• 13 •
l/h
kPa
kW
kW
kW
10 °C
2150
25
---
---
---
13,59
3,39
3070
40
---
---
---
13,99
3,43
4390
60
---
---
---
14,26
3,46
15 °C
2150
25
16,02
6,41
0,67
15,06
3,54
3070
40
16,20
6,67
0,67
15,49
3,58
4390
60
16,31
6,89
0,67
15,80
3,61
20 °C
2150
25
15,49
5,56
0,68
16,54
3,66
3070
40
15,67
5,79
0,67
17,00
3,70
4390
60
15,79
5,98
0,67
17,35
3,72
25 °C
2150
25
14,92
4,79
0,68
18,04
3,76
3070
40
15,10
5,00
0,68
18,52
3,79
4390
60
15,23
5,17
0,68
18,92
3,81
30 °C
2150
25
14,32
4,11
0,70
---
---
3070
40
14,50
4,30
0,69
---
---
4390
60
14,63
4,44
0,69
---
---
35 °C
2150
25
13,68
3,51
0,71
---
---
3070
40
13,87
3,69
0,70
---
---
4390
60
14,00
3,80
0,70
---
---
40 °C
2150
25
13,01
3,01
0,72
---
---
3070
40
13,20
3,17
0,72
---
---
4390
60
13,34
3,26
0,71
---
---
l/h
kPa
kW
kW
kW
10 °C
2540
30
---
---
---
15,55
3,36
3640
45
---
---
---
16,00
3,42
5200
70
---
---
---
16,28
3,45
15 °C
2540
30
18,55
5,86
0,66
17,25
3,56
3640
45
18,72
6,07
0,66
17,73
3,62
5200
70
18,81
6,25
0,66
18,07
3,65
20 °C
2540
30
18,03
5,15
0,67
18,98
3,75
3640
45
18,21
5,34
0,66
19,50
3,80
5200
70
18,31
5,50
0,66
19,89
3,84
25 °C
2540
30
17,44
4,51
0,67
20,74
3,91
3640
45
17,63
4,69
0,67
21,30
3,96
5200
70
17,75
4,83
0,67
21,75
4,00
30 °C
2540
30
16,80
3,93
0,68
---
---
3640
45
17,00
4,10
0,68
---
---
5200
70
17,14
4,22
0,68
---
---
35 °C
2540
30
16,09
3,43
0,69
---
---
3640
45
16,31
3,58
0,69
---
---
5200
70
16,46
3,68
0,69
---
---
40 °C
2540
30
15,33
3,00
0,70
---
---
3640
45
15,55
3,13
0,70
---
---
5200
70
15,72
3,21
0,70
---
---
AWH 015
2.450 m
3
/h
AWH 018
2.800 m
3
/h
AQUALEAN - AWC/AWH - MIL118E-1407 / 10-2013
GENERAL CHARACTERISTICS
1.8.- CAPACITY TABLES
Water
fl
ow
Water
pressure drop
AWC/AWH
COOLING CAPACITY
AWH
HEATING CAPACITY
Total capacity
EER
Sensible/Total
Total capacity
Total absorbed
power
W
ater inlet temperature
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Water
fl
ow
Water
pressure drop
AWC/AWH
COOLING CAPACITY
AWH
HEATING CAPACITY
Total capacity
EER
Sensible/Total
Total capacity
Total absorbed
power
W
ater inlet temperature
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Nominal operating conditions:
Exchanger air inlet temperature: 27ºC DB/19ºC WB in cooling mode and 20ºC WB
in heating mode.
(DW:dry bulb / WB:wet bulb)
For another working conditions use correction factor tables.
Nominal air
fl
ow rate
Nominal air
fl
ow rate