Adjustments 

The mild weather pressure switch automatically resets; no
adjustments are required. The factory-set cut-out and cut-
in (reset) points are given in table 1.

Table 1

Cut-out and Cut-in (Reset) Points

Refrigerant

Cut-Out

Cut-in (Reset)

HCFC-22

375 psig (2551 kPa)

275 psig (1862 kPa)

HFC-410A

550 psig (3965 kPa)

425 psig (3102 kPa)

Figure 4. 13 and 14 Series Units Wiring Connections

Figure 5. XP17 Series Unit Wiring Connections (Earlier Version A175 Control)