25: ...ch opens on a pressure rise All commercial units GCS16 are equipped with the limit GCS16R and GCS16H are not equipped with the limit The switch is lo cated in the compressor discharge line and is wire...

Page 26: ...6H 311 Type MFD Volts Single Single GCS16 411 GCS16R 411 Dual shared with compressor 7 370 5 370 GCS16 413 Single 5 370 208 230 208 230 208 230 ALL GCS16 511 651 GCS16R 511 651 208 230 Single 7 370 GC...

Page 27: ...MMON FAILURE TO CONNECT THE BLUE TAP AS SHOWN ON UNIT DIAGRAM WILL CAUSE IMPROPER OPERATION INCREASED CURRENT FLOW AND OR BURNT WINDINGS 10 Indoor Blower Motor Capacitor C4 All GCS16 208 230v units us...

Page 28: ...CAL CONNECTIONS A Power Supply Refer to start up directions and refer closely to the unit wir ing diagram when servicing Refer to unit nameplate for minimum circuit ampacity and maximum fuse size 208...

Page 29: ...ber Turn off power to the unit All access panels covers and vent caps must be in place and secured VI REFRIGERATION SYSTEM SERVICE CHECKS The charge should be checked during start up using the method...

Page 30: ...513 and GCS16R 511 units Approach temperature should be 9 F 5 C for GCS16 651 653 and GCS16R 651 units Refrigerant must be added to lower approach temperature Re move refrigerant from system to incre...

Page 31: ...s supply pressure connect test gauge to the inlet pressure tap field provided Test supply gas pressure with unit firing at maximum rate Make sure the reading falls within the range of the following va...

Page 32: ...6 H 50 GCS16 75 GCS16 100 GCS16 125 Unit Output 40 000 Btuh 60 000 Btuh 80 000 Btuh 100 000 Btuh G High Altitude Derate The maximum input may be reduced by up to 24 percent on A G A units equipped wit...

Page 33: ...rner head alignment Bolts must be torqued to 35 in lbs to ensure proper operation 7 Be sure to secure all wires and check plumbing and burner plate for airtight seal 8 Turn on power to unit Follow lig...

Page 34: ...g heat exchanger in burner plate see figure 32 6 Support heat exchanger to prevent heat exchang er from dropping when final bolts are removed Remove bolts securing tailpipe to heating vesti bule Bolts...

Page 35: ...2 inside the flame en velope Do not bend electrodes To measure flame cur rent follow the procedure below 1 Disconnect power to unit 2 Remove lead from sensing electrode and install a 0 50DC microamp m...

Page 36: ...uously With the fan switch in the AUTO position the blower cycles with demand or with some control systems runs continuously while the heating or cooling circuits cycle 3 In most cases the blower and...

Page 37: ...wir ing diagram Adjust the blower heating speed for proper air temperature rise listed on unit rating plate To measure temperature rise place thermometers in the supply and return air plenums Turn up...

Page 38: ...ment 208V 230V Only to determine which J38 jumper to use WARNING DO NOT ISOLATE MEDIUM OR LOW SPEED WINDINGS WHEN OPERATING AT ME DIUM OR LOW SPEED THE BLUE LEAD MUST NEVER BE CONNECTED TO A POWER LEA...

Page 39: ...ctrode and flame sensing electrode gaps Re install the burner and ensure that the burner head is lined up correctly with flame spreader Replace the four screws se curing the gas burner manifold to the...

Page 40: ...t can drain accumulated conden sate 7 Clean the vestibule panel louvers using a small brush F Flue Make sure the flue is clean and free of debris G Evaporator Coil 1 Clean coil if necessary 2 Check co...

Page 41: ...serted in the bracket and through a hole in the base channel of the unit The pin is used only to hold the bracket in place it does not support any weight The bracket bottom lip supports the weight of...

Page 42: ...ctures A typical field fabricated roof mounting frame is shown in figure 43 C Economizers 1 Application REMD16 M and EMDH16 M economizers can only be applied to GCS16 commercial units GCS16R residenti...

Page 43: ...TALLED RETURN AIR FILTER DAMPER MOTOR ENTHALPY CONTROL TYPICAL REMD16M shown OUTDOOR AIR DAMPER HOOD CONTROL ACCESS COVER 3 EMDH16 Horizontal Economizer EMDH16M Horizontal Economizer The EMDH16 and EM...

Page 44: ...fac tory installed in a REMD16 41 REMD16 65 is similar Mixed air sensor should be removed from economizer and installed in unit blower compartment and sensing bulb should be installed in supply air st...

Page 45: ...nstalled in supply air stream as shown in figure 50 OUTDOOR AIR DAMPERS RETURN AIR DAMPERS ENTHALPY SENSOR ENTHALPY SENSOR ACCESS COVER REMOVED OUTDOOR AIR DAMPERS RETURN AIR DAMPERS MIXED AIR SENSOR...

Page 46: ...midity would drive the economizer outdoor air dampers open to utilize outdoor air for cooling The compressor cooling circuit would be disabled Howev er if the outdoor air should change to 70 F a drop...

Page 47: ...rn and supply air see figure 50 The three position economizer sensor switch mounts to pre drilled holes in the unit panel dividing return and supply air e Wiring Installation Maintenance The economize...

Page 48: ...e to fully open position 60 to 90 sec required for full travel Observe travel for proper damper operation 6 Disconnect power to the unit Outdoor damp er should spring return to closed position 7 Remov...

Page 49: ...tems Kit includes a DPDT relay which is hard wired to the economizer harness If a W973 system is used the relay holds the out door dampers closed during setback If an electro mechanical thermostat sys...

Page 50: ...must be used to provide the proper opening for economizer Duct enclo sure RDE16 41 mounts to the GCS16H horizontal air openings and the economizer slides in the RDE16 41 economizer opening see figure...

Page 51: ...W1 ACC C L1 L2 GCS16H J3 ECONOMIZER JACK INSIDE RDE16 41 TRANSITION MATES TO ECONOMIZER PLUG P4 GCS16H TO REMD16 41 or REMD16M 41 ECONOMIZER FIELD WIRING INDOOR THERMOSTAT THERMOSTAT TO ECONOMIZER 2 W...

Page 52: ...tment provides a preliminary pressure setting of about 10 w c 2 5 kPa for the LP regulator 5 Check regulator setting either with a manometer or by clocking the gas meter 6 Install new cap screw CONVER...

Page 53: ...65 In units equipped with burner enclosure figure 12 the en closure must be carefully disassembled to gain access to the burner and restrictor plate FIGURE 64 INSTALL OUTER RESTRICTOR PLATE SECURING A...

Page 54: ...REMOVE FOR 2 FILTER SECURING SCREW LEFT SIDE FIGURE 67 DF16 65 DOWNFLOW FILTER KIT BLOWER LEFT FILTER BRACKET RIGHT FILTER BRACKET SECURING SCREW SECURING SCREW FILTER BRACKET FILLER PIECE REMOVE FOR...

Page 55: ...otection for the compressor The monitor figure 69 is a N O temperature switch located in the control box area It is wired in series with the compres sor contactor When ambient temperature drops below...

Page 56: ...nob CUT IN POINT fixed mi nus CUT OUT POINT To find CUT OUT point this equation can be re arranged CUT OUT CUT IN minus the DIFFERENCE 2 Rotate the knob as needed to set the difference indica tor at 1...

Page 57: ...open the con trol circuit is de energized while control transformer T1 re mains energized to operate dampers exhaust blower etc The unit shuts down and economizer outdoor dampers drive full closed FI...

Page 58: ...FIGURE 76 SP11 STATUS PANEL Cool Mode Heat Mode Compressor 1 Compressor 2 No Heat Filter 1 SP11 Application Required Equipment Readout Relay Kit Optional Equipment Filter Switch Kit The SP11 can be a...

Page 59: ...ontinuously i The AFTER HOURS TIMER on the SSP11 pro vides override of unoccupied mode operation night heating setback cooling setup from 0 to 12 hours In the occupied day mode the after hours timer h...

Page 60: ...onnections as shown in fig ure 79 c SSP11 Relay Kit An SSP11 relay kit is required on units using an electromechanical thermostat and an SSP11 switching status panel The kit is used with the RRB reado...

Page 61: ...Y K29 FIELD WIRING IS CON NECTED TO TERMI NAL STRIP UNLESS W973 OR W7400 IS INSTALLED GCS16 UNIT CONTROL BOX FIELD WIRING SP11 GCS16 410 THROUGH 650 applicable to units equipped with commercial contro...

