![LenelS2 5000 Series Quick Installation Manual Download Page 2](http://html.mh-extra.com/html/lenels2/5000-series/5000-series_quick-installation-manual_1876397002.webp)
Tamper
GPO1
GPO2
GND
B/RX
A/TX
GND
DC+
CP
D1 Clock
D0 Data
GND
G-LED
R-LED
BZ CTRL
K-LED
Tamper output
General purpose I/O
General purpose I/O
Ground
RS485 - / OSDP
RS485 + / OSDP
Power supply
Power supply 9
to
30 VDC
Card Present
Wiegand Data1/Clock/Data
Wiegand Data0/Clock/Data
Ground
External Green LED control
External Red LED control
External Buzzer control
External keypad LED control
PIN
Description
Description
Wiegand
Wiegand
x
-
-
-
-
-
x
x
-
x
x
-
x
x
x
x
Terminal description
RS485/
OSDP
RS485/
OSDP
Clock/
Data
Clock/
Data
-
-
-
-
x
x
x
x
-
-
-
-
-
-
-
-
-
-
-
-
x
x
x
x
x
-
-
-
-
-
-
-
P2
P1
PIN
K-LED
BZ CTRL
R-LED
G-LED
GND
D0 Data
D1 Clock
CP
Tamper
GPO1
GPO2
GND
B/RX
A/TX
GND
DC+
P1
P2
Tamper
GPO1
GPO2
GND
B/RX
A/TX
P1
P2
CP
D1 Clock
D0 Data
GND
G-LED
R-LED
BZ CTRL
K-LED
Quick Installation Guide
LenelS2 Readers - 5000 Series Standard 13.56 MHz
LenelS2 Readers - 5000 Series Standard 13.56 MHz/125 kHz
GND
DC+
Quick Installation Guide
LenelS2 Readers - 5000
Series Slimline 13.56 MHz
Please note that this is only a quick installation guide.
Information regarding recommendations, measurements and accessories are
available in the full version of the Lenel
S2
Readers - 5000 Series installation
guide.
1 Current draw does not include heater consumption.
2 LED settings; LED Bar = Low, Back Light = Low
Please consult table in full installation manual for more information on heater
consumption settings and how the LED-settings will affect current draw.
Power consumption:
Notes
1.
Maximum
W
iegand cable length is 150 meters and requires a high quality
shielded cable with minimum AWG18 dimension (=0.8231
mm
2
) in an environment
free from electrical noise. A cable with smaller dimension or an installation
environment with electrical disturbances will reduce the maximum cable length.
2.
Wiegand & Clock/Data requires dedicated wires for external control of Green
LED, Red LED, Buzzer and Keypad backlight.
3.
When utilizing the GPI/O’s, each respective GPO1 or GPO2 must be connected
to each respective pin and also to GND. The general purpose input/output will only
be activated if so applied in the reader configuration.
4.
RS485/OSDP requires twisted pair cable.
Model
Current draw (idle
1
)
Current draw (peak
1,2
)
12
V
24
V
12
V
24
V
Standard 13.56
MHz
50 mA
40 mA
147 mA
99 mA
Standard
13.56 MHz/125 kHz
90 mA
60 mA
187 mA
119 mA
Slimline 13.56
MHz
50 mA
40 mA
164 mA
108 mA
Please note that this is only a quick installation guide.
Information regarding recommendations, measurements and QR code modules and other
accessories are available in the full version of the LenelS2 Readers - 5000 Series installation
guide.
Please consult table in the full installation manual for more information on heater
consumption settings and how the LED-settings will affect current draw.
12 VDC
12 VDC
24 VDC
24 VDC