Energence
®
Packaged Gas / Electric 45.7 to 88 kW - 50 Hz/ Page 27
HUMIDITROL
®
DEHUMIDIFICATION SYSTEM RATINGS
45.7 kW - LGH156H4 (1ST STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C
23.9°C
29.4°C
35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
L/s
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
17.2°C
1965
21.1
4.13
0.58 0.77 0.97
17.7
4.65
0.51 0.77 1.00
14.3
5.20
0.47 0.75 1.00
10.9
5.74
0.40
0.75
1.00
2455
23.0
4.16
0.60 0.85 1.00
19.3
4.67
0.55 0.83 1.00
15.4
5.20
0.49 0.83 1.00
11.7
5.72
0.43
0.81
1.00
2945
25.3
4.18
0.63 0.91 1.00
21.0
4.69
0.57 0.89 1.00
16.7
5.20
0.51 0.86 1.00
12.5
5.72
0.46
0.86
1.00
19.4°C
1965
24.0
4.21
0.41 0.59 0.77
20.6
4.75
0.34 0.55 0.78
17.3
5.28
0.27 0.50 0.77
14.0
5.81
0.18
0.48
0.77
2945
26.1
4.21
0.42 0.64 0.85
22.3
4.75
0.35 0.59 0.85
18.5
5.28
0.27 0.56 0.86
14.8
5.81
0.19
0.52
0.86
2945
28.1
4.22
0.44 0.67 0.91
23.9
4.75
0.36 0.63 0.93
19.7
5.28
0.27 0.60 0.93
15.7
5.80
0.18
0.56
0.93
21.7°C
1965
26.8
4.29
0.25 0.42 0.57
23.6
4.83
0.16 0.34 0.53
20.4
5.36
0.07 0.28 0.48
17.2
5.92
-0.03 0.21
0.45
2455
28.9
4.28
0.26 0.42 0.61
25.3
4.81
0.15 0.36 0.57
21.6
5.37
0.05 0.30 0.55
17.9
5.89
-0.06 0.23
0.51
2945
31.0
4.27
0.26 0.45 0.64
26.9
4.81
0.14 0.38 0.62
22.9
5.34
0.03 0.32 0.60
18.9
5.89
-0.09 0.24
0.58
45.7 kW - LGH156H4 (2ND STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C
23.9°C
29.4°C
35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
L/s
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
17.2°C
1965
35.0
6.30
0.66 0.85 1.00
31.0
7.15
0.64 0.87 1.00
27.1
8.02
0.63 0.89 1.00
23.1
8.87
0.59
0.89
1.00
2455
38.0
6.32
0.70 0.92 1.00
33.5
7.19
0.70 0.94 1.00
29.1
8.04
0.68 0.95 1.00
24.7
8.91
0.66
0.95
1.00
2945
41.0
6.35
0.75 0.96 1.00
36.1
7.22
0.75 0.99 1.00
31.3
8.08
0.75 1.00 1.00
26.4
8.94
0.76
1.00
1.00
19.4°C
1965
39.7
6.39
0.48 0.66 0.82
35.5
7.24
0.46 0.65 0.85
31.3
8.10
0.42 0.64 0.87
27.1
8.96
0.38
0.64
0.88
2945
42.8
6.44
0.51 0.70 0.90
38.1
7.28
0.48 0.70 0.92
33.4
8.14
0.45 0.70 0.93
28.6
8.99
0.42
0.68
0.96
2945
45.8
6.47
0.53 0.75 0.96
40.6
7.32
0.51 0.75 0.97
35.3
8.18
0.49 0.74 0.97
30.2
9.03
0.46
0.74
1.00
21.7°C
1965
44.2
6.49
0.31 0.47 0.61
39.8
7.36
0.27 0.43 0.60
35.5
8.20
0.23 0.40 0.60
31.2
9.04
0.17
0.37
0.59
2455
47.6
6.53
0.31 0.49 0.66
42.6
7.40
0.28 0.46 0.65
37.7
8.24
0.23 0.43 0.65
32.6
9.09
0.17
0.40
0.65
2945
50.9
6.59
0.33 0.51 0.70
45.3
7.44
0.28 0.49 0.71
39.7
8.29
0.23 0.46 0.71
34.3
9.12
0.17
0.44
0.72
52.8 kW - LGH180H4 (1ST STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C
23.9°C
29.4°C
35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
L/s
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
17.2°C
2265
24.5
4.75
0.58 0.77 0.95
21.1
5.34
0.52 0.77 0.97
17.6
5.90
0.47 0.74 0.98
14.1
6.49
0.43
0.74
1.00
2830
26.0
4.78
0.62 0.85 1.00
22.0
5.33
0.58 0.86 1.00
18.0
5.89
0.56 0.86 1.00
14.1
6.45
0.52
0.86
1.00
3400
27.5
4.82
0.65 0.92 1.00
23.0
5.34
0.64 0.93 1.00
18.6
5.88
0.62 0.99 1.00
14.2
6.41
0.60
1.00
1.00
19.4°C
2265
27.8
4.84
0.42 0.59 0.76
24.2
5.44
0.35 0.55 0.75
20.6
6.01
0.28 0.51 0.75
16.9
6.58
0.21
0.48
0.75
3400
29.0
4.89
0.44 0.64 0.83
25.0
5.45
0.38 0.62 0.85
21.2
5.98
0.32 0.59 0.87
17.2
6.53
0.26
0.56
0.88
3400
30.2
4.91
0.46 0.68 0.91
25.9
5.44
0.41 0.67 0.95
21.7
5.97
0.34 0.66 0.96
17.5
6.50
0.29
0.66
0.99
21.7°C
2265
31.1
4.96
0.25 0.40 0.55
27.3
5.52
0.17 0.34 0.52
23.5
6.11
0.09 0.29 0.47
19.8
6.69
0.01
0.23
0.45
2830
32.0
4.97
0.25 0.42 0.59
28.1
5.53
0.17 0.37 0.57
24.2
6.09
0.08 0.32 0.54
20.5
6.65
0.00
0.26
0.53
3400
32.9
5.00
0.25 0.45 0.64
28.9
5.55
0.17 0.40 0.63
25.0
6.06
0.08 0.35 0.61
21.1
6.60
-0.01 0.29
0.60
52.8 kW - LGH180H4 (2ND STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C
23.9°C
29.4°C
35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Dry Bulb
Dry Bulb
Dry Bulb
L/s
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
17.2°C
2265
41.3
7.16
0.67 0.84 1.00
37.0
8.05
0.66 0.85 1.00
32.7
8.95
0.65 0.86 1.00
28.3
9.84
0.63
0.88
1.00
2830
43.5
7.20
0.72 0.92 1.00
38.6
8.08
0.72 0.94 1.00
33.6
8.95
0.72 0.95 1.00
28.8
9.84
0.72
0.95
1.00
3400
45.9
7.24
0.77 0.98 1.00
40.4
8.12
0.78 1.00 1.00
35.0
9.00
0.79 1.00 1.00
29.4
9.87
0.80
1.00
1.00
19.4°C
2265
45.8
7.29
0.50 0.64 0.80
41.5
8.19
0.46 0.64 0.83
37.1
9.08
0.43 0.64 0.84
32.6
9.98
0.40
0.63
0.86
3400
48.1
7.33
0.51 0.69 0.85
43.1
8.21
0.50 0.68 0.89
38.2
9.10
0.48 0.70 0.91
33.2
9.97
0.46
0.70
0.95
3400
50.3
7.36
0.56 0.70 0.86
44.8
8.23
0.53 0.72 0.92
39.2
9.09
0.51 0.75 0.95
33.7
9.95
0.49
0.77
1.00
21.7°C
2265
50.4
7.44
0.32 0.47 0.62
45.9
8.33
0.28 0.44 0.60
41.4
9.21
0.23 0.41 0.60
37.1
10.10 0.18
0.38
0.59
2830
52.5
7.46
0.32 0.45 0.56
47.8
8.35
0.28 0.43 0.60
42.7
9.22
0.23 0.44 0.64
37.9
10.09 0.20
0.43
0.67
3400
54.9
7.49
0.33 0.42 0.52
49.5
8.36
0.28 0.44 0.60
43.9
9.23
0.24 0.46 0.69
38.6
10.09 0.19
0.47
0.77