Page 2
SPECIFICATIONS
General
D t
Model Number (R−22)
CB26UH−018
CB26UH−024
CB26UH−030
CB26UH−036
Data
Model Number (R−410A)
CBX26UH−018
CBX26UH−024
CBX26UH−030
CBX26UH−036
Nominal tonnage
1.5
2
2.5
3
Connections
Suction/Vapor line (o.d.) − in. (mm) sweat
3/4 (19)
3/4 (19)
7/8 (22.2)
7/8 (22.2)
Liquid line (o.d.) − in. (mm) sweat
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
Condensate − in. (mm) fpt
(2) 3/4 (19)
(2) 3/4 (19)
(2) 3/4 (19)
(2) 3/4 (19)
Blower
Wheel nominal diameter x width − in. (mm)
10 x 6
(254 x 152)
10 x 6
(254 x 152)
11 x 8
(279 x 203)
11 x 8
(279 x 203)
Blower motor output − hp (W)
1/4 (187)
1/4 (187)
1/4 (187)
1/3 (249)
1
Filters
Size of filter − in. (mm)
16 x 20 x 1
(406 x 508 x 25)
16 x 20 x 1
(406 x 508 x 25)
18 x 20 x 1
(457 x 508 x 25)
18 x 20 x 1
(457 x 508 x 25)
ELECTRICAL DATA
Voltage − 1 phase (60 hz)
208/240V
208/240V
208/240V
208/240V
2
Maximum overcurrent protection (unit only)
15
15
15
15
3
Minimum circuit ampacity (unit only)
1.5
1.5
1.6
1.8
Shipping Data −1 package −
lbs. (kg)
129 (58)
131 (59)
148 (67)
148 (67)
SPECIFICATIONS
General
D t
Model Number (R−22)
CB26UH−042
CB26UH−048
CB26UH−060
Data
Model Number (R−410A)
CBX26UH−042
CBX26UH−048
CBX26UH−060
Nominal tonnage
3.5
4
5
Connections
Suction/Vapor line (o.d.) − in. (mm) sweat
7/8 (22.2)
7/8 (22.2)
7/8 (22.2)
Liquid line (o.d.) − in. (mm) sweat
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
Condensate − in. (mm) fpt
(2) 3/4 (19)
(2) 3/4 (19)
(2) 3/4 (19)
Blower
Wheel nominal diameter x width − in. (mm)
11 x 8
(279 x 203)
11 x 8
(279 x 203)
11−1/2 x 9
(292 x 229)
Blower motor output − hp (W)
1/3 (249)
1/2 (373)
1/2 (373)
1
Filters
Size of filter − in. (mm)
18 x 25 x 1
(457 x 635 x 25)
18 x 25 x 1
(457 x 635 x 25)
18 x 25 x 1
(457 x 635 x 25)
ELECTRICAL DATA
Voltage − 1 phase (60 hz)
208/240V
208/240V
208/240V
2
Maximum overcurrent protection (unit only)
15
15
15
3
Minimum circuit ampacity (unit only)
1.9
2.6
4.1
Shipping Data −1 package −
lbs. (kg)
172 (78)
177 (80)
190 (86)
1
Filter is not furnished and must be field supplied.
2
HACR type circuit breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167
°
F (75
_
C).
OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA
Model
−018
−024
−030
−036
−042
−048
−060
Circuit Breaker Cover Kit
93M85
93M85
93M85
93M85
Down−Flow Conversion Kit
12W61
12W61
12W61
12W61
Horizontal Support Frame Kit
56J18
56J18
56J18
56J18
Side Return Unit Stand
(Up−Flow Only)
45K32
45K32
45K32
45K32
Single Point Power Source Control Box
(for Electric Heat)
21H39
21H39
21H39
21H39
Wall Hanging Bracket Kit
(Up−Flow Only)
45K30
45K30
45K30
45K30