506228−01 05/09
Page 20
Humidification
(continued)
USER SETTINGS
BASIC & PRECISION
if set up by the installer settings for BASIC or
PRECISION, this adjustment controls the relative humidity (RH) be-
tween 15 and 45%.
Scroll to HUMIDITY SETTINGS; press ENTER. Press the box below
HUMIDIFY.
HUMIDITY MODE
HUMIDIFY
DEHUMIDIFY
|
|
Use up/down arrows to change the humidity setpoint (between 15 and
45%); press SAVE.
HUM SETPOINT
DEFAULT (45%)
4O%
DEWPOINT
if set up by the installer settings for dew point, this adjust-
ment (only when in heating mode) will change the humidification set-
point based on the outdoor temperature and a user−defined dew point
adjustment setting. When humidifying, if condensation forms on the
windows, the dew point should be adjusted in the range of −15 to −5%; if
the home feels dry, set dew point upward in the range of +5 to +15%.
Scroll to HUMIDITY SETTINGS; press ENTER. Press the box below
HUMIDIFY.
HUMIDITY MODE
HUMIDIFY
DEHUMIDIFY
|
|
Use up/down arrows to change the dew point (b15 and −15%);
press SAVE.
DEW POINT ADJ
DEFAULT (O%)
−5%
NOTE − Dew point adj available only when outdoor sensor is attached.
OFF
if OFF selected in installer settings for both humidify and dehu-
midify, this message appears when HUMIDITY SETTING is pressed:
HUMIDITY MODES OFF
If OFF is selected by the installer settings for HUMIDIFY but DE-
HUMIDIFY is on, the dehumidification menu appears (this setpoint ad-
just has NO effect on humidification):
DEHUM SETPOINT
DEFAULT (5O%)
45%