4.- MAINTENANCE
-GENERAL STATE OF THE CASING :
Furniture, paint, deterioration due to bumps, rust spots, leveling and supporting, state of the shock absorbers,
if installed, screwed panels, etc.
- ELECTRICAL CONNECTIONS :
State of hoses, tightness of screws, grounding, current draw of the compressor and fans and checking that the
unit is receiving the correct voltage.
- COOLING CIRCUIT :
Check that pressure values are correct and that there are no leaks. Check that there is no damage to the pipe
insulation, that the state of the batteries is correct and that there are no chips or clogs
retained by the air flow, etc.
- COMPRESSOR :
Inspect the oil level, if sight glass is present.
Inspect the state of the silent block fixtures.
- DRAINS :
Check that water drains correctly and that the drain trays are clean.
- FANS :
Check that fans turn freely and in the correct direction without excesive noises.
- CONTROL :
Check Set Points and normal operation.
- AIR FILTER :
The air filter can be removed through the side by sliding it over the rail or down. (See figure).
For down removal, remove the two profiles supporting it (depending on the model) which are under the filter
guide rail and screwed into the unit.
The filter should be cleaned with a vacuum cleaner or washed in soapy water.
The frequency for cleaning or changing the air filters will depend on the quality air in the area (fumes, vapors,
suspended dust particles, etc.).
Remember that the metal grille should always be toward the inside of the unit.
4.1.- PREVENTIVE MAINTENANCE
DOWN
REMOVAL
SIDE
REMOVAL
PREVENTIVE MAINTENANCE PREVENTS COSTLY REPAIRS.
BECAUSE OF THIS PERIODIC INSPECTIONS ARE REQUIRED.
Remember that the Control Panel may program a notification parameter, for cleaning or
replacement of air filters depending on the number of hours of fan operation in the indoor section.