Page 62: ...4 15 16 17 18 19 20 21 CMC3 1 T7067 THERMOSTAT W2 W1 G RC 1 2 3 COMPRESSOR FIELD WIRING SSP11 GCS16 410 THROUGH 650 UNITS WITH ELECTROMECHANICAL THERMOSTAT applicable to units equipped with commercial...

Page 63: ...HROUGH 650 UNITS WITH W973 applicable to units equipped with commercial controls platform only OPTIONAL EQUIPMENT 24VAC FIELD INSTALLED 24VAC FACTORY INSTALLED 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1...

Page 64: ...HOUSING OR INSIDE MULLION ATTACH HOSE TO HIGH SIDE OF SWITCH BLOWER HOUSING HORIZONTAL SUPPLY AND RETURN AIR COVERS ROUTE HOSE THROUGH DUCT TO OPPOSITE SIDE OF FILTER LEAVE LOW SIDE OF SWITCH OPEN TO...

Page 65: ...1 D5 Modulating Economizer Horizontal or Downflow Modulating Economizer Op tional field installed in all GCS16 and GCS16H units GCS16R excepted Sensors continuously monitor air conditions and adjust...

Page 66: ...for night setback 8 C2 Standard 2 heat 2 cool thermostat for all commercial units with economizer and warm up CMC3 1 clock and night thermostat must be added for night set back Night relay must also...

Page 67: ...ercial units with economizer and warm up Requires W973 relay kit Also requires CMC3 1 clock and night relay for night setback FIGURE 87 W973 THERMOSTAT CONTROL KIT Control Module Relay Kit J17 P17 P6...

Page 68: ...se with either the electromechanical thermostat or the Honeywell W973 control system Both allow mechanical thermostats to set back during unoccu pied periods The clocks models 202A and 702A allow 24 h...

Page 69: ...n the building is not occupied The night kit achieves this by disconnecting thermostat S1 and con necting a night thermostat during periods when the build ing is not occupied The night thermostat can...

Page 70: ...0 relay kit must be added to inter face the control to the economizer WARNING CONNECT ONLY RELAY KITS DE SIGNED FOR THIS CONTROL SYSTEM RELAY KITS DESIGNED FOR OTHER CONTROL SYS TEMS ARE NOT COMPATIBL...

Page 71: ...RELAY KIT J3 P5 BLOWER HARNESS FROM UNIT HARNESS TO ECONOMIZER P16 P17 J5 P4 J16 J17 CONTROL MOUNTING BRACKET HORIZONTAL UNITS W7400 CONTROL CONTROL MOUNTING BOX DOWNFLOW UNITS CAUTION HARNESS BUNDLE...

Page 72: ...hanical control system is being used CMC3 1 time clock and night thermostat must be used An economizer allows outside air to be used for cooling when conditions are acceptable and permits a preset amo...

Page 73: ...ted to plug P19 on the W973 Jumper plug J12 also supplied with the W973 is not used with GCS16s and may be discarded 2 W973 Relay Kit units without economizer or units with economizer and without warm...

Page 74: ...IES AWAY FROM DAMPER BLADES FAILURE TO SECURE WIRES COULD RENDER ECONOMIZER INOPERABLE FIGURE 99 HONEYWELL W973 RELAY KIT AND WARM UP KIT INSTALLATION W973 RELAY KIT W973 CONTROL GCS16 UNIT SUPPLY AIR...

Page 75: ...34 Diagram Pages 76 77 Commercial Application GCS16H and 3 position Economizer C19 Diagram with B34 Diagram and D8 Diagram Pages 78 79 Commercial Application GCS16H and Modulating Economizer C19 Diagr...

Page 76: ...C24 diagram with B34 diagram basic thermostat with residential GCS16R or GCS16H Page 76 1 2 3 4 5 6 7 8 9 10 6 4 7...

Page 77: ...trols and thermostat 2 Cooling demand energizes Y1 and G in the thermostat Y1 energizes compressor contactor K1 G energizes relay K3 3 K1 is a single pole contactor allowing compressor terminal R and...

Page 78: ...al limited commercial application of residential GCS16H with basic thermostat downturn transition and three position economiz er Page 78 Thermostat Footnotes Economizer Footnotes Unit Footnotes 1 2 3...

Page 79: ...d delay relay K25 closes to energize the indoor blower on heating speed I Enthalpy Control in Low Position outside air can be used for cooling First stage cool all models 7 Initial cooling demand Y1 i...

Page 80: ...ecial limited commercial application of residential GCS16H with basic thermostat downturn transition and modulating economiz er Page 80 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Thermostat Footnote...

Page 81: ...Enthalpy Control in Low Position outside air can be used for cooling First stage cool all models 7 Initial cooling demand Y1 is sent to enthalpy control A6 terminal 1 8 Enthalpy control A6 has determi...

Page 82: ...C1diagramwith B34 diagram basic thermostat with commercial single phase GCS16 Page 82 1 2 3 4 5 6 7 4 8 9 10 7 6...

Page 83: ...mostat Y1 energizes compressor contactor K1 G energizes relay K3 3 K1 is a single pole contactor allowing compressor terminal R and one leg of the condenser fan to be powered at all times K1 1 closes...

Page 84: ...C1diagram electromechanical thermostat without economizer connected to 208 230V 3ph commercial unit with B35 diagram Page 84 1 2 3 4 5 5 6 6 7 7 8 9 10 3 Unit Footnotes Thermostat Footnotes...

Page 85: ...diagram electromechanical thermostat without economizer connected to 460V or 575V 3ph commercial unit with B36 diagram Page 85 1 2 3 4 5 5 6 7 8 9 10 11 12 13 14 Unit Footnotes Thermostat Footnotes 10...

Page 86: ...dium speed Refer to unit components section of this manual for more information OPERATION SEQUENCE 460 575V THREE PHASE UNITS ABOVE All units equipped with Crankcase Heater High Pressure Switch Loss o...

Page 87: ...C1diagram electromechanical thermostat with three position economizer with D8 diagram Page 87 1 2 3 4 5 6 11 11 7 8 9 10 Thermostat Footnotes Economizer Footnotes...

Page 88: ...mid minimum position I Enthalpy Control in Low Position outside air can be used for cooling 1st stage cool all models 5 Initial cooling demand Y1 is sent to enthalpy control A6 terminal 1 6 Enthalpy c...

Page 89: ...thermostat with modulating economizer with D5 diagram Page 89 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2 COOL 2 COOL 1 24V COMMON 1 2 Economizer Footnotes Thermostat Footnotes 3 4 5 6 7 8 9 10 11 12 13...

Page 90: ...terminal 1 5 Enthalpy control A6 has determined that outside air can be used for cooling and has switched internal 1K and 2K internally 6 Cooling demand is routed through enthalpy control to energize...

Page 91: ...hermostat with three position economizer and warm up with D8 diagram Page 91 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2 COOL 2 COOL 1 24V COMMON Economizer Footnotes Unit Footnotes 1 2 3 4 5 6 7a 7b 7c...

Page 92: ...shown in the economizer and K42 in the warm up kit are energized 5 Contacts K11 1 open to disconnect power to thermostat S1 K11 2 not shown open to drive the dampers full closed 6 Contacts K42 1 open...

Page 93: ...tat with modulating economizer and warm up with D5 diagram Page 93 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2 COOL 2 COOL 1 24V COMMON Economizer Footnotes Thermostat Footnotes 1 2 3 4 5 5 6 7c 7a 7b 8...

Page 94: ...in the economizer and K42 in the warm up kit are ener gized 5 Contacts K11 1 open to disconnect power to thermostat S1 K11 2 contacts open to drive the dampers full closed 6 Contacts K42 1 open to di...

Page 95: ...C11 1 diagram electromechanical thermostat with night setback relay kit Page 95 24V POWER ECONOMIZER HEAT 1 HEAT 2 COOL 2 COOL 1 BLOWER 24V COMMON 4 3 2 1 5...

Page 96: ...TE 1 The night kit accessory requires the use of optional time clock CMC3 1 and optional night thermostat 2 The time clock accessory requires the use of field wired night kit relay K11 No wiring is re...

Page 97: ...C5 diagram C3 diagram Page 97 1 1 2 2 3 3 4 4 Flexstat thermo stat Prostat thermostat...

Page 98: ...AL G Y1 Y2 W1 W2 10 7 5 4 G 6 5 Y1 4 7 Y2 3 2 W1 9 3 W2 8 8 9 RH RC 2 1 C Operation Sequence 1 The GCS16 with Flexstat Prostat is designed so that the fan switch in the thermostat should be left in th...

Page 99: ...C3 diagram with D8 diagram Flexstat with three position economizer Page 99 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Thermostat Footnotes Economizer Footnotes...

Page 100: ...Prostat with three position economizer with D8 diagram Page 100 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2 COOL 2 COOL 1 24V COMMON Thermostat Footnotes Economizer Footnotes 1 2 3 4 5 6 7 8 9 10 11 12...

Page 101: ...lay K25 in the GCS16 During a cooling demand when the buildingis not occupied the blower is activated through terminal 4 in the Flexstat G in Pros tat 4 Setback relay K11 not furnished is not used in...

Page 102: ...C3 diagram with D5 diagram Flexstat with modulating economizer Page 102 Thermostat Footnotes Economizer Footnotes 1 2 3 4 4 4 5 6 7 8 9 10 11 12 13 14 15...

Page 103: ...Prostat with modulating economizer with D5 diagram Page 103 Economizer Footnotes Thermostat Footnotes 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2 COOL 2 COOL 1 24V COMMON 1 2 3 4 4 4 5 6 7 8 9 10 11 12...

Page 104: ...ctivated only when a heating demand passes through relay K25 in the GCS16 During a cooling demand when the building is not occupied the blower is activated through terminal G in the Prostat 4 in Flex...

Page 105: ...with three position economizer and warm up Page 105 Economizer Footnotes Thermostat Footnotes 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2 COOL 2 COOL 1 24V COMMON 1 16 20 18 17 2 3 15 11 25 5 5 9 24 10...

Page 106: ...t with three position economizer and warm up Page 106 Economizer Footnotes Thermostat Footnotes 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2 COOL 2 COOL 1 24V COMMON 1 2 3 4 5 6 5 7 8 13 14 15 16 17 18 1...

Page 107: ...K40 6 Contacts K40 1 open to keep relay K41 de energized Contacts K41 3 remain open to keep outdoor air dampers closed during initial heating demand 7 When heating demand is satisfied unit gas valve a...

Page 108: ...exstat with modulating economizer and warm up Page 108 Thermostat Footnotes Economizer Footnotes 24V POWER ECONOMIZER 24V COMMON COOL 1 COOL 2 HEAT 1 HEAT 2 BLOWER 1 2 3 5 4 6 7 8 9 10 11 12 13 14 15...

Page 109: ...ostat with modulating economizer and warm up Page 109 Thermostat Footnotes Economizer Footnotes 24V POWER ECONOMIZER 24V COMMON COOL 1 COOL 2 HEAT 1 HEAT 2 BLOWER 3 5 6 11 12 15 24 25 4 22 18 20 8 13...

Page 110: ...lexstat terminal 2 activates the heating section of the GCS16 directly and relay K40 6 Contacts K40 1 open to keep relay K41 de energized Contacts K41 3 remain open to keep outdoor air dampers closed...

Page 111: ...C12diagram T7300 thermostat Page 111 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2 COOL 2 COOL 1 24V COMMON 1 2 3 4...

Page 112: ...ermostat and night relay kit are not needed and are not compatible Operation Sequence 1 The GCS16 with T7300 is designed so that the fan switch in the thermostat should be left in the ON mode at all t...

Page 113: ...ram with D8 diagram T7300 with three position economizer Page 113 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2 COOL 2 COOL 1 24V COMMON Thermostat Footnotes Economizer Footnotes 1 2 3 4 5 6 7 8 9 10 11 1...

Page 114: ...id minimum position I Enthalpy Control in Low Position outside air can be used for cooling 1st stage cool all models 4 Initial cooling demand Y1 is sent to enthalpy control A6 terminal 1 5 Enthalpy co...

Page 115: ...agram with D5 diagram T7300 with modulating economizer Page 115 Thermostat Footnotes Economizer Footnotes 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2 COOL 1 COOL 2 24V COMMON 1 2 3 4 5 6 7 8 9 10 11 12...

Page 116: ...oling First stage cool all models 4 Initial cooling demand Y1 is sent to enthalpy control A6 terminal 1 5 Enthalpy control A6 has determined that outside air can be used for cooling and has switched i...

Page 117: ...C7 3 diagram W7400 Control three position economizer with D8 diagram Page 117 1 2 3 4 5 6 7 5 11 8 9 12 13 10 Thermostat Footnotes Economizer Footnotes...

