Page 43
Integrated Control Diagnostic Codes
FLASH CODE
(X + Y)
STATUS / ERROR DESCRIPTION
FLASH CODE DESCRIPTIONS
Pulse
A 1/4 second flash followed by four seconds of off time.
Heartbeat
Constant 1/2 second bright and 1/2 second dim cycles.
X + Y
LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2Hz, remains off for four
seconds, then repeats.
Pulse
Power on − Standby.
Heartbeat
Normal operation − signaled when heating demand initiated at thermostat.
FLAME CODES
1 + 2
Low flame current −− run mode.
1 + 3
Flame sensed out of sequence −− flame still present.
PRESSURE SWITCH CODES
2 + 3
Low pressure switch failed open.
2 + 4
Low pressure switch failed closed.
2 + 5
High pressure switch failed open.
2 + 6
High pressure switch failed closed.
2 + 7
Low pressure switch opened during ignition trial or heating demand.
LIMIT CODE
3 + 1
Limit switch open.
WATCHGUARD CODES
4 + 1
Watchguard −− Exceeded maximum number of retries.
4 + 2
Watchguard −− Exceeded maximum number of retries or last retry was due to pressure switch opening.
4 + 3
Watchguard −− Exceeded maximum number of retries or last retry was due to flame failure.
4 + 5
Watchguard −− Limit remained open longer than three minutes.
4 + 6
Watchguard −− Flame sensed out of sequence; flame signal gone.
4 + 7
Ignitor circuit fault −− Failed ignitor or triggering circuitry.
4 + 8
Low line voltage.
HARD LOCKOUT CODES
5 + 1
Hard lockout −− Rollout circuit open or previously opened.
5 + 2
Control failed self check, internal error (control will restart if error recovers).
5 + 3
No Earth ground (control will restart if error recovers).
5 + 4
Reversed line voltage polarity (control will restart if the error recovers).
5 + 6
Low secondary (24VAC) voltage.
Error Code Storage
The ignition control stores the last ten error codes in
memory. The codes are retained in case of power loss.
Error Code Review
1 − Short R (2) to (1). Within 1/2 second, the STATUS LED
will stay lit continuously to indicate that the short was
sensed.
2 − Continue to hold the short between R (2) to (1). After 5
seconds, STATUS LED will go from being continuously
lit to off. This indicates that error code review is pend-
ing.
3 − Remove R (2) to (1) short within ten seconds of STA-
TUS LED turning off. This activates error code review.
4 − Last ten error codes will be flashed on the STATUS
LED.
5 − After final error code is indicated, STATUS LED will
flash to indicate normal operation.
Clearing Error Codes
1 − Short R (2) to (1). Within 1/2 second, the STATUS LED
will stay lit continuously to indicate that the short was
sensed.
2 − Continue to hold the short between R (2) to (1). After 5
seconds, STATUS LED will go from being continuously
lit to off.
3 − Continue to hold the short between R (2) to (1) beyond
ten seconds after STATUS LED has turned off. STA-
TUS LED will turn on, indicating that error codes have
been cleared.
4 − Remove R (2) to (1) short. STATUS LED will flash to in-
dicate normal operation.