Installation Manual •
COMPACTAIR ADV2 IOM-MIL162E-0920 09/2020
STANDARD EXECUTION
OPTIONAL EXECUTION
(TO BE CARRIED OUT BY THE INSTALLER)
1.11.- AIR SUPPLY CONFIGURATIONS.
1.- GENERAL CHARACTERISTICS
1.12.- OPTIONS.
INDOOR UNIT
1 CIRCUIT
020-035-045
INDOOR UNIT
2 CIRCUITS
060-075-085
Free-cooling.
1.- OPERATION.
The control compares the values of temperature between outside air and room air by means of the probes; if there
is a negative difference and the safety elements allow (discharge temperature probes) then the control acts on the
servomotor, which opens the outside damper and closes the return damper, allowing cool outside air to enter the
room.
The damper is proportionally regulated. If there is not a great demand for air indoors, it may be enough just to have
free cooling to condition the room. If there is a greater demand for air, the free cooling and the unit may need to be
working in different cooling mode stages.
2.- SUPPLY AND INSTALLATION.
The free cooling option will be supplied loose.
The return probe must be installed in the return air intake duct.
FRESH AIR OPTIONS.
RETURN AIR
RETURN AIR
RETURN AIR
FRESH AIR
FRESH AIR
FRESH AIR
The position of the dampers can be different as the one indicated in the drawings, by interchanging fresh and return air.
UNITS
1 CIRCUIT
2 CIRCUITS