Measuring Functions
22
Analyst
3P
EO 0620GDF Rev. E
Events
Events are voltage dips, swells and interruptions. This measuring mode
automatically records all events for later evaluation. The threshold values
for starting the recording are freely configurable in the menu.
3.2 Connecting the Analyser
When connecting current circuits, the corresponding measuring lines must
first be connected to the base unit and then to the current sensor to prevent
the risk of electric shock in case of false connection
.
Use the original cables only for connecting the current probes and the voltages
to the analyser. If these are damaged do not use them anymore. Make sure
that all plugs are connected correctly and locked, in order to prevent contact
with live sections.
Measurement in a Single-Phase Power Network
In order to measure in a single-phase power network, connect your device to
the power network according to the following figure .
In order to analyse the measured values correctly, you must pay attention to
the colour code or the labels of the measuring wires:
Voltage:
Current:
Mains line Test leads
L L1
L L2
L L3
N N
Mains line
Test leads
L1 L1
not connected L2
not connected
L3
not connected
N