Page 18
FIGURE 18
Step 1. Determine the desired
D
T
Measure entering air tempera-
ture using dry bulb (
A
) and wet bulb (
B
).
D
T
is the intersecting value
of
A
and
B
in the table (see triangle).
Step 2. Find temperature drop across coil
Measure the coil’s dry
bulb entering and leaving air temperatures (
A
and
C
). Temperature
Drop Formula: (
T
Drop
) =
A
minus
C
.
Step 3. Determine if fan needs adjustment
If the difference be-
tween the measured
T
Drop
and the desired
D
T
(T
Drop
–
D
T)
is within
+3º, no adjustment is needed. See examples: Assume
D
T
= 15 and
A
temp. = 72º, these
C
temperatures would necessitate stated ac-
tions:
Cº T
Drop
–
D
T
=
ºF
ACTION
53º
19
–
15
=
4
Increase the airflow
58º
14
–
15
=
−1
(3º range) no change
62º
10
–
15
=
−5
Decrease the airflow
Step 4. Adjust the fan speed
See indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and
D
T are 3º.
D
T
80
24 24 24 23 23 22 22 22 20 19 18 17 16 15
78
23 23 23 22 22 21 21 20 19 18 17 16 15 14
76
22 22 22 21 21 20 19 19 18 17 16 15 14 13
74
21 21 21 20 19 19 18 17 16 16 15 14 13 12
72
20 20 19 18 17 17 16 15 15 14 13 12 11 10
70
19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
Temp.
of air
entering
indoor
coil ºF
INDOOR
COIL
DRY BULB
DRY
BULB
WET
BULB
B
T
Drop
19º
A
Dry−bulb
Wet−bulb ºF
A
72º
B
64º
C
53º
air flow
air flow
All temperatures are
expressed in ºF
C − Pre− Charge Maintenance Checks
IMPORTANT
Use table 5 as a general guide when performing maintenance checks. This is not a procedure for charging the
unit (Refer to Charging / Checking Charge section). Minor variations in these pressures may be expected due
to differences in installations. Significant differences could mean that the system is not properly charged or that
a problem exists with some component in the system.
Table 5
Normal Operating Pressures − 10 & Vapor +5 PSIG*
14HPX−018
14HPX−024
14HPX−030
14HPX−036
14HPX−042
14HPX−048
14HPX−060
5
F (
5
C)**
Liquid / Vapor
Liquid / Vapor
Liquid / Vapor
Liquid/ Vapor
Liquid / Vapor
Liquid / Vapor
Liquid / Vapor
Cooling
65 (18)
226 / 140
233 / 137
238 / 138
220 / 138
223 / 125
231 / 136
243 / 136
70 (21)
244 / 141
252 / 138
263 / 139
236 / 140
241 / 130
248 / 139
263 / 137
75 (24)
263 / 142
271 / 140
279 / 139
256 / 141
261 / 134
271 / 140
282 / 138
80 (27)
283 / 143
292 / 141
299 / 140
276 / 142
282 / 138
291 / 142
306 / 139
85 (29)
302 / 144
314 / 142
324 / 141
298 / 143
302 / 139
312 / 143
327 / 140
90 (32)
328 / 145
338 / 143
340 / 142
321 / 144
326 / 140
335 / 144
351 / 141
95 (35)
351 / 146
361 / 145
375 / 145
344 / 144
349 / 141
359 / 145
376 / 142
100 (38)
376 / 147
387 / 146
397 / 145
369 / 146
374 / 142
384 / 146
401 / 143
105 (41)
402 / 148
412 / 147
424 / 147
394 / 147
399 / 143
411 / 148
426 / 145
110 (38)
430 / 149
441 / 148
454 / 150
421 / 148
428 / 145
439 / 149
452 / 146
115 (45)
465 / 150
471 / 151
485 / 150
449 / 149
455 / 146
468 / 150
484 / 148
Heating
60 (15)
346 / 139
352 / 138
338 / 137
350 / 134
373 / 139
355 / 130
351 / 117
50 (10)
323 / 117
331 / 114
334 / 112
331 / 117
363 / 117
336 / 113
333 / 105
40 (4)
306 / 98
304 / 99
312 / 93
313 / 97
348 / 97
315 / 88
316 / 88
30 (−1)
278 / 84
299 / 80
302 / 74
298 / 83
336 / 74
296 / 72
308 / 70
20 (−7)
273 / 66
283 / 66
280 / 53
284 / 66
322 / 64
286 / 64
300 / 61
*IMPORTANTThese are most−popular−match−up pressures. Indoor match up and indoor load cause
pressures to vary.
**Temperature of the air entering the outside coil (outdoor ambient temperature).