Lennox Hearth Products RAVENNA RDV33 Installation And Operation Manual Download Page 24

24

SYMPTOM

PROBABLE CAUSE

CORRECTIVE ACTION

Thin black coating (soot) 

forms on the viewing 

glass, logs, or firebox

Improper log or ember 

placement

Improper air shutter 

setting

Not enough combus­

tion air

See 

Brick Panel and Log Set Installation on Pages 12 and 13

. If there is soot in one 

specific location, the glowing embers (rockwool) below this location needs to be ad­

justed. This can be done by pulling embers forward slightly. If the flames have soot tails, 

the shutter will need to be opened.

If sooting continues open air shutter (see 

Air Shutter Adjustment on Pages 14 and 15

).

Check for debris obstructing air flow in valve compartment under insert or in front of 

lower venting.

Humming or whistling 

coming from insert.

Normal operating noise

Obstructed orifice 

opening

See 

Quiet Operation on Page 19

. The noise may be reduced by slightly turning down the 

flame. Turning the flame down will reduce the heat output of the insert.

If noise is excessive or is “whistling” have your gas supplier check the regulator and 

orifices and replace if necessary.

A change in flame appear­

ance or burner operation.

A change in gas pres­

sure

Improper ember place­

ment

Have your gas supplier check for correct gas pressure (7" W.C. / po. C.E. [1.74 kPa] natu­

ral gas; 11" W.C. / po. C.E. [2.74 kPa] LP gas). 

NOTE:  NEVER BLOCK OR OBSTRUCT AIR 

INTAKE OR OUTLET VENTS.

See 

Brick Panel and Log Set Installation on Pages 12 and 13.

Spark igniter will not light 

pilot after repeated tries.

No gas supplied to unit 

or air in line

Defective igniter (no 

spark at electrode)

Defective or misaligned 

electrode at pilot (spark 

at electrode)

Check gas supply. To purge, hold in gas cock on valve for 1­2 minutes and try again.

Check for spark at electrode and pilot, if no spark and electrode wire is properly con­

nected, replace igniter and igniter wire.

Using a match, light pilot. If pilot lights, turn off pilot and trigger the igniter again. If pilot 

lights, an intermittent gas/air supply may be the problem, if longer purge will not light 

­ check gap between electrode and pilot ­ should be 1/8 inch (3 mm) to have a strong 

spark. If OK, replace pilot.

Pilot will not stay lit after 

carefully following lighting 

instructions.

Low gas inlet pressure

Defective thermopile

Defective automatic 

valve operator

Check inlet pressure and adjust pilot if necessary.

Be sure wire connections from thermopile are tight at gas valve terminals.

Either rocker switch or thermostat wires may be grounded. Remove wires from valve 

terminals. If pilot stays lit, trace switch wiring for a ground. May be grounded to insert or 

gas supply.

Check open circuit millivolt output of thermopile. Reading should be greater than 325mV. 

Also check thermopile wire for kinks that can cause loss of mV. Replace faulty thermopile 

if wire is okay and reading is less than 325mV.

Turn valve knob to “ON” and thermostat (if installed) to 90º. Millivolt meter should read 

greater than 100 mV. If reading is OK and burner does not turn on, replace gas valve 

(qualified service technician only).

Main burner will not burn. Pilot has gone out

Rocker switch, thermo­

stat, or wires defective

Thermopile may not be 

generating sufficient 

millivolts

See 

Lighting Instructions.

Disconnect rocker switch and thermostat wires at terminals 1 and 3 on valve. Jumper 

across from 1 to 3 with pilot lit. If burner comes on either rocker switch, thermostat, or 

wiring is not functioning.

Check thermopile with millivolt meter (see 

Maintenance and Servicing

), recheck symp­

tom #2.

TROUBLESHOOTING

NOTE:  When troubleshooting the gas control system, be sure the external gas shut off valve, located at the gas supply inlet is in 

the “ON” position.

IMPORTANT:  Call your gas supplier or plumber for additional help with any gas control problem.  Valve system troubleshooting 

should only be accomplished by a qualified service technician.

Summary of Contents for RAVENNA RDV33

Page 1: ...les instructions du fournis seur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur s par un installateur ou un service...

Page 2: ...bles 10 Insert Leveling 10 Installation 11 13 Venting Installation 11 Zero Clearance Fireplace Installation 12 Brick Panel and Log Set Installation 12 Surround Panels Installation 13 Face Installation...

Page 3: ...ller service agency or the gas supplier WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance voiding its warranty Any change to...

Page 4: ...onnected to a chimney or flue serving a separate solid fuel burning appliance These appliances are vented gas appliances Do not burn wood or other material in these appliances This appliance is only f...

Page 5: ...red quecontrolalachimenea verifiquequeelinterruptor opera la chimenea encendi ndola y apag ndola Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta enlasuperf...

Page 6: ...hall not be altered by the installation of the insert i e DO NOT BLOCK louvers or cooling air inlet or outlet ports circulating air chambers in a steel fireplace liner or metal heat circulator See Pag...

Page 7: ...recognized testing and certification laboratory to ANSI American National Standard Institute gas appliance safety standards This appliance has been tested and certified by OMNI Test Laboratories to AN...

Page 8: ...ng List 1 Insert Body with Burner Cassette 1 Set of Refractory Brick Panels 1 Log Set 1 Bag of Embers 1 Fasteners 6 slotted 1 4 truss screws 6 speed nuts 9 spring clips 3 plastic adhesive wire restrai...

Page 9: ...rfaces the faulty portion must be repaired or replaced prior to installing this appliance The factory built firebox must accept the insert withoutmodificationotherthanremovingbolted or screwed togethe...

Page 10: ...bove the appliance Paint or lacquer used to finish the mantel must be heat resistant in order to avoid discoloration The letters below E through J correspond to Figure 5 showing minimum clearancesrequ...

Page 11: ...place Figure 6b WARNING Direct VentFireplaceInsertVentRequirements Useliner listed to UL181 Factory made Air Ducts And Air Connec tors orUL1777 ChimneyLiners fortheAIRINTAKE Use liner listed to UL1777...

Page 12: ...ure des parois ou au fond de la chambre de combustion Cetorificedoit treobtur aumoyend isolantincombustible une fois la conduite de gaz en place The installer must mechanically attach the marking supp...

Page 13: ...rt two slotted 1 4 truss screws for each side surround panel and secure loosely 5 Fasten the top surround panel with the remaining two truss screws Tighten all six truss screws after adjusting the sur...

Page 14: ...e com ponents Verify that the tanks have step down regulators to reduce the pressure to safe levels LP and Natural Gas Supplies Your gas appliance is equipped from the factory for use with natural gas...

Page 15: ...LLUSTRATIONS ARE NOT TO SCALE Moving shutter bracket to the right will open shutter to the left will close shutter Figure 15a Figure 15b SHUTTER ADJUSTMENT DETAIL See Detail Shutter Adjustment Shutter...

Page 16: ...e le fonctionnement du foyer en le faisant basculerdeMarche Arr t etvice versa Nettoyez soigneusement la plaque murale de l interrupteur ou le thermostat mural pour liminer la poussi re et les traces...

Page 17: ...plier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by...

Page 18: ...our service technician or gas supplier 10 After pilot is lit turn gas control knob counterclockwise to ON Knob can only be turned to ON if the knob has popped out 11 To turn burner on turn ON OFF rock...

Page 19: ...gas valve and orifice may make a rushing or whistling noise If this noise is objectionable it can be reduced by turning down the flame Turning down the flame can reduce total heat output by more than...

Page 20: ...es to the appliance for example a rocker switch and a wall thermostat Additional switches may affect the system resistance and increase the chance of the burner not igniting Follow the instructions in...

Page 21: ...ER ADJUST THE PILOT untilafterthegaspressurehasbeencheckedandthesupplylineshave been completely bled this may take an hour or more when bleeding through the pilot All pilots are checked and burned at...

Page 22: ...lass is neo ceramic and alterna tive types must not be used NOTE BE CAREFUL NOT TO SPRAY COMMERCIAL GLASS CLEANER WITH AMMONIA ON GASKET AREA OF DOOR AM MONIA WILL DISSOLVE GASKET GLUE Glass Door Only...

Page 23: ...weennaturalgasandLPcanbeaccomplished by installing a conversion kit valve regulator and burner orifice Only a qualified service technician should perform the conversion Conversion Kit Please see instr...

Page 24: ...wire Using a match light pilot If pilot lights turn off pilot and trigger the igniter again If pilot lights an intermittent gas air supply may be the problem if longer purge will not light check gap b...

Page 25: ...Glowing Embers rockwool H3130 Firebox Door w Glass H5989 Hardware Package H5839 Log Set Support H5913 Hinge Right Double Door W Screen all Faces H5914 Hinge Left Double Door W Screen all Faces H5980 K...

Page 26: ...IC Black Nickel 75330 NAPA Black 75298 TUSCAN Black 75332 NAPA Gold 75300 TUSCAN Gold 75331 NAPA Brushed Nickel 75299 TUSCAN Brushed Nickel 75333 NAPA Black Nickel 75301 TUSCAN Black Nickel Controls H...

Page 27: ...plete face 37 5 8 W x 23 3 4 H 75093 PILCST GLASS Glass Door Box 1 of 3 ref form 775258M 75092 PILCST PILRS2 Back Pillars Top Box 2 of 3 75094 PILCST GRL TRD3 Grill bars Traditional Box 3 of 3 Or 7509...

Page 28: ...28 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE SAFETY LISTING LABEL RDV33 40 AND SDVI33 40 2011 2012 2013 2014...

Page 29: ...29 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE LIGHTING LABEL RDV33 40 AND SDVI33 40...

Page 30: ...cement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your Lennox distributor or dealer Parts will be shipped at prevailing prices at time of or...

Reviews: