7 − On field supplied terminations, a minimum separation
distance between the end of the exhaust pipe and the
end of the intake pipe is 203mm (8 inches).
TABLE 7
EXHAUST PIPE TERMINATION SIZE REDUCTION
G61MPVT
MODEL
Exhaust Pipe Size
Termination Pipe Size
070
50 or 80mm
40mm
090
50 or 80mm
50mm
110
80mm
50mm*
135
80mm
50mm*
*Approved 3" concentric termination kit terminates with 2−5/8" ID pipe.
FIGURE 22
DIRECT VENT ROOF TERMINATION KIT
UNCONDITIONED
ATTIC SPACE
13mm FOAM
INSULATION IN
UNCONDITIONED
SPACE
SIZE TERMINATION
PIPE PER TABLE 7.
76mm MAX.
80mm or
50mm PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
203 mm MIN
FIGURE 23
EXHAUST
EXHAUST
TERMINATION
INTAKE
TERMINATION
INTAKE
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
(71M80, 69M29 or 60L46)
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
FIGURE 24
EXHAUST
EXHAUST
TERMINATION
INTAKE
TERMINATION
INTAKE
305mm Min.
above ground level.
DIRECT VENT CONCENTRIC WALL TERMINATION
(71M80, 69M29 or 60L46)
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
Details of Exhaust Piping Terminations for Non-Direct
Vent Applications
Exhaust pipes may be routed either horizontally through an
outside wall or vertically through the roof. In attic or closet
installations, vertical termination through the roof is pre-
ferred. Figure 25 shows a typical terminations.
1 − Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in
table 7.The specified pipe size ensures proper veloc-
ity required to move the exhaust gases away from the
building.
2 − On field supplied terminations for side wall exits, ex-
haust piping should extend a maximum of 305mm (12
inches) beyond the outside wall, unless support is pro-
vided in the horizontal section.
FIGURE 25
NON−DIRECT VENT ROOF TERMINATION KIT
UNCONDITIONED
ATTIC SPACE
80mm or
50mm PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
SIZE TERMINATION
PIPE PER TABLE 7.