background image

Page 1

504,532M

*P504532M*

06/04

*2P0604*

2002 Lennox Industries Inc.

Dallas, Texas, USA

®

12HPB Outdoor Units

Lennox Merit

®

 Series 12HPB outdoor units are approved

and warranted only for installation with specially
matched indoor coils, line sets, and refrigerant control
devices as designated by Lennox. Refer to Lennox engi-
neering handbook for expansion valve (TXV) kits which
must be ordered separately.

Shipping and Packing List

 1 − Assembled 12HPB outdoor unit

Check unit for shipping damage. Consult last carrier imme-
diately if damage is found.

WARNING

Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person-
al injury or loss of life. Installation and service must
be performed by a qualified installer or service
agency.

IMPORTANT

The Clean Air Act of 1990 bans the intentional vent-
ing of refrigerant (CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarcera-
tion may be levied for noncompliance.

INSTALLATION
INSTRUCTIONS

12HPB Series Units

HEAT PUMP UNITS

2 through 5 tons
504,532M
06/04
Supersedes 04/04

Table of Contents

12HPB Outdoor Units

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . 

Shipping & Packing List

1

. . . . . . . . . . . . . . . . . . . . . . . . . 

General Information

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Unit Dimensions

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Setting the Unit

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Electrical

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Refrigerant Piping

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Refrigerant Metering Device

10

. . . . . . . . . . . . . . . . . . . . 

Manifold Gauge Set

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . 

Service Valves

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Leak Testing

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Evacuation

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Start−Up

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Charging

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

System Operation

16

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Defrost System

16

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Maintenance

18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Optional Accessories

18

. . . . . . . . . . . . . . . . . . . . . . . . . . 

Start−Up and Performance Check List

18

. . . . . . . . . . . . 

RETAIN THESE INSTRUCTIONS

FOR FUTURE REFERENCE

General Information

These instructions are intended as a general guide and do
not supersede national or local codes in any way. Authori-
ties having jurisdiction should be consulted before installa-
tion.

WARNING

This product and/or the indoor unit it is matched with
may contain fiberglass wool.

Disturbing the insulation during installation, mainte-
nance, or repair will expose you to fiberglass wool
dust. Breathing this may cause lung cancer. (Fiber-
glass wool is known to the State of California to
cause cancer.)

Fiberglass wool may also cause respiratory, skin,
and eye irritation.

To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.

Lennox Industries Inc.

P.O. Box 799900
Dallas, TX 75379−9900

Litho U.S.A.

Summary of Contents for 12HPB Series

Page 1: ...4 532M 06 04 Supersedes 04 04 Table of Contents 12HPB Outdoor Units 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Setting the Unit 3 Electrical 4 Refrigerant Piping 6 Refrigerant M...

Page 2: ...tion 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 compressor coil drain outlets around perimeter of base optional unit stand off kit 4 field installed B C A optional unit stand off kit 4 field in...

Page 3: ...to allow adequate drainage of defrost water and prevent ice buildup 3 In heavy snow areas do not locate the unit where drift ing will occur The unit base should be elevated above the depth of average...

Page 4: ...G Unit must be grounded in accordance with national and local codes Electric Shock Hazard Can cause injury or death 1 Install line voltage power supply to unit from a properly sized disconnect switch...

Page 5: ...power power common common 1st stage aux heat 1st stage aux heat indoor blower compressor Figure 5 R C W1 Y1 O G R C W1 W2 W3 G Outdoor Unit and Blower Unit Thermostat Designations with emergency heat...

Page 6: ...o the compressor Installing Refrigerant Line During the installation of any heat pump or a c system it is important to properly isolate the refrigerant lines to prevent unnecessary vibration Line set...

Page 7: ...Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve Woo...

Page 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 9: ...Line Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 9 Out...

Page 10: ...d line at the indoor coil Refrigerant Metering Device 12HPB units are used in check expansion valve systems only See the Lennox Engineering Handbook for approved TXV match ups and application informat...

Page 11: ...e wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger tight then an additional 1 6 turn To Open Service Valve 1 Remove stem cap with an adjus...

Page 12: ...r use oxygen to pressurize a refrigera tion or air conditioning system Oxygen will explode on contact with oil and could cause personal injury WARNING Danger of explosion Can cause equipment damage in...

Page 13: ...r port hose from vacuum pump Attach the manifold center port hose to a nitrogen cylin der with pressure regulator set to 150 psig 1034 kPa and purge the hose Open the manifold gauge valves to break th...

Page 14: ...which charg ing method to use Proceed with the appropriate charg ing procedure Weighing in the Charge TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant or if the outdoor ambient...

Page 15: ...erature to check liquid line tempera ture Verify the unit charge using the approach method 5 The difference between the ambient and liquid temper atures should match values given in table 6 If the val...

Page 16: ...ts An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode Emergency heat is usually used during an outdoor shut down but it should al...

Page 17: ...mode If the jumper is removed before an addi tional 5 second period has elapsed 7 seconds total the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed If th...

Page 18: ...lubrication is needed 3 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tabl...

Reviews: