Circuit Breaker Cover Installation 

If the air handler is installed in an unconditioned space the 

provided circuit breaker cover must be installed.

1 -   

Use isopropyl alcohol to clean the surface

 that 

the circuit breaker cover will be attached to.

FIGURE 7. Circuit Breaker Location

2 -   Remove paper backing from foam seal around 

perimeter of circuit breaker cover (figure 8).

CIRCUIT BREAKER COVER (BACKSIDE)

REMOVE PAPER BACKING FROM FOAM SEAL

FIGURE 8. Remove Paper Backing

3 -   Run a bead of clear silicone around the perimeter of 

the circuit breaker cover to seal any gaps between 

the cabinet access door and the circuit breaker 

cover.

4 -   Position the breaker cover over the air handler 

circuit breaker opening (figure 9).

CIRCUIT BREAKER COVER

FIGURE 9. Circuit Breaker Cover Installation

 IMPORTANT

Confirm  airtight  seal  between  breaker  cover  and  air 

handler access panel. Apply a thin silicone bead to the 

adhesive back seat to ensure airtight seal.
Failure to seal circuit breaker cover will allow warm 

moist air to be pulled into control panel which can create 

condensation to form on the circuit breaker and other 

electrical components within the control panel.

Electrical Connections 

 IMPORTANT

USE COPPER CONDUCTORS ONLY

NOTE

 – 

Refer to the nameplate on the air handler unit 

for minimum circuit ampacity and maximum over-current 

protection size.

 

The air handler units are provided with openings to be 

used with 1-1/2 inch trade size (1-31/32 inch diameter) 

conduit. A conduit reducer washer has been provided if 

you are installing a smaller sized conduit. 
For single-point power supply, refer to the nameplate on 

the single-point power supply accessory for minimum cir-

cuit ampacity and maximum over-current protection size. 

Select the proper supply circuit conductors in accordance 

with tables 310-16 and 310-17 in the National Electric 

Code, ANSI/NFPA No. 70 or tables 1 through 4 in the Ca-

nadian Electric Code, Part I, CSA Standard C22.1. Refer 

to figure 11 for typical air conditioner applications and fig

-

ure 12 for typical heat pump applications with an air han-

dler unit and electric heat section. 

Refer to figure 13 for typical system diagram for air han

-

dlers with electric heat sections. 

Make wiring connections 

1 -   

Disconnect the interface harness from the air 

handler unit. Connect the plug from the heater to 

the matching plug inside the air handler. 

NOTE

 – 

575V,  3-Phase,  60Hz  heaters  are  shipped  with 

a  line-voltage-to-460V  transformer.  This  transformer  pro

-

vides 460V power to the air handler motor and transformer 

only. Disconnect the 2-wire connector from the air handler 

interface harness and the air handler transformer. Connect 

the  575V to 460V transformer between these connections. 

See figure 10 for installation location. 

2 -   

If using a two-stage thermostat

—Remove 

the jumper between terminals 

W2

 and 

R

 of 

TB1

 

terminal block and connect the second-stage heat 

bulb lead to 

W2

.

3 -   

If using an outdoor thermostat

 — Remove the 

jumper between terminals 

W2

 and 

R

 of 

TB1

 terminal 

block and connect leads to 

W2

 and 

R

.

Summary of Contents for ECB27 Series

Page 1: ...ing Replace all parts and panels before operating Failure to do so can result in death or electrical shock Electric Heat Section The ECB27 series electric heat section provides field in stalled electr...

Page 2: ...vided in the bag assembly Cabinet Modifications for 460 Volt 3 Ton Models Modifications are necessary when an ECB27 10F G 15F G voltage 460 volt electric heat section is installed in a 460 volt 3 ton...

Page 3: ...plate for the specific size of electric heat section that you are installing Discard the unused piece of patch plate see figures 5 and 6 6 Secure the patch plate on the air handler access door IN DOW...

Page 4: ...B ECB27 5CB ECB27 6CB ECB27 8CB ECB27 9CB ECB27 12 5CB ECB27 15CB ECB27 20CB ECB27 25CB ECB27 10CB 3 Ph ECB27 15CB 3 Ph ECB27 20CB 3 Ph ECB27 25CB 3 Ph SIDE OF UNIT DISCARD BREAK AT THIS POINT DISCARD...

Page 5: ...ith 1 1 2 inch trade size 1 31 32 inch diameter conduit A conduit reducer washer has been provided if you are installing a smaller sized conduit For single point power supply refer to the nameplate on...

Page 6: ...using ECB27 heat section adjust the blower speed according to the size of electric heat and air handler unit The minimum blower setting for each air handler size with any heat sections in any applicat...

Page 7: ...PHASE ELECTRIC HEATERS ONLY STATS Y2 USED ONLY WHEN TWO SPEED COMPRESSOR IS USED HP21 COMMON USED ONLY ON SOME THERMOSTATS USING SERVICE LIGHT OPTION S54 WITH SOME ELECTRONIC THERMOSTATS MAY REQUIRE...

Page 8: ...Page 8 Unit Field Wiring Diagrams FIGURE 13 Typical Unit Diagram Air Handlers with Constant Torque Motors P Voltage 208 230V 1 Phase 60Hz...

Page 9: ...Page 9 FIGURE 14 Typical Unit Diagram Air Handlers with PSC Non Communicating Motors P Voltage 208 230V 1 Phase 60Hz...

Page 10: ...Page 10 FIGURE 15 Typical Unit Diagram Air Handlers with Variable Speed Communicating Motors P Voltage 208 230V 1 Phase 60Hz...

Page 11: ...Page 11 FIGURE 16 Typical Unit Diagram Air Handlers with Constant Torque Motors G Voltage 460V 3 phase 60Hz...

Page 12: ...ECB27 5 CB P 538002 01 ECB27 6 CB P 538002 01 ECB27 8 CB P 538003 01 ECB27 9CB P 538004 01 ECB27 12 5CB P 538005 01 ECB27 15CB P 538005 01 ECB27 20CB P 538006 01 ECB27 25CB P 538010 01 ECB27 8 Y 53800...

Reviews: