background image

LV-FS-2DC-IOM-

20.04-E

e-

Lite

FLOOR STANDING UNIT

Installation and Operation Manual

Summary of Contents for e-Lite

Page 1: ...LV FS 2DC IOM 20 04 E e Lite FLOOR STANDING UNIT Installation and Operation Manual...

Page 2: ......

Page 3: ...er installa tion may cause the air conditioner to drop leading to accidents Make sure a standalone circuit is used for the power supply All electrical parts must comply with the local laws and regulat...

Page 4: ...g to suffocation 11 The appliance shall not be installed in the laundry Accessories Verify that the air conditioner includes the following accessories Name Installation Manual Insulation piping two ki...

Page 5: ...onment Square bar material Beam Ceiling Lifting bolt Figure 3 1 Wooden structure Secure the square rod on the beam to set the lifting bolts Figure 2 3 Covered Figure 2 2 Uncovered bottom return air Fi...

Page 6: ...stall 1 Dismantle the panel and follow the instructions described in the following diagram to remove the structure and fix the screws Figure 3 6 B A C Capacity kW 2 2 2 8 3 6 4 5 5 6 8 0 A mm B mm 120...

Page 7: ...5 6 4 12 7 12 7 15 9 C mm 725 925 1225 2 2 2 8 3 6 4 5 5 6 8 0 C Dimensions of unit Capacity kW Table 3 3 Figure 3 11 Figure 3 12 Figure 3 13 Liquid end of refrigerant piping A Gas end of refrigerant...

Page 8: ...ot let air or other gases enter the refrigeration circuit If the refrigerant leaks during installation make sure you fully ventilate the room Use two wrenches when you install or dismantle the piping...

Page 9: ...ject 500 1000 ml of water into the water pan 2 Verify that the water discharge piping outlet discharges water properly and check for water leakages at each joint 5 2 Water Discharge Test 6 When connec...

Page 10: ...nits electrical characteristics Capacity IFM Hz Volts MCA MFA kW FLA 2 8kW 2 2kW 50 50 60 220 240 15 0 49 0 55 0 55 0 55 0 85 1 4 1 4 15 4 5kW 15 5 6kW 15 7 1kW 15 8 0kW 15 15 Power supply 3 6kW 0 1 0...

Page 11: ...system are not controlled by the centralized controller The system can connect up to 64 indoor units address 0 63 at the same time Each indoor unit can only have one address DIP switch in the system...

Page 12: ...is the same as the rated voltage of the air conditioner No obstacles at the air inlet and outlet of the indoor and outdoor units Cut off valves for the gas and liquid ends of the outdoor unit are ope...

Page 13: ...t place vases or other liquid containers on the unit or in places where liquid could drip onto it Water or other liquids that come into contact with the unit can lead to electric shocks or fires Do no...

Page 14: ...ust the air out direction Air Intake Intakes room air Air intake Intake room air here Air out air out louver Adjust the air out direction Feet Lift up the air conditioner 9 Part Names The figure shown...

Page 15: ...Unit state Digital display Standby Shutting down Operation indicator flashes slowly All indicators off Operation indicator on Operation Normal operation Cold draft prevention or outdoor unit defrosti...

Page 16: ...tioner ensure it is powered off Check that the wiring is undamaged and connected Use a dry cloth to wipe the indoor unit and remote controller A wet cloth may be used to clean the indoor unit if it is...

Page 17: ...rom the remote controller Symptom 2 The unit emits white mist White mist is generated and emitted when the unit starts to operate in a very humid environment This phenomenon will stop once the humidit...

Page 18: ...ant leak has occurred Low heating effect Doors or windows are not completelyclosed Close doors and windows Arrange for a professional technician to check the following A refrigerant leak has occurred...

Page 19: ...a certain time No receiving soundfrom the indoor unit whenthe ON OFF button is pressed Check whether the MODE indicated on the display is AUTO Check whether the MODE indicated on the display is DRY A...

Page 20: ...Line loosened or broken w The electronic expansion valve in stuck w Outdoor unit error Ed w Outdoor unit error Water level error EE w Water level float stuck w Water level switch not connected proper...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...and dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause property damage or personal injury Ins...

Reviews: