SPECIFICATIONS
GAS HEAT
Usage Data
Model Number
LGH156
LGH180
LGH210
LGH156
LGH180
LGH210
LGH240
LGH300
LGH180
LGH210
LGH240
LGH300
Heat Input Type
Low (L)
Standard (S)
Medium (M)
High (H)
Number of Gas Heat Stages
1
2
2
2
Gas Heating
Performance
(Two-Stage)
Input - kW (Btuh)
First Stage
49.5 (169 000)
49.5 (169 000)
68.5 (234 000)
91.4 (312 000)
Second Stage
- - -
68.5 (234 000)
91.9 (314 000)
123.0 (420 000)
Output - kW (Btuh)
First Stage
39.5 (135 000)
- - -
- - -
- - -
Second Stage
- - -
54.8 (187 000)
73.5 (251 000)
98.4 (336 000)
1
Gas Heating
Performance
(Two-Stage)
Input - kW (Btuh)
First Stage
N/A
24.7 (84,500)
34.3 (117,000)
45.7 (156,000)
Second Stage
N/A
49.5 (169,000)
68.5 (234,000)
91.4 (312,000)
Third Stage
N/A
62.7 (214,000)
87 (297,000)
116.1 (396,000)
Fourth Stage
N/A
76.2 (260,000)
105.5 (360,000)
140.7 (480,000)
Output - kW (Btuh)
First Stage
39.5 (135,000)
- - -
- - -
- - -
Second Stage
N/A
- - -
- - -
- - -
Third Stage
N/A
- - -
- - -
- - -
Fourth Stage
N/A
60.9 (208,000)
84.4 (288,000)
112.5 (384,000)
Temperature Rise Range - °C (°F)
8 - 25 (15 - 45)
8 - 25 (15 - 45)
17 - 33 (30 - 60)
22 - 39 (40 - 70)
Thermal Efficiency
80.0%
80.0%
80.0%
80.0%
Gas Supply Connections
1 in. npt
1 in. npt
1 in. npt
1 in. npt
Recommended Gas Supply
Pressure - kPa (in. w.g.)
Natural
1.7 (7)
1.7 (7)
1.7 (7)
1.7 (7)
LPG/Propane
2.7 (11)
2.7 (11)
2.7 (11)
2.7 (11)
1
Four-stage gas heating is enabled when zone sensor, Discharge Air Control, or fresh air tempering mode is selected. (Available when using the CS8500 thermostat or
when connected to Building Automation Systems using BACnet, LonTalk, or S-Bus protocols.
HIGH ALTITUDE DERATE
Units may be installed at altitudes up to 610 m (2000 feet) above sea level without any modification.
At altitudes above 610 m (2000 feet), units must be derated to match gas manifold pressures shown in table below.
At altitudes above 1372 m (4500 feet) unit must be derated 2% for each 305 m (1000 feet) above sea level.
NOTE - This is the only permissible derate for these units.
Gas Heat
Type
Altitude - m
(ft.)
Gas Manifold Pressure
kPa (in. w.g.)
Input Rate
Natural Gas or LPG/Propane - kW (Btuh)
Natural Gas
LPG/Propane Gas
First Stage
Second Stage
Low (L)
No adjustment required
Standard (S) 610 - 1372
(2001 - 4500)
0.52 (2.6)
1.82 (7.3)
49.5 (169 000)
66.0 (225 500)
Medium (M) 6110 - 1372
(2001 - 4500
0.52 (2.6)
1.82 (7.3)
68.5 (233 000)
88.7 (303 400)
High (H)
6110 - 1372
(2001 - 4500
0.52 (2.6)
1.82 (7.3)
91.4 (311 000)