background image

PLANNING YOUR INSTALLATION 
 

PAGE 5 

CLEARANCES 

 

WARNING:  IT IS VERY IMPORTANT THAT YOU 

OBSERVE THE MINIMUM CLEARANCES. DO NOT 

STORE FIREWOOD WITHIN THIS CLEARANCE 

SPACE. FAILURE TO MAINTAIN CLEARANCES TO 

ALL COMBUSTIBLES MAY RESULT IN A HOUSE 

FIRE.

 

 

There are listed clearances for your fireplace insert, 

which were determined in a Laboratory testing and 

must be maintained. 

 

Stove top to mantel: 

 

27" (686 mm) 

Stove top to trim: 

 

16" (406 mm) 

Stove side to trim: 

 

6" (152 mm) 

Stove side to sidewall:    

 6" (152 mm) 

 

 

 

 

 

For installation with a combustible mantel or top trim, 
Part #16101 deflector must be installed.

 

 

DRAFT REQUIREMENTS

 

The appliance is merely one component of a larger sys-
tem. The other equally important component is the vent-
ing system. This is necessary for achieving the required 
flow of combustion air to the fire chamber and for safely 
removing unwanted combustion byproducts from the 
appliance.  If the venting system's design does not pro-
mote these ends, the system may not function properly. 
Poorly functioning venting systems may create per-
formance problems as well as be a safety hazard (i.e. 
an oversized chimney may result in less than optimum 
performance. Installations into a large, masonry chim-
ney may require a liner to improve performance). A 
draft test should read greater than .04' W.C. (inches 
water column) and less than .08" W.C.  
 

American National Standards Institute ANSI/NFPA 211-92, 
draft 1-7: A chimney or vent shall be so designed and con-
structed to develop a flow sufficient to completely remove all 
flue and vent gases to the outside atmosphere. The venting 
system shall satisfy the draft requirements of the connected 
appliance in accordance with the manufacturer’s instructions.

 

 

PROVIDE ADEQUATE AIR FOR COMBUSTION

  

In well insulated and weather tight homes, it may be 
difficult to establish a good draft up your chimney. The 
poor draft is caused by a shortage of air in the house. 
To provide the needed air, crack a window on the wind-
ward side of the house. 
 

VENTILATION REQUIREMENTS 

 

THE FRESH AIR REQUIREMENTS OF THIS APPLI-
ANCE MUST BE MET WITHIN THE SPACE WHERE 
IT WILL BE INSTALLED. 

 
Ventilation is essential when using a solid fuel burning 
heater. The combustion process of this heater uses 
oxygen from inside the dwelling and it may be neces-
sary to open a window or install a vent to provide make-
up air into a dwelling that is well insulated (modern con-
struction standards have resulted in homes that are 
highly energy-efficient and that allow little heat loss and 
air transfer). Other appliances in the dwelling also con-
tribute to removing air from the dwelling (i.e. clothes 
dryers, exhaust fans, fireplaces, and other fuel burning 
appliances). If the available fresh air delivery in the 
dwelling is insufficient to support the demands of these 
appliances, problems can result (i.e. excessive negative 
pressure can develop in the dwelling which will affect 
the rate at which this appliance can draft. See 

Draft Re-

quirements

 on this page). 

 

Summary of Contents for EARTH STOVE 2800HT

Page 1: ...ODEL 2800HT RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE EPA CERTIFIED WOOD BURNING FIREPLACE INSERT THIS APPLIANCE MUST BE INSTALLED BY A QUALIFIED INSTALLER READ ENTIRE MANUAL THOROUGHLY BEFORE IN...

Page 2: ...er fluid or similar liq uids to start or freshen up a fire in this heater Keep all such liquids well away from the heater while it is in use 12 DO NOT OVERFIRE If heater or chimney con nector glows yo...

Page 3: ...ne Insulation pad and strips Place pad under top marble and strips under ash lip marble USING THIS MANUAL Please read and carefully follow all of the instructions found in this manual Please pay speci...

Page 4: ...thin the same room you must follow the requirements of your local code Check with your local building department for requirements in your area IMPORTANT THIS APPLIANCE IS NOT AP PROVED FOR INSTALLATIO...

Page 5: ...PA 211 92 draft 1 7 A chimney or vent shall be so designed and con structed to develop a flow sufficient to completely remove all flue and vent gases to the outside atmosphere The venting system shall...

Page 6: ...not alter the integrity or outer shell of the pre engineered fireplace cabinet in any way Venting Requirements for factory built fireplace The fireplace damper must be secured in the open po sition T...

Page 7: ...nry fireplace only installation into a factory built fireplace is not approved The fireplace damper must be secured in the open position The fireplace in sert must be installed with a continuous chimn...

Page 8: ...th into fireplace 15 3 4 400 mm FACTORY BUILT FIREPLACE REQUIREMENTS Note In Canada installation into a Factory Built Fireplace is not approved When installing the 2800HT into a high dome or low profi...

Page 9: ...of the baffle plate should be flush to the back wall of the firebox MARBLE Marble is a natural product and therefore each piece will have its own unique character Marble can be scratched so care shoul...

Page 10: ...e hearth leveling bolts will need to be installed not included with the hardware Use a 3 8 10 mm bolt with 2 nuts The bolt length should be at least 1 25 4 mm longer than needed Locate the leveling bo...

Page 11: ...ides of the flue outlet Use self tapping screws to secure in place Cut a 13 mm height and 19 mm width notch in the front of connector pipe liner or adapter that will attach to flue outlet Install conn...

Page 12: ...e blowers will turn on when the insert is hot and turn off when the insert is cool See Care and Operation Section Blower System on page 16 Blower System Controls Located on right side of door at botto...

Page 13: ...may get dirty A short hot fire 15 20 minutes will help clean off much of the normal buildup see Troubleshooting pages 19 20 A commercial glass cleaner designed for fireplace inserts is recommended for...

Page 14: ...AINTAIN A FIRE 1 Set the primary air control to the open position push in 2 Set the start up air control to the open position pull out 3 Build a fire directly on the firebrick covering the bot tom of...

Page 15: ...ctrical cord that must be electrically grounded per lo cal codes or NEC ANSI NFPA 70 latest edi tion Do not route the power cord under or in front of the appliance Blower System Controls Located on ri...

Page 16: ...s Logs that are 5 127 mm diameter across or larger should be split in half three pieces if over 8 inches 203 mm and four pieces when over a foot across If the tree fell 2 to 4 years ago it still needs...

Page 17: ...nstall door CLEANING BLOWERS The blowers require inspection and cleaning annually to remove lint dust etc If there are pets in the dwelling the blowers should be cleaned at least twice a year To ac ce...

Page 18: ...agonally into lower firebox Remove baffle plate through door opening diagonally WARNING DO NOT OPERATE THE INSERT WITH OUT THE BAFFLE PLATE PROPERLY INSTALLED THIS WILL VOID WARRANTY In the event of a...

Page 19: ...ceiling fan with a winter summer switch 4 The area to heat is too large square foot heating estimates are based on average climates and home design 5 There is an obstruction in the chimney 6 The chim...

Page 20: ...re this may result in improper operation of appliance i e wont maintain fire unless fuel door is left open See below Overfiring Caused From Improper Op eration on this page Overfiring Caused From Impr...

Page 21: ...e 8 10 hours Fuel capacity 50 60 lbs 23 27 kg Firebox size cubic feet 2 9 c f 884 cubic mm Maximum Burn Rate 74 100 BTU EPA BTU Range 11 500 46 700 BTU EPA Efficiency 63 Emissions Rate grams hour 4 5...

Page 22: ...28 Rheostat W Connectors Knob Not Included p n 10050087 10050087 Rheostat Knob 410 270 Rocker Switch On Off Switch 11565 Disc Fan F110 20F 60T12 410 265 Terminal Block Small 410 260 Terminal Block Lar...

Page 23: ...nt parts contact Lennox Hearth Products 1110 West Taft Avenue Orange CA 92865 PAGE 23 Part No Description MS2805 Marble Set Green Also requires 1 each 1053 4 each 1051 1053 Cerawool Pad For Marble req...

Page 24: ...COMPONENT DIAGRAMS Model 2800HT PAGE 24 FIREBRICK 1 THICK AIR CONTROLS FIREBOX PARTS DOOR ASSEMBLY HANDLE ASSEMBLY...

Page 25: ...be handled using an off set adapter it aligns starter pipe with flue Actual Appearance Masonry Fireplace Kit This header insulation kit is required when installing the insert into a masonry fireplace...

Page 26: ...SAFETY LISTING LABEL PAGE 26...

Page 27: ...EPA LABEL PAGE 27...

Page 28: ...28 OWNERSHIP RECORDS Dealer s Name Dealer s Address City State Zip Code Serial Number Date of Purchase Date Installed Notes SERVICE AND MAINTENANCE LOG Service Service Service Date Technician Descrip...

Page 29: ...1110 West Taft Avenue Orange CA 92865...

Reviews: