16
E-Flex User Manual, Rev. 1.30
Hi – active high* (default)
Lo – active low*
Press
Sel
to choose the displayed option. The apostrophe LED will be lit for the current selected option.
Press
Store button
to record the new setting.
*Note: Dip switch SW2-x must be set to ON for active low, OFF for active high.
Assign Zones to Occupancy Input
Press
Enter
at the
occX
menu, the
options
list control
is displayed.
Press the
Up
button twice to scroll to the
zone
list control.
Press
Enter
to show the first item in the zone list.
Use the
Up
and
Down
buttons to scroll thru the list of zones:
Zon1-4
– 4 circuit panel
Zon1-8
– 8 circuit panel
Press
Sel
to assign or un-assign the displayed zone. The apostrophe LED will be lit for each assigned
zone.
Press
Store
button to record the new zone assignments.
Set Occupied Preset
Press
Enter
at the
occX
menu, the
options
list control is displayed.
Press the
Down
button twice to scroll to the
occupied preset
entry control.
Press
Enter.
The current occupied preset will be displayed.
Use the
Up
and
Down
buttons to set the occupied preset, 1-16, or OFF. The
default is preset 1.
Press
Store
button to record the new setting.
Set Un-occupied Preset
Press
Enter
at the
occX
menu, the
options
list control is displayed.
Press the
Down
button to scroll to the
un-occupied preset
entry control.
Press
Enter.
The current un-occupied preset will be displayed.
Use the
Up
and
Down
buttons to set the un-occupied preset, 1-16, or OFF. The
default is preset OFF.
Press
Store
button to record the new setting.