background image

Page 9

ACBX32CM SERIES

drain line does not required venting or a trap. Refer to

local codes.

Left−Hand

Discharge

Main Drain on Right

Auxiliary Drain on Left

Upflow or

Downflow

Right−Hand

Discharge

Figure 10. Drain Locations

Inspecting and Replacing Filters

IMPORTANT

Filter  access  panel  must  be  in  place  during  unit

operation.  Excessive warm air entering the unit may

result in water 

blow−off

 problems.

Each unit includes a 

factory−ins

talled filter. Note that filter

access door fits over access panel. Air leakage will occur if

access panel is placed over filter door.
Filters should be inspected monthly and must be cleaned

or replaced when dirty to assure proper furnace operation.
Reusable filters supplied with some units can be washed

with water and mild detergent. Some units are equipped

with  standard 

throw−away

  type  filters  which  should  be

replaced when dirty.

To replace filter:

1. Loosen  the  thumbscrews  holding  the  filter  panel in

place.

2. Slide  the  filter  out  of  the  guides  on  either  side  of

cabinet.

3. Insert new filter.
4. Replace panel.

See table 2 for replacement filter sizes.

Table 2. Filter Dimension

Unit Model No.

Filter Size Inches (mm)

−136

20 x 22 (508 x 559)

−14

8 and

 −

1

6

0

20 x 24 (508 x 

61

0)

Making Electrical Connections

WARNING

USE COPPER CONDUCTORS ONLY.
Run 24V Class II wiring only through specified low

voltage  opening.  Run  line  voltage  wiring  only

through specified  high  voltage  opening.  Do  not

combine voltage in one opening.

Wiring must conform to the current National Electric Code

ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA

Standard  C22.1,  and  local  building  codes.  Refer  to

following  wiring  diagrams.  See  unit  nameplate  for

minimum  circuit  ampacity  and  maximum  overcurrent

protection size.
Select  the  proper  supply  circuit  conductors  in

accordance  with  tables  310

1

6

  and  310

17  in  the

National Electric Code, ANSI/NFPA No. 70 or tables 1

through 4 in the Canadian Electric Code, Part  I, CSA

Standard C22.1.
This unit is provided with knockouts for conduit. Refer to

figure 15 for unit schematic wiring diagram. Refer to

figures 14 through 13 for typical field wiring.
Separate  openings  have  been  provided  for  24V  low

voltage and line voltage. Refer to the dimension illustration

for specific location.

Summary of Contents for ACBX32CM

Page 1: ...LLATION INSTRUCTIONS ACBX32CM Units AIR HANDLER 506316 01 11 16 Table of Contents ACBX32CM Upflow Downflow Unit Dimensions 2 ACBX32CM Horizontal LH RH Unit Dimensions 3 3 n o i t a m r o f n I l a r e...

Page 2: ...o r F Blower PIPING PLATE DETAIL FOR UPFLOW AND DOWNFLOW POSITIONS A C B 11 1 16 281 D F E LIQUID LINE SUCTION LINE CONDENSATE DRAINS 2 HORIZONTAL Coil 3 4 19 3 4 19 5 8 16 5 8 16 1 25 5 8 16 1 3 4 4...

Page 3: ...1 25 1 25 11 1 16 281 PIPING PLATE DETAIL LIQUID LINE SUCTION LINE 2 51 1 1 8 29 5 3 8 137 4 3 8 111 PIPING PLATE DETAIL Horizontal Position Left Hand Air Discharge Top View Front View 3 4 19 End Vie...

Page 4: ...AIR HANDLER UNIT The ACBX32CM air handler unit consists of two sections which are shipped assembled from the factory If necessary the unit may be disassembled to facilitate setting the unit Follow the...

Page 5: ...opening is fully open and free of any debris Also check to make sure that no debris has fallen into the drain pan during installa tion that may plug up the drain opening 3 Rotate the drain pan 180 fro...

Page 6: ...to downflow ACBX32CM unit circuit breakers must be rotated 180 to the UP position See AECB29 installation instructions for more details NOTE If downflow application is required order Allied downflow k...

Page 7: ...ed refrigerant lines see the piping section of the Allied Commercial Refrigerant Piping Design and Fabrication Guidelines Corp 0912 L5 AIR HANDLER UNIT SUCTION LINE LIQUID LINE Figure 8 Brazing Connec...

Page 8: ...sate Drain Before connecting drain line s check drain hole s to verify that drain opening is fully open and free of any debris Also check to make sure that no debris has fallen into the drain pan duri...

Page 9: ...Insert new filter 4 Replace panel See table 2 for replacement filter sizes Table 2 Filter Dimension Unit Model No Filter Size Inches mm 136 20 x 22 508 x 559 148and 160 20 x 24 508 x 610 Making Electr...

Page 10: ...Electric Heat W1 O Y1 R L T R L T SERVICE LIGHT THERMISTOR Y2 Y2 2ND STAGE COMPRESSOR 1 2 3 4 5 6 COMMON ELECTRIC HEAT REVERSING VALVE COMPRESSOR POWER 1 4 7 3 6 9 LINE VOLTAGE FIELD INSTALLED CLASS...

Page 11: ...ED ONLY ON SOME THERMOSTATS Y2 USED ONLY WHEN TWO SPEED COMPRESSOR IS USED HP21 AMBIENT COMPENSATING THERMISTOR CONNECTION USED ONLY ON SOME THERMOSTATS LINE VOLTAGE FIELD INSTALLED CLASS 2 VOLTAGE FI...

Page 12: ...Page 12 506316 01 11 16 Figure 15 Typical Wiring Diagram Single Phase...

Page 13: ...ation or field provided material e g Armaflex Permagum or equivalent Any of the previously mention materials may be used to seal around the main and auxiliary drains and around open areas of electrica...

Page 14: ...1055 495 230 1190 560 280 1475 695 455 25 60 1060 500 220 1185 560 275 1450 685 440 30 75 1050 495 215 1175 555 375 1415 670 430 40 100 1005 475 290 1135 535 325 1335 630 400 50 125 915 430 255 1060...

Page 15: ...5 515 1870 880 590 15 35 1750 825 510 1850 875 585 20 50 1720 815 500 1825 860 575 25 60 1685 795 490 1790 845 560 30 75 1645 775 480 1745 825 545 40 100 1530 720 450 1625 765 505 50 125 1380 650 420...

Page 16: ...inside surface temperature of the cabinet The temperature humidity difference between the inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads t...

Reviews: