LNX15-574.2

Kit Installation Instructions

(For Non-Condensing Models)

4.  Assemble the extended vent kit assembly (tee, tee cap, 

vent pipe, vent pipe clamp support bracket, and vent cap) 

as shown in Figure 3.3.  Note the following:
• 

Do not tighten the vent extension support bracket(s) 

yet. That will be tightened in a later step.

• 

While most B-vent components lock together when 

joined, it is recommended that the joints also be 

secured with the sheet metal screws provided.  Drill (3) 

1/8” pilot holes around the circumference of each joint 

and secure with the included screws.

1.  Remove the standard power exhaust vent terminal(s) from 

the unit casing by removing the sheet metal mounting 

screws.  Refer to Figure 3.1.

2.  Remove any remaining caulk that is on the casing from 

removing the vent terminal(s).

3.  Mount the extended vent collar(s) and collar gasket(s) 

to the casing using (4) self-tapping sheet metal screws 

included for each collar.  The collar(s) should be centered 

over the gas furnace vent outlet opening(s) so as to not 

block any portion of the vent outlet opening(s).  Refer to 

Figure 3.2.

EXTENDED VENT KIT INSTALLATION - 

NON-CONDENSING

THIS SECTION APPLIES TO ONLY KITS FOR 

NON-CONDENSING FURNACE OPTIONS.

REVIEW THE INFORMATION ON PAGE 2 

TO CONFIRM THE PROPER KIT. IF THE KIT 

TO BE INSTALLED IS FOR A CONDENSING 

FURNACE, PROCEED TO PAGE 4.

REVIEW BEFORE PROCEEDING

Gas Furnace

Vent Outlet

Remove vent terminal(s).

- B-Cabinet units have one terminal

- C-Cabinet units have two terminals

- D-Cabinet units have two or four terminals

Figure 3.1

Remove Standard Power Exhaust Vent Terminal(s)

Gas Furnace

Vent Outlet

(4) Screws for each Vent Collar

     - B-Cabinet units have one collar

     - C-Cabinet units have two collars

     - D-Cabinet units have two or four collars

Include Gasket between

Vent Collar and unit casing

Side view showing

collars centered on

 outlet openings

Figure 3.2 – Extended Vent Flue Collar Installation

Installed Extended Vent Kit(s)

 - B-Cabinet units have one

 - C-Cabinet units have two

 - D-Cabinet units have two or four

Vent Extension

Support Brackets

Figure 3.3 – Extended Vent Kit Installed

5.  Place a bead of high temperature RTV caulk (by others) 

around the exhaust collar where it will mate with the vent 

kit tee.  Fit the extended vent kit assembly to the exhaust 

collar installed on the unit casing, as shown in Figure 3.3.  

Verify that the vent assembly is vertically plumb.  Drill (3) 

1/8" diameter bite holes through the tee and into the flue 

collar, equally spaced around the circumference of the tee. 

Using (3) sheet metal screws provided, securely fasten the 

tee to the collar.

6.  Position the extended vent support bracket on the unit 

casing, several inches below the bottom edge of the roof 

panel.  Drill (2) 1/8" diameter bite holes through the casing 

panel and fasten the bracket using the sheet metal screws 

provided.

7.  Attach the vent pipe clamp support bracket to the extended 

vent support bracket with (2) self-tapping sheet metal 

screws.

8.  With the brackets secured, tighten the clamp around the 

vent pipe.  Drill (3) 1/8" diameter bite holes through the 

vent pipe and into the tee. Equally space the holes around 

the circumference of the vent pipe. Using (3) sheet metal 

screws, securely fasten the vent pipe to the tee.

9.  Caulk the joint around the exhaust collar where it attaches 

to the unit casing with high temperature RTV caulk (by 

others).

10.  The installation is complete.