background image

2

#12 – #14 AWG

Cu Wire Only

WIRING

21

/RDG

/LQH

*URXQG

1HXWUDO

/RDG

+RW

Single-switch Wiring

Three-way Wiring

When using a three-way application, 

lights may be turned on from either 

switch, but can only be turned off at 

the switch that turned them on.

21

/LQH

/RDG

*URXQG

21

/RDG

/LQH

*URXQG

1HXWUDO

/RDG

+RW

Wire insert

Optional

wire wrap

Insert or wrap wire as shown and 

tighten screw in the clockwise direction.

Strip Gauge

1/2"

12.7mm

SWITCH ADJUSTMENT

Enter Settings Mode by pressing the Calibration Button (located on the left, behind the faceplate).

•  If no input occurs within four seconds the display flashes then moves to the next setting.
•  Press the Calibration Button to view the settings without making changes.
•  Press the ON/OFF button within four seconds to change the setting.

DELAY: 5 min. to 12 hr.

DELAY sets the time-out period. The selections begin at the currently set time (3 hours, default). When  

the time is less than an hour, the time increases by 5 minutes each time you press the ON/OFF button. 

When the time is more than an hour, it increases by 15 minues. When the selection passes 12 hours, it 

restarts the selection scrolling at 5 minutes.

SCROLL: Up or Down (dn)

To have the user’s time override options decrease from a longer time to a shorter time, set Scroll for dn 

(down). To increase from a shorter time to a longer time, set Scroll for UP.

FLASH: ON or OFF
SOUND: ON or OFF

When the setting selection is complete the unit will either:

•  Beep once and display END if the calibration button is being held; release the button to continue.
•  Beep three times while it displays END. This gives you a chance to press the ON/OFF button to restart the setting procedure.

If you don’t press either button within three seconds, the unit exits the Settings Mode and resumes its previous state.

TS-400

ON

1

LCD 

Display

ON/OFF 

Button

Calibration 

Button

INSTALLATION

1.  Connect the existing wires to the switch terminals.

•  Hot to Line; 
•  Load to Load; 
•  Ground to Ground.

2.  Attach the time switch to the wall by mounting it in the wall box with 2 mounting screws provided.
3.  Turn on power to the time switch 
4.  7-15 seconds after power is supplied to the time switch, it will be ready to function. 

The time switch beeps and the word OFF appears in the display. Push the ON/

OFF switch to activate the lights. The timer begins its countdown. Push the ON/OFF 

switch during countdown to turn the lights off.

5.  Select feature settings using the Switch Adjustment procedures.
6.  Install cover plate.

WARNING:

 TURN THE POWER OFF AT THE 

CIRCUIT BREAKER BEFORE WIRING.

WARNING:

 

BE SURE THE GROUND 

WIRE IS SECURELY CONNECTED.