Page 118: ...ded Relay kit plug P5 connects directly to jack J3 in the blower compartment figure 95 The economizer plugs in to the relay kit Economizer plug P4 connects directly to jack J5 of the W7400 relay kit I...

Page 119: ...C7 3 diagram W7400 Control with modulating economizer with D5 diagram Page 119 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Thermostat Footnotes Economizer Footnotes...

Page 120: ...to the relay kit Economizer plug P4 connects directly to jack J5 of the W7400 relay kit IMPORTANT P14 MUST BE DISCONNECTED FROM J23 IN THIS APPLICATION ONLY IMPROPER UNIT OPERATION WILL RESULT IF P14...

Page 121: ...C8 1 diagram W973 Control Page 121 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2 COOL 2 COOL 1 24V COMMON 1 2 3 4 11 15 7 6 12 8 16 17 13 9 14 5 10...

Page 122: ...Generally A1 cooling contacts C1 close when voltage input to A1 terminal 4 reaches 4VDC C2 cooling contacts close when voltage input to A1 terminal 4 increases to 5 VDC A1 heating contacts H1 close wh...

Page 123: ...ee position economizer with D8 diagram Page 123 Thermostat Footnotes Economizer Footnotes 1 2 3 4 5 6 7 8 9 10 12 13 14 15 16 17 18 19 20 21 22 23 23 24 25 26 24V POWER ECONOMIZER BLOWER HEAT 1 HEAT 2...

Page 124: ...increases to 5 VDC A1 heating contacts H1 close when voltage input to A1 terminal 5 reaches 4 VDC and H2 con tacts close when the voltage ramp increases to 5 VDC 3 To provide anticipation discharge se...

Page 125: ...cool Outdoor air dampers are held closed by contacts K11 2 remaining open not shown 24 A1 terminal 1 feeds 20VDC at all times to A2 terminal 1 and contacts K38 1 and K38 2 source of voltage for resist...

Page 126: ...with modulating economizer with D5 diagram Page 126 1 Thermostat Footnotes Economizer Footnotes 2 3 4 24V POWER ECON BL H 1 HEAT 2 COOL 2 COOL 1 24V COMMON 6 7 8 9 10 22 18 21 25 5 24 14 26 13 19 11...

Page 127: ...increases from 1 to 16 VDC When the heating setpoint is crossed the T7067 begins transmitting a heating ramp from ter minal 5 through TB1 5 to terminal 5 of A1 As room temperature increases the coolin...

Page 128: ...close relays K11and K38 energize 24 Contacts K38 1 close to energize setback resistor R4 Contacts K38 2 close to energize setup resistor R5 Contacts K38 3 open to energize blower B3 on demand only Dur...

Page 129: ...mizer and warm up Page 129 Thermostat Footnotes Economizer Footnotes 24V POWER ECON H 1 H 2 C 2 C 1 24V COMMON 1 17 24 18 19 29 27 3 4 28 37 22 25 34 10 7 16 2 21 9 33 5 36 30 38 18 26 23 30 38 25 22...

Page 130: ...ING RELAY KITS MUST BE CONNECTED IN THE ORDER THEY APPEAR ON THE UNIT CONTROL WIRING DIAGRAM ON THE ADJACENT PAGE Operation Sequence 1 Room temperature is controlled by a thermistor located in A2 T706...

Page 131: ...41 3 opens to drive dampers closed 33 Contacts K38 1 close to energize setback resistor R4 Contacts K38 2 close to energize setup resistor R5 Contacts K38 3 open to energize blower B3 on demand only D...

Page 132: ...ing economizer and warm up Page 132 3 5 6 11 12 15 24 25 4 22 18 20 8 13 9 14 7 10 2 16 19 1 23 21 17 26 27 28 29 30 31 32 33 34 35 36 38 37 39 40 41 42 43 24V POWER 24V COMMON EC H 1 H 2 C 1 C 2 Ther...

Page 133: ...rmistor resistance also changes If room temperature goes up thermistor resistance goes down If room tempera ture goes down thermistor resistance goes up The thermistor allows 2 5V F 1 4V C When the co...

Page 134: ...38 3 open to energize blower B3 on demand only During night operation when contacts K38 3 are open blower B3 operates only on demand powered through relays K25 for heat or K37 for cool Outdoor air dam...

Reviews: