
Page 3
SPECIFICATIONS
Gas
Heating
Performance
Model No.
EL296UH110XV60C
EL296UH135XV60D
1
AFUE
96%
96%
High
Fire
Input - Btuh
110,000
132,000
Output - Btuh
106,000
126,000
Temperature rise range - °F
45 - 75
55 - 85
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0
3.5 / 10.0
Low
Fire
Input - Btuh
72,000
86,000
Output - Btuh
70,000
84,000
Temperature rise range - °F
35 - 65
40 - 70
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
1.7 / 4.5
1.7 / 4.5
High static - in. w.g.
Heating
0.8
0.8
Cooling
1.0
1.0
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
3/4
3/4
with furnished 90° street elbow
3/4 slip x 3/4 Mipt
3/4 slip x 3/4 Mipt
with field supplied (PVC coupling) - o.d.
3/4 slip x 3/4 MPT
3/4 slip x 3/4 MPT
Indoor
Blower
Wheel nominal diameter x width - in.
11 x 11
11 x 11
Motor output - hp
1
1
Tons of add-on cooling
3-5
3-5
Air Volume Range - cfm
850 - 2125
950 - 2250
Electrical Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
12.8
12.8
Maximum overcurrent protection
20
20
Shipping Data
lbs. - 1 package
174
188
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.