background image

Page 19

Refrigerant Charge 

ELS units have a factory holding charge of 2 pounds of 

HFC-410A in each circuit. Additional refrigerant will need 

to be added during installation. 
To charge the system, use the following procedure:

1 -   Measure actual length of liquid and vapor lines for 

each circuit. 

2 -   Add refrigerant to each circuit based on measured 

liquid and suction line lengths. 

A -  If the measured line length is greater than 25 feet, 

add refrigerant (refer to table 2). 

B -   If the measured line length is less than 25 feet, 

remove refrigerant (refer to table 2).

TABLE 2. Adding Refrigerant

Models

Total lbs –  

Stage 1 with 

25ft line set

Total lbs –  

Stage 2 with  

25ft line set

Liquid Line  

Diameter

Ounces  

Adjustment per 

foot of liquid line

Suction Line  

Diameter 

Ounces  

Adjustment per 

foot of suction line

ELS072S4S

18.5

N/A

3/8

0.5

1-1/8

0.2

ELS090S4S

21.75

N/A

5/8

1.5

1-1/8

0.2

ELS120S4S

23

N/A

5/8

1.5

1-1/8

0.2

ELS120S4D

12

12

3/8

1.5

1-1/8

0.2

ELS150S4D

15

15.5

3/8

0.5

1-1/8

0.2

ELS180S4D

23.75

23.5

5/8

1.5

1-1/8

0.2

ELS240S4D

22.5

23.5

5/8

1.5

1-1/8

0.2

3 -  Check normal operating pressures: 

A - Connect a manifold gauge set to the service valves: 

•  Low pressure gauge to vapor valve service port 
•  High pressure gauge to liquid valve service port

B -   

Operate the system until pressures and 

temperatures stabilize (5 minutes minimum). 

C -   Use a thermometer to measure the outdoor ambient 

temperature. 

D -   If the outdoor temperature is greater than 65

º

(18

º

C): 

•  Apply the outdoor ambient temperature to tables 

4, 5, or 7 to determine normal operating pressures. 

Compare the normal operating pressures to the 

pressures obtained from the connected gauges. If 

liquid pressure is high, remove refrigerant from the 

system. If liquid pressure is low, add refrigerant to 

the system.

•  Add or remove charge in increments.
•  Allow the system to stabilize at least 5 minutes each 

time refrigerant is added or removed.

•  Minor variations in these pressures may be expect-

ed due to differences in installations. Significant dif

-

ferences could mean that the system is not properly 

charged or that a problem exists with some compo-

nent in the system.

4 -   If the outdoor ambient temperature is below 65ºF 

(18ºC) it may be necessary to restrict the air flow 

through the outdoor coil to achieve liquid pressures 

in the 325-375 psig (2240-2585 kPa) range. These 

higher pressures are necessary for checking the 

charge. Block equal sections of the outdoor coil on 

all coil sides until the liquid pressure is in the 325-

375 psig range (figure 10). 

CARDBOARD OR

PLASTIC SHEET

OUTDOOR COIL SHOULD BE BLOCKED ONE SIDE AT A TIME

WITH  CARDBOARD  OR  PLASTIC  SHEET  UNTIL  PROPER

TESTING PRESSURES ARE REACHED.

FIGURE 10. Blocking Outdoor Coil

A -   Charge the unit using the approach method in the 

next section: 

•  Using the same thermometer, compare liquid tempera-

ture at service valve to outdoor ambient temperature. 

Approach Temperature = Liquid temperature minus 

ambient temperature 

•  Approach temperature should be as indicated in ta-

bles 3 or 6 for each stage. An approach temperature 

greater than this value indicates an undercharge. 

An approach temperature less than this value indi-

cates an overcharge.

•  Add or remove charge in increments.
•  Allow system to stabilize at least 5 minutes each 

time refrigerant is added or removed.

•  Do not use the approach method if system pres-

sures do not match pressures in table 4, 5, or 7 

except when the outdoor ambient temperature is 

below 65ºF (18ºC).

•  The approach method is not valid for grossly over or 

undercharged systems.

Summary of Contents for Elite ELS Series

Page 1: ...IR CONDITIONERS 6 20 TONS 507743 02 5 2019 Elite ELS Series 6 20 Ton Shipping and Packing List Check the unit for shipping damage If damaged or parts are missing immediately contact the last shipping...

Page 2: ...CC DD 37 5 8 956 48 3 4 1238 3 1 2 89 45 1 4 1149 REFRIGERANT LINE CONNECTIONS SEE DETAIL REFRIGERANT LINE CONNECTIONS DETAIL EE FF CONTROL BOX ACCESS COMPRESSOR COMPRESSOR CENTER OF GRAVITY INLET AIR...

Page 3: ...CONTROL BOX ACCESS ELECTRICAL INLETS Above Refrigerant Lines TOP VIEW FF EE INLET AIR INLETAIR B B A A CC DD CENTER OF GRAVITY ELECTRICAL INLETS Above Refrigerant Lines OUTDOOR FAN GUARDS 2 INLETAIR...

Page 4: ...D LINE 2 OUTDOOR FAN GUARDS 4 REFRIGERANT LINE CONNECTIONS DETAIL INLET AIR INLET AIR ELECTRICAL INLETS Above Refrigerant Lines DISCHARGE AIR REFRIGERANT LINE CONNECTIONS SEE DETAIL ELECTRICAL INLETS...

Page 5: ...Page 5 Unit Plumbing Parts Arrangement ELS072S4S ELS090S4S...

Page 6: ...Page 6 ELS120S4S ELS120S4D STAGE 2...

Page 7: ...Page 7 ELS120S4D STAGE 1 ELS150S4D STAGE 2...

Page 8: ...Page 8 ELS150S4D STAGE 1 ELS180S4D STAGE 2...

Page 9: ...Page 9 ELS180S4D STAGE 1 ELS240S4D STAGE 2...

Page 10: ...0 Tons 150 12 5 Tons 180 15 Tons 240 20 Tons Cooling Efficiency S Standard Efficiency Minor Design Sequence 1 1st Revision 2 2nd Revision 3 3rd Revision Voltage Y 208 230V 3 phase 60hz G 460V 3 phase...

Page 11: ...Page 11 Unit Control Box Components Arrangement...

Page 12: ...adequate strength and length An H style frame will prevent the top of the unit from being damaged Caution do not walk on unit Important all panels must be in place for rigging Lifting point should be...

Page 13: ...ntrol box Piping can be routed directly from the service valves or field supplied elbows can be added to divert the piping as required Refer to table 1 for field fabricated refrigerant line sizes for...

Page 14: ...AT DISCONNECT SWITCH OR TO AN EARTH GROUND CIRCUIT SIZING AND DISCONNECT SWITCH DISCONNECT SWITCH MAIN FUSE BOX BREAKER PANEL 1 2 TYPICAL HIGH VOLTAGE POWER SUPPLY CONNECTIONS Install room thermostat...

Page 15: ...MAINTAINS SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS NOTE DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL BOX Two Stage Compressor Solenoid L34 Resistance Check Resistanc...

Page 16: ...Page 16 FIGURE 7 Typical Wiring Diagram ELS072S4S ELS090S4S and ELS120S4S G J M Y Voltages...

Page 17: ...VOLTAGE CB8 CIRCUIT BREAKER TRANS T1 S24 S25 T1 SWITCH LOSS OF CHARGE COMP 1 SWITCH LOSS OF CHARGE COMP 2 TRANSFORMER CONTROL SECTION A 3 WIRING DIAGRAM 4 S25 S24 3 1 CB8 T1 208V COOL 1 COOL 2 C2 C1 2...

Page 18: ...OL 1 C2 C1 CB8 CIRCUIT BREAKER TRANS T1 S24 S25 T1 TRANSFORMER CONTROL SWITCH LOSS OF CHARGE COMP 1 SWITCH LOSS OF CHARGE COMP 2 WIRING DIAGRAM SECTION A 4 4 2 5 3 1 S25 S24 T1 240 460 575V 208V CB8 2...

Page 19: ...ssure is high remove refrigerant from the system If liquid pressure is low add refrigerant to the system Add or remove charge in increments Allow the system to stabilize at least 5 minutes each time r...

Page 20: ...91 142 125 52 540 155 558 157 545 140 553 144 548 146 SCFM 2600 2750 2725 2750 3850 pressures at 80F dry bulb and 67F wet bulb entering indoor air temperatures TABLE 5 Normal Operating Pressures Cooli...

Page 21: ...408 141 423 147 420 147 115 46 465 138 463 142 480 149 477 150 125 52 526 139 522 143 544 152 541 152 SCFM 5400 7125 Entering Outdoor Air Temp F C ELS240 ELA240 ELS240 2 ELA120 STAGE 1 STAGE 2 STAGE 1...

Page 22: ...5 374 134 373 137 375 136 105 41 446 143 441 142 425 139 427 137 427 141 428 139 115 46 505 145 501 144 483 143 484 141 484 144 486 142 125 52 569 148 566 147 545 146 548 145 547 147 550 146 SCFM 3615...

Page 23: ...ked as follows OUTDOOR UNIT 1 Clean and inspect the condenser coil You can flush the coil with a water hose 2 The outdoor fan motor is prelubricated and sealed No further lubrication is necessary 3 Vi...

Page 24: ...e or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Vapor Pressure Refrigerant Lines...

Reviews: