Figure 6.
Equipment in Confined Space - All Air from
Outside
(Inlet Air from Crawl Space and Outlet Air to
Ventilated Attic)
When communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1
square inch (645 mm²) per 2,000 Btu (.56 kW) per hour of
the total input rating of all equipment in the enclosure. See
Figure 7.
Equipment in Confined Space - All Air from
Outside
(All Air through Ventilated Attic)
Figure 8.
Equipment in Confined Space - All Air from
Outside
Figure 9.
Equipment in Confined Space
(Inlet Air from Ventilated Attic and Outlet Air to
Outside)
NOTE
-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
Roof Terminated
Exhaust Pipe
Furnace
*Intake Debris
Screen
(Provided)
* See Maximum Vent Lengths table
Figure 10.
Equipment in Confined Space
(Inlet Air from Ventilated Crawlspace and Outlet Air to
Outside)
NOTE
-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
Roof Terminated
Exhaust Pipe
Furnace
Ventilation
Louvers
(Crawl space)
*Intake Debris Screen Provided)
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
* See Maximum Vent Lengths table