506257-01
Issue 1330
Page 2 of 29
INSTALLATION
Inspection of Shipment
Upon receipt of equipment, carefully inspect it for possible
shipping damage. If damage is found, it should be noted on
the carrier’s freight bill. Take special care to examine the unit
inside the carton if the carton is damaged. Any concealed
damage discovered should be reported to the last carrier
immediately, preferably in writing, and should include a
request for inspection by the carrier’s agent.
If any damages are discovered and reported to the carrier
DO NOT INSTALL THE UNIT
, as claim may be denied.
Check the unit rating plate to confirm specifications
are as ordered.
Location of Unit
Outdoor units operate under a wide range of weather
conditions; therefore, multiple factors must be considered
when positioning the unit. The unit must be positioned to
give adequate clearances for sufficient airflow and servicing.
Refer to Figure 1 for installation clearances.
• Place a sound-absorbing material, such as Isomode
under the unit if it will be installed in a location or position
that will transmit sound or vibration to the living area or
adjacent buildings..
General
Read this entire instruction manual, as well as the
instructions supplied in separate equipment, before
starting the installation. Observe and follow all
warnings, cautions, instructional labels, and tags.
Failure to comply with these instructions could result
in an unsafe condition and/or premature component
failure.
These instructions are intended as a general guide only
for use by qualified personnel and do not supersede any
national or local codes in any way. The installation must
comply with all provincial, state, and local codes as well as
the National Electrical Code (U.S.) or Canadian Electrical
Code (Canada). Compliance should be determined prior
to installation.
4SHP18LT condensing units use R410A which is an ozone-
friendly HFC refrigerant. The unit must be installed with a
matching indoor coil and line set. A filter drier approved for
use with R410A is installed in the unit.
IMPORTANT:
This product has been designed and
manufactured to meet ENERGY STAR criteria for energy
efficiency when matched with appropriate coil components.
However, proper refrigerant charge and proper air flow are
critical to achieve rated capacity and efficiency. Installation
of this product should follow the manufacturer’s refrigerant
charging and air flow instructions.
Failure to confirm
proper charge and airflow may reduce energy efficiency
and shorten equipment life.
When servicing or repairing HVAC components, ensure the
fasteners are appropriately tightened. Table 1 shows torque
values for fasteners.
Table 1
Torque Table
Figure 1
Installation Clearances
* A service clearance of 30” must be maintained on one of
the sides adjacent to the control box. Clearance to one
of the other three sides must be 36”. Clearance to one
of the remaining two sides may be 12” and the final side
may be 6”.
A clearance of 24” must be maintained between units.
48” clearance required on top of unit. Maximum soffit
overhang is 36”.
36”*
36”*
36”*
36”*
Fastener
Torque
Stem Caps
8 ft. lbs.
Service Port Caps
8 ft. lbs.
Sheet Metal Screws
16 in. lbs.
#8 Machine Screws
16 in. lbs.
#10 Machine Screws
28 in. lbs.
Compressor Bolts
90 in. lbs.