INSTALLATION  Combustible Wall Chimney Connector Pass-Throughs 
 

Notes:  
1.  Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall pass-through system 

and the chimney wall, to but not past the inner flue liner face.

  

2. 

A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a floor, or ceiling.

 

3. 

Where passage through a wall, or partition of combustible construction is desired, the installation shall conform to CAN/CSA-B365.

 

 

PAGE 12 

 

 

 

 

 

 

 

 

 

Method A. 12 inch (305mm) Clearance to Combustible Wall Mem-
ber: Using a minimum thickness 3.5 inch (90 mm) brick and a 5/8 
inch (16 mm) minimum wall thickness clay liner, construct a wall 
pass-through.  The clay liner must conform to ASTM C315 (Stan-
dard Specification for Clay Fire Linings) or its equivalent. Keep a 
minimum of 12 inches of brick masonry between the clay liner and 
wall combustibles.  The clay liner shall run from the brick masonry 
outer surface to the inner surface of the chimney flue liner but not 
past the inner surface.  Firmly grout or cement the clay liner in 
place to the chimney flue liner.   
 
Method B. 9 inch (229mm) Clearance to Combustible Wall Mem-
ber: Using a 6 inch inside diameter, listed, factory-built Solid-Pak 
chimney section with insulation of 1 inch (25.4 mm) or more, build 
a wall pass-through with a minimum 9 inch air space between the 
outer wall of the chimney length and wall combustibles.  Use sheet 
metal supports fastened securely to wall surfaces on all sides, to 
maintain the 9-inch air space.  When fastening supports to chim-
ney length, do not penetrate the chimney liner (the inside wall of 
the Solid-Pak chimney).  The inner end of the Solid-Pak chimney 
section shall be flush with the inside of the masonry chimney flue, 
and sealed with a non-water soluble refractory cement.  Use this 
cement to also seal to the brick masonry penetration.  
 
 
Method C. 6 inch (152mm) Clearance to Combustible Wall Mem-
ber: Starting with a minimum 24 gage (.024 inch [.61 mm]) 6-inch 
metal chimney connector, and a minimum 24 gage ventilated wall 
thimble which has two air channels of 1 inch each, construct a wall 
pass-through. There shall be a minimum 6 inch separation area 
containing fiber glass insulation, from the outer surface of the wall 
thimble to wall combustibles.  Support the wall thimble, and cover 
its opening with a 24-gage minimum sheet metal support. Maintain 
the 6-inch space.  There should also be a support sized to fit and 
hold the metal chimney connector. See that the supports are fas-
tened securely to wall surfaces on all sides.  Make sure fasteners 
used to secure the metal chimney connector do not penetrate 
chimney flue liner.   
 
 
Method D.  2 inch (51mm) Clearance to Combustible Wall Mem-
ber:

 

Start with a solid-pak listed factory built chimney section at 

least 12 inches (305mm) long, with insulation of 1 inch (25.4mm) 
or more, and an inside diameter of 8 inches (2 inches [51 mm] 
larger than the 6 inch chimney connector). Use this as a pass-
through for a minimum 24-gage single wall steel chimney connec-
tor. Keep solid-pak section concentric with and spaced 1 inch off 
the chimney connector by way of sheet metal support plates at 
both ends of chimney section.  Cover opening with and support 
chimney section on both sides with 24 gage minimum sheet metal 
supports. See that the supports are fastened securely to wall sur-
faces on all sides. Make sure fasteners used to secure chimney 
section do not penetrate chimney flue liner. 

D

C

B

A

Summary of Contents for 1900HT-M

Page 1: ...NUAL RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE EPA CERTIFIED WOOD BURNING STOVE THIS APPLIANCE MUST BE INSTALLED BY A QUALIFIED INSTALLER READ ENTIRE MANUAL THOROUGHLY BEFORE INSTALLATION P N 775002M Rev F 11 03 MODEL 1900HT M ...

Page 2: ...se gasoline gasoline type lantern fuel kerosene charcoal lighter fluid or similar liq uids to start or freshen up a fire in this heater Keep all such liquids well away from the heater while it is in use 10 DO NOT OVERFIRE If heater or chimney con nector glows you are overfiring Overfiring this appliance could cause a house fire Overfiring is a condition where the appliance is operated at temperatu...

Page 3: ...and ash lip One Insulation pad and strips Place pad and strips under top marble USING THIS MANUAL Please read and carefully follow all of the instructions found in this manual Please pay special attention to the safety instructions provided in this manual The Homeowner s Care and Operation Instructions included here will assure you have many years of dependable and enjoyable service from your appl...

Page 4: ...2 1 WARNING ELECTRICAL GROUNDING INSTRUC TIONS THIS APPLIANCE IS EQUIPPED WITH A THREE PRONG GROUNDING PLUG FOR YOUR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A PROP ERLY GROUNDED THREE PRONG RECEPTACLE DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLI ANCE 2 Local amendments 3 Is a permit required cost You may wish...

Page 5: ...ity to Combustibles Electrical Wiring The installation of this stove will require some research Once your options are determined consult with your local building department who will be able to give you the necessary installation requirements for your area Is a building permit required Rooms where installation may not be allowed etc WARNING CHECK ALL LOCAL BUILDING AND SAFETY CODES BEFORE INSTALLAT...

Page 6: ...not permit ted Chimney must be Simpson Dura Vent Dura Plus chimney with manufactured mobile home installation kit Dura Vent part number 6DP MH Chimney connec tor between stove and chimney must be Simpson Dura Vent DVL close clearance connector pipe Manufac tured Mobile Home installations must use a rain cap with a spark arrester Clearances Inches A 13 6 C 15 E 15 B 25 D 6 F 5 PROTECTED WALL CLEARA...

Page 7: ...The following 2 optional kits are required to deliver out side air to this appliance Contact your dealer to order Catalog 14M67 Outside Air Floor Duct Catalog 14M68 Back Cover Plate In all manufactured mobile homes and in many site built residences subject to local code a stove may be required to use outside air for combustion A 5 square outside air floor duct Back Cover Plate is available through...

Page 8: ...for shipping with a small retaining screw at the top of drawer Remove and dis card this screw BAFFLE PLATES This appliance has two heavy steel baffle plates that are installed in the upper firebox over the steel secon dary air supply tubes During shipment and installa tion the baffle plates might slide around and may need to be repositioned lined up to each other and pushed to the back wall in ord...

Page 9: ...per the Vent Manufactur ers installation instructions Ensure that there is an ef fective vapor barrier at the location where the chimney penetrates to the exterior of the structure This can be accomplished by applying a non hardening waterproof sealant to the following components Around the chimney at the point where the storm collar will meet the chimney just above the Flash ing Along the vertica...

Page 10: ...ion air to the fire chamber and for safely removing unwanted combustion byproducts from the appliance If the venting system s design does not pro mote these ends the system may not function properly Poorly functioning venting systems may create per formance problems as well as be a safety hazard i e an oversized chimney may result in less than optimum performance Installations into a large masonry...

Page 11: ...Using 6 Diameter Single Wall Connector Pipe Not Approved For Manufactured Mobile Homes MANUFACTURED MOBILE HOME STAN DARD Using 6 Diameter Type L Vent Connector Pipe MANUFACTURED MOBILE HOME STANDARD Using 6 Diameter Type L Vent Connector Pipe ...

Page 12: ...ide wall of the Solid Pak chimney The inner end of the Solid Pak chimney section shall be flush with the inside of the masonry chimney flue and sealed with a non water soluble refractory cement Use this cement to also seal to the brick masonry penetration Method C 6 inch 152mm Clearance to Combustible Wall Mem ber Starting with a minimum 24 gage 024 inch 61 mm 6 inch metal chimney connector and a ...

Page 13: ... with 24 karat industrial grade gold and requires curing to harden the gold Once it is cured it will never tarnish Prior to burning this appliance the doorframe should be cleaned thoroughly with a good window cleaning solution and a soft cloth Do not use any metal polishes or abrasives to clean the gold sur face Any oils or fingerprints left on the gold could be come permanent blemishes if the sto...

Page 14: ...e high burn control plate so it is not left open Generally you will want to set the air control somewhere in the low or medium range Low Burn approx 9 000 13 000 Btu hr Pull control handle out approx 3 4 Medium Burn approx 13 000 16 000 Btu hr Pull control handle out approx 1 1 2 Medium High Burn approx 16 000 25 000 Btu hr Pull control handle out approx 2 1 2 until small click is felt High Burn M...

