Page 18
IMPORTANT
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
capable of accurately measuring down to 50 microns.
WARNING
Possible equipment damage.
Avoid deep vacuum operation. Do not use compressors
to evacuate a system. Extremely low vacuum can cause
internal arcing and compressor failure. Damage caused
by deep vacuum operation will void warranty.
Evacuating the system of non-condensables is critical for
proper operation of the unit. Non-condensables are de-
fined as any gas that will not condense under tempera
-
tures and pressures present during operation of an air
conditioning system. Non-condensables and water suc-
tion combine with refrigerant to produce substances that
corrode copper piping and compressor parts.
Electrical
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the cur-
rent Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air han-
dler for low-voltage control power (24VAC - 40 VA mini-
mum).
WARNING
Electric Shock Hazard. Can cause injury or
death. Unit must be properly grounded in
accordance with national and local codes.
Line voltage is present at all components
when unit is not in operation on units with
single-pole contactors. Disconnect all remote
electric power supplies before opening
access panel. Unit may have multiple power
supplies.
Refer to the unit nameplate for minimum circuit ampacity, and maximum
fuse or circuit breaker (HACR per NEC). Install power wiring and properly
sized disconnect switch.
NOTE — Units are approved for use only with copper conductors.
Ground unit at disconnect switch or to an earth ground.
SIZE CIRCUIT AND INSTALL SERVICE
DISCONNECT SWITCH
NOTE — 24VAC, Class II circuit connections are made in the control
panel.
Install room thermostat (ordered separately) on an inside wall
approximately in the center of the conditioned area and 5 feet (1.5m) from
the floor. It should not be installed on an outside wall or where it can be
affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
INSTALL THERMOSTAT
SERVICE
DISCONNECT
SWITCH
MAIN FUSE BOX/
BREAKER PANEL
Summary of Contents for 16HPX Series
Page 27: ...Page 27 Wiring and Sequence of Operation FIGURE 15 Typical Unit Wiring 024 036 and 048 Units...
Page 28: ...Page 28 FIGURE 16 Typical Unit Wiring 060 Units...
Page 29: ...Page 29 FIGURE 17 Typical Factory Wiring 024 036 and 048 Units...
Page 30: ...Page 30 FIGURE 18 Typical Factory Wiring 060 Units...