BLOWER DATA CHA16 Cont
CHA16-036 BLOWER PERFORMANCE
@ 230 VOLTS (With Down-Flow Air Openings)
External Static
Air Volume at Various Blower Speeds
External Static
Pressure
High
MediumĆ
High
MediumĆ
Low
Low
in. w.g.
Pa
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
0
0
1415 670 1350 635 1135 530 915 430
.05
12
1395 660 1335 630 1125 530 905 425
.10
25
1375 650 1315 620 1115 525 895 420
.15
37
1360 640 1290 610 1110 525 890 420
.20
50
1355 640 1275 600 1105 520 885 420
.25
62
1325 625 1255 590 1095 515 875 415
.30
75
1310 620 1235 585 1085 510 865 410
.40
100
1265 595 1195 565 1060 500 845 400
.50
125
1220 575 1155 545 1020 480 825 390
.60
150
1170 550 1105 520
975
460 785 370
.70
175
1115 525 1045 495
925
435 725 340
.75
185
1085 510 1010 475
895
420 685 325
NOTE Ċ For 208v unit operation, derate air volume by 7%. All air data is meaĆ
sured external to the unit with dry coil and without air filter.
CHA16-036 BLOWER PERFORMANCE
@ 230 VOLTS (With Horizontal Air Openings)
External Static
Air Volume at Various Blower Speeds
External Static
Pressure
High
MediumĆ
High
MediumĆ
Low
Low
in. w.g.
Pa
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
0
0
1490 705 1460 690 1145 540 920 435
.05
12
1470 695 1440 680 1135 535 910 430
.10
25
1450 685 1420 670 1125 530 900 425
.15
37
1435 675 1395 660 1120 530 895 420
.20
50
1430 675 1375 650 1115 525 890 420
.25
62
1400 660 1355 640 1105 520 880 415
.30
75
1380 650 1335 630 1095 515 870 410
.40
100
1335 630 1285 605 1070 505 850 400
.50
125
1285 605 1235 585 1030 485 830 390
.60
150
1235 585 1195 565
985
465 790 375
.70
175
1185 560 1140 540
935
440 730 345
.75
185
1160 545 1110 525
905
425 690 325
NOTE Ċ All air data is measured external to the unit with dry coil and without air filter.
CHA16-036 BLOWER PERFORMANCE
@ 460/575 VOLTS (With Down-Flow Air Openings)
External Static
Air Volume at Various Blower Speeds
External Static
Pressure
High
Medium
Low
in. w.g.
Pa
cfm
L/s
cfm
L/s
cfm
L/s
0
0
1625
765
1465
690
1100
520
.05
12
1600
755
1445
680
1100
520
.10
25
1570
740
1420
670
1100
520
.15
37
1555
735
1395
660
1095
515
.20
50
1525
720
1385
655
1090
515
.25
62
1485
700
1365
645
1075
505
.30
75
1465
690
1340
630
1070
505
.40
100
1400
660
1285
605
1035
490
.50
125
1335
630
1235
585
1005
475
.60
150
1260
595
1165
550
955
450
.70
175
1170
550
1085
510
875
415
.75
185
1100
520
1045
495
815
385
NOTE Ċ All air data is measured external to the unit with dry coil and without air filter.
CHA16-036 BLOWER PERFORMANCE
@ 460/575 VOLTS (With Horizontal Air Openings)
External Static
Air Volume at Various Blower Speeds
External Static
Pressure
High
Medium
Low
in. w.g.
Pa
cfm
L/s
cfm
L/s
cfm
L/s
0
0
1710
805
1590
750
1105
520
.05
12
1685
795
1565
740
1105
520
.10
25
1655
780
1535
725
1105
520
.15
37
1630
770
1510
715
1100
520
.20
50
1610
760
1490
705
1095
515
.25
62
1570
740
1470
695
1085
510
.30
75
1540
725
1445
680
1075
505
.40
100
1475
695
1385
655
1040
490
.50
125
1405
665
1330
630
1010
475
.60
150
1335
630
1260
595
960
455
.70
175
1240
585
1185
560
885
420
.75
185
1180
555
1150
545
825
390
NOTE Ċ All air data is measured external to the unit with dry coil and without air filter.
CHA16-048 BLOWER PERFORMANCE
@ 230 VOLTS (With Down-Flow Air Openings)
External Static
Air Volume at Various Blower Speeds
External Static
Pressure
High
MediumĆ
High
MediumĆ
Low
Low
in. w.g.
Pa
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
0
0
2065 975 1715 810 1515 715 1305 615
.05
12
2055 970 1705 805 1505 710 1300 615
.10
25
2040 965 1690 800 1495 705 1300 615
.15
37
2020 955 1680 795 1485 700 1295 610
.20
50
2000 945 1665 785 1475 695 1290 610
.25
62
1975 930 1650 780 1470 695 1285 605
.30
75
1950 920 1635 770 1450 685 1280 605
.40
100
1885 890 1600 755 1425 670 1260 595
.50
125
1810 855 1565 740 1395 660 1225 580
.60
150
1730 815 1525 720 1360 640 1175 555
.70
175
1645 775 1600 755 1320 625 1110 525
.75
185
1600 755 1455 685 1295 610 1070 505
NOTE Ċ For 208v unit operation, derate air volume by 7%. All air data is meaĆ
sured external to the unit with dry coil and without air filter.
CHA16-048 BLOWER PERFORMANCE
@ 230 VOLTS (With Horizontal Air Openings)
External Static
Air Volume at Various Blower Speeds
External Static
Pressure
High
MediumĆ
High
MediumĆ
Low
Low
in. w.g.
Pa
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
0
0
2140 1010 1785 840 1535 725 1305 615
.05
12
2115 1000 1770 835 1530 720 1300 615
.10
25
2090 985 1755 830 1520 715 1295 610
.15
37
2070 975 1745 825 1510 715 1290 610
.20
50
2045 965 1730 815 1500 710 1285 605
.25
62
2020 955 1715 810 1490 705 1280 605
.30
75
1995 940 1700 800 1480 700 1275 600
.40
100
1935 915 1665 785 1460 690 1260 595
.50
125
1875 885 1630 770 1430 675 1235 585
.60
150
1800 850 1585 750 1400 660 1205 570
.70
175
1710 805 1530 720 1370 645 1170 550
.75
185
1655 780 1495 705 1355 640 1150 545
NOTE Ċ For 208v unit operation, derate air volume by 7%. All air data is meaĆ