Page 15: ...t is available at your local authorized Len nox Hearth Products dealer Never attempt to paint a hot stove FIRST FIRE When your installation has been completed and in spected you are ready to build your first fire 1 Pull the primary air control to the full open position located below the ash lip 2 Open door and build a small fire in the stove using paper and dry kindling Wait a few minutes for a go...

Page 16: ...od only see Important Warnings page 2 No 8 Do not burn particleboard scraps or pressed logs using bonding agents because they can produce conditions which will deteriorate metal Green or uncured wood does not work well as fuel and can cause increased creosote buildups The value of green wood as a source of heat is limited Do not overload or use kindling wood or mill ends as primary fuel as this ma...

Page 17: ...gallons of ashes DOOR GLASS AND ASH DRAWER GASKETS A 3 4 spun fiberglass rope gasket provides the seal around the fuel door and a 1 8 x 1 flat woven gasket glass provides the seal around the glass And a 1 4 spun fiberglass gasket provides a seal around the ash drawer Should these gaskets become frayed or dam aged they should be replaced with the same size and type as the original gasket Contact yo...

Page 18: ...ts of two heavy gage steel plates One of these plates has a welded strap to overlap the seam which runs front to back between the two Before removing the baffle plates from the firebox wearing a pair of leather or work gloves is recommended 1 To remove the baffle reach inside the firebox and slide one plate over the other 2 Next move the metal plates stacked one on top of the other sideways toward...

Page 19: ...se a full length liner to achieve ade quate draft for the appliance A draft gauge should read a minimum of 05 w c inches water column not to exceed 07 w c for optimum performance See Draft Requirements on page 10 OVERFIRING DAMAGE If the heater or chimney connector glows you are overfir ing Other symptoms may include Cracking warping or burning out of components gold doors may turn color stove gla...

Page 20: ...8 UNF Retrofit Requires Drill 3 213 Tap 10362 Torque Plate Latch Component Parts 1135 Knob Ash Drawer 27M80 Gasket Ash Drawer 1 2 X 1 8 x 16 907 Handle Air Control 26M19 Module Draft Control controls burn rate Includes gasket 14440 Dial A Temp rheostat MS1502 Marble Set Gray Also requires 1each 1054 4 each 1051 MS1505 Marble Set Green Also requires 1each 1054 4 each 1051 775002M Installation Opera...

Page 21: ...B 2 2 9 x 4 1 2 w notch FB11 2 4 1 2 x 4 1 2 FB 3 2 9 x 4 1 2 w hole FB23 2 5 x 1 FB7 4 9 x 2 1 8 37075 grate 2 4 1 2 x 4 3 8 PAGE 21 FIREBRICK DIAGRAM DOOR ASSEMBLY HANDLE ASSEMBLY MARBLESETS INSETSFORSTOVETOP ASHLIP Part Catalog MS1502 Gray Marble Set Part Catalog MS1505 Green Marble Set Marble is a natural product and therefore each piece will have its own unique character ...

Page 22: ... utilizing this floor penetration duct Duct penetration measures 5 square Back Cover Plate BCP 19 See illustration above When using outside combustion air the back cover plate is required to seal off the primary combustion air intake so that it can no longer draw air from within the room Blower Kit BK 100 A Blower Kit includes rheostat for variable speed con trol is available for increased heat ci...

Page 23: ...8 460 mm Fuel capacity 45 to 55 lbs 20 25 kg Firebox Size 2 cubic feet 610 mm Loading Front Width of outer top 27 3 4 705 mm Depth 27 1 2 699 mm stove back to ash lip front edge Height to flue 32 3 4 832 mm Height to stove top 33 1 2 851 mm Back to center line of flue 9 Approx weight with brick 380 lbs 173 kg Blower Optional 160 cfm Square feet heating capacity and burn time are approximations onl...

Page 24: ...SAFETY LISTING LABEL PAGE 24 ...

Page 25: ...EPA LABEL PAGE 25 ...

Page 26: ...e 26 OWNERSHIP RECORDS Dealer s Name Dealer s Address City State Zip Code Serial Number Date of Purchase Date Installed Notes SERVICE AND MAINTENANCE LOG Service Service Service Date Technician Description ...

Page 27: ...1110 West Taft Avenue Orange CA 92865 ...

Reviews: