TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
4/13
5.-Parameters
5. a Climatic 200
This controller is installed in EAC 0091 to EAC 0812 and EAR 0091 to 0431. This controller has the following map of standard
parameters.
/CHART 1/
/Logical parameters/
/Analogical parameters/
00H 2049
M/Pa_G01
G01-Cooling
setpoint
L/E
01H 2050
M/Pa_G02
G02-Heating
setpoint
L/E
02H 16468
M/MachineStatus
Machine_Status
L/E
80H
2052
Pa_H01
H01-Max setpoint in heating
L
81H
2053
Pa_H02
H02-Min setpoint in heating
L
82H
2054
Pa_H03
H03-Max setpoint in cooling
L
83H
2055
Pa_H04
H04-Min setpoint in cooling
L
84H 2079
Pa_H28
H28-HeatPump
selecction
L
85H
16415
ST1_MSB
Inlet Temp : MSB
L
86H
16416
ST1_LSB
Inlet Temp : LSB
L
87H
16417
ST2_MSB
Oulet Temp : MSB
L
88H
16418
ST2_LSB
Outlet Temp : LSB
L
89H
16419
ST3_MSB
Piping : MSB
L
8AH
16420
ST3_LSB
Piping : LSB
L
8BH
16421
ST4_MSB
Outdoor temp : MSB
L
8CH
16422
ST4_LSB
Outdoor temp : LSB
L
8DH 16483
Ana_Output
Analog
Output
L
8EH 16404
Digit_Input
Digit_Input
L
8FH 16469
Digit_Output
Digital
Output
L
90H 16492
Alarm_Auto_1
Alarm_Auto_1
L
91H 16493
Alarm_Auto_2
Alarm_Auto_2
L
92H 16494
Alarm_Auto_3
Alarm_Auto_3
L
93H 16495
Alarm_Manu_1
Alarm_Manu_1
L
94H 16496
Alarm_Manu_2
Alarm_Manu_2
L
95H 16497
Alarm_Manu_3
Alarm_Manu_3
L
96H 18433
Version
VERSION
L
5.b Detailed information about CLIMATIC 200 parameters
00H, 01H parameters (readable and writable)
This parameter defines the setpoint which the unit will function with , in cooling mode ( parameter 00 H ) or heating mode (
01H) .
¡Important : The value of the desired temperature has to be multiplied by 10!
Introduced values for this parameter have to be within the range between minimum setpoint ( Parameter 82 H cooling / 80 H
heating ) and the maximum setpoint ( Parameter 83 H cooling / 81 H heating ) .
¡Important: if the unit Works out of this range of temperatures , unit can work suffering critical damages !
If the unit is cooling only , there is no sense in using 01H parameter . This possibility can be restrained with the parameter 84 H
, which shows with the value 1 if the unit is heat pump version .
Example : H00=110 and H01=430 shows the cooling setpoint 11.0ºC and the heating setpoint 43.0ºC