background image

# 48369K005

Page 7

OPERATION

Sequence of Operation

Cooling

When the thermostat is in the cooling mode, the O circuit is
powered which energizes the reversing valve. Upon cooling
demand, the thermostat closes circuit R and Y. Closing R
and Y closes the unit contactor, starting the compressor and
outdoor fan. The thermostat automatically closes R to G
circuit which also brings on the indoor blower at the same
time. Upon satisfying cooling demand, the thermostat will
open the above circuits and open the main contactor,
stopping the compressor and outdoor fan. If the unit is
equipped with a delay timer, the blower will continue to
operate for 90 seconds which improves system efficiency.

Heating

Upon heating demand, the thermostat closes circuit R to Y,
which closes the unit contactor, starting the compressor and
outdoor fan. The reversing valve is not energized in the heating
mode. The thermostat again automatically brings on the indoor
fan at the same time. Upon satisfying heating demand, the
thermostat opens above circuits and stops unit operation.

Defrost System

The defrost system includes two components: the defrost
thermostat and the defrost control.

Defrost Thermostat

The defrost thermostat is located on the liquid line between
the check/expansion valve and the distributor. When the
defrost thermostat senses 42°F or cooler, the thermostat
contacts close and send a signal to the defrost control
board to start the defrost timing. It also terminates defrost
when the liquid line warms up to 70°F.

Defrost Control

The defrost control board includes the combined functions of
time/temperature defrost control, defrost relay, diagnostic LEDs
and terminal strip for field wiring connections (see Figure 8).

The control provides automatic switching from normal
heating operation to defrost mode and back. During the
compressor cycle (call for defrost), the control accumu-
lates compressor run time at 30, 60, 90 minute field-
adjustable intervals. If the defrost thermostat is closed
when the selected compressor run time interval ends, the
defrost relay is energized and the defrost begins.

Defrost Control Timing Pins

Each timing pin selection provides a different accumulated
compressor run time period during one thermostat run
cycle. This time period must occur before a defrost cycle
is initiated. The defrost interval can be adjusted to 30 (T1),
60 (T2), or 90 (T3) minutes. The defrost timing jumper is
factory installed to provide a 60-minute defrost interval. If

Defrost Control Board

Figure 8

Defrost Interval

Timing Pins

Diagnostic LEDs

24V TerminalStrip
Connections

High Pressure Switch

(optional)

Defrost Thermostat

Reversing Valve

Compressor Delay Pins

Test Pins

K1 Relay

K2 Relay

FAN

DS1

L

24V

P2

P5

O-OUT

DF

Y1-OUT

HI-PS

U1

U2

DS2

K3 Relay

P6

TST PS DF C

R

O Y1

C5

LO-PS

C2

P1

30
60

90

TEST

W1

C

L

R

Y1

O

Low Pressure Switch

(optional)

Summary of Contents for (2/4)SH13

Page 1: ...ion of this appliance must conform to the requirements of the National Fire Protection Association the National Electrical Code ANSI NFPA No 70 latest edition in the United States the Canadian Electri...

Page 2: ...es must also be observed The unit must not be installed with any ductwork in the outdoor air stream The outdoor fan is not designed to operate against any additional static pressure Location The unit...

Page 3: ...h a 3 4 FPT cou pling for condensate line connection Plumbing must conform to local codes Use a sealing compound on male pipe threads The condensate drain line must be properly trapped and routed to a...

Page 4: ...free from duct flange 3 Slide duct cover out the side duct opening Filters Air filters are to be used with this heating cooling unit Filters are not factory supplied in the unit However a filter frame...

Page 5: ...T OUTDOOR UNIT GROUND SCREW POWER WIRING 200 230 3 60 460 575 3 60 90 C MIN WIRE 24V CONTROL WIRING NEC CLASS 2 POWER WIRING TYPICAL WIRING CONNECTION 3 PHASE W1 W2 CAN BE USED TO STAGE ELECTRIC HEAT...

Page 6: ...test should be conducted with each appliance while the other appliances connected to the common venting system are not in operation 1 Seal any unused openings in the common venting system 2 Visually i...

Page 7: ...F or cooler the thermostat contacts close and send a signal to the defrost control board to start the defrost timing It also terminates defrost when the liquid line warms up to 70 F Defrost Control Th...

Page 8: ...optional can be connected to the HI PS terminals see Figure 8 on page 7 During a single demand cycle the defrost control will lock out the unit after the fifth time that the circuit is interrupted by...

Page 9: ...t conditions of 82 F outdoor and 80 F indoor dry bulb 67 F wet bulb If subcooling measured deviates from values found in Table 4 refrigerant charge should be adjusted accordingly for maximum performan...

Page 10: ...and outdoor fan and vent motors are permanently lubricated and require no maintenance Outdoor Coil Dirt and debris should not be allowed to accumulate on the outdoor coil surface or other parts in the...

Page 11: ...e Because the pressure switches are monitored only when Y1 Input is active the code for pressure switch open will not be seen when Y1 is off Instead the Normal Operation or Anti Short Cycle Lockout co...

Page 12: ...f and excludes all other warranties express or implied The warrantor does not authorize any person to provide any other warranty or to assume for it any further obligation in connection with the warra...

Reviews: