Page - 29
HP5 SYSTEM LOCKOUT
ISSUE
The heat pump has locked due to five high-pressure faults during one call for heating .
RESOLUTION
1. Deactivate then reactivate power to the heat pump to clear error.
2. Troubleshoot the high-pressure issue causing the error.
l
LOW PRESSURE FAULT
ISSUE
The refrigerant system’s low-pressure switch is showing as open.
RESOLUTION
Heat and Cool Units (Reversing)
Place heat pump in heating mode and perform the following troubleshooting.
1. Check for proper fan operation. If the fan is not operating, contact Leisure Temp Technical Support.
2. Check for obstructed airflow around the heat pump.
l
3. Check for a dirty or blocked evaporator coil.
l
4. Check for signs of heavy ice buildup on the coil.
LP5 SYSTEM LOCKOUT
ISSUE
The heat pump has locked due to five low-pressure faults during one call for heating .
RESOLUTION
1. Deactivate then reactivate power to the heat pump to clear error.
2. Troubleshoot the low-pressure issue causing the error.
l
MULTI-UNIT COMM FAULT
ISSUE
Slaved heat pump is not receiving a signal from the master heat pump.
RESOLUTION
1. Confirm the master heat pump is operating correctly. If, for example, no power is supplied to the master
heat pump, an error will appear on the slaved heat pumps.
OTA SYSTEM LOCKOUT
ISSUE
A malfunction has occurred that could allow the water temperature to surpass a safe level. An installed
"Over Temperature Alarm" kit has disabled the system.
l
" on page 40 for more information.
RESOLUTION