Reader Interface
40
DirecDoor Installation Guide
•
Alpha Xtra Guard1® foil shield cable, non-plenum-rated
•
Belden series security and alarm cable (commercial applications shielded), plenum-rated
For readers not listed in the table below, refer to the applicable reader installation manual.
Wiring to Wiegand Readers, Door Contacts, and Exit Request
Wiring to F/2F Readers, Door Contacts, and Exit Request
Wiring Output Device to DO Interface
Note:
The DDSDC only supports one door strike DO relay, one alarm DI, and one exit DI on
Connector J2.
Wiring to Wiegand Readers, Door Contacts, and Exit Request
J1/J3: Connecting T-5xx Series Reader
J1/J3 Pin
Signal Name
Reader Pigtail Colors
1
+12 VDC
Red
2
Ground
Black
3
Reader Data 0
Green
4
Reader Data 1
White
5
Door DO (Reader LED)
Orange
J1/J3: Connecting the DO Outputs
J1/J3 Pin
Signal Name
Cable Color
6
16DO - DO (Open Collector)
Blue
7
16DO - DO (Open Collector)
Brown
8
16DO - DO (Open Collector)
Yellow
J2/J4: Door and Exit DI Wiring
Pin
Signal Name
Cable Color
1
Supervised Door DI (Alarm Point) (1K/1K)
Red
2
Supervised Door DI Return
Green
3
Supervised Exit DI (Exit Request) (1K/1K)
Orange
4
Supervised Exit DI Return
White
J2/J4: Door Strike Relay Wiring
Pin
Signal Name
Cable Color
5
Ground
Black
6
Door Strike Relay – Normally Closed (NC)
Blue
Summary of Contents for DirecDoor
Page 1: ...7 4 DirecDoor Installation Guide...
Page 4: ......
Page 8: ...Table of Contents 8 DirecDoor Installation Guide...
Page 14: ...Introduction 14 DirecDoor Installation Guide...
Page 19: ...DirecDoor Installation Guide 19 Mounting DirecDoor Mounting Template...
Page 22: ...Installation Planning and Mounting 22 DirecDoor Installation Guide...
Page 56: ...DDIO Interface 56 DirecDoor Installation Guide Resistances Detected by PXNplus...
Page 58: ...DO Interface 58 DirecDoor Installation Guide Wiring Output Device to DO Interface...
Page 76: ...Controller Firmware Tools 76 DirecDoor Installation Guide...
Page 79: ...DirecDoor Installation Guide 79 CE Regulatory Notice CE Regulatory Notice...