background image

3

INSTALLATION

1.  Install the power pack according to its instructions.
2.  Connect the power pack wires to the sensor as follows:

RED

 wire (+24VDC) to the +24V IN terminal on the sensor.

BLACK

 wire (Return) to common (COMM.) terminal on the sensor.

BLUE

 wire to control output (CTRL. OUT) terminal on the sensor.

3.  Wire the Isolated Relay. The Isolated Relay is rated for 1A @ 30VAC/VDC. 

Connect the wires necessary to the application that requires this output:
•  Normally Closed (N.C.) - Open when occupancy is detected.
•  Relay Common (must be used for proper operation)
•  Normally Open (N.O.) - Closed when occupancy is detected.
The bottom terminal on the sensor is not used.

NOTE: 

The isolated relay follows the actual occupancy state of the sensor 

and is not affected by  the switch.

4.  Turn the power 

ON

.

5.  Test and adjust the sensor if necessary.
6.  Install industry standard decorator wall switch cover plate (not included).

Common

White (Neutral)

Red

(Load)

Red (Line)

White

Black

Hot

Neutral

Power

Pack

Blue

Black

Red

Lighting

Load

Control Outputs

+24 VDC

Isolated Relay Outputs 

Normally closed contact

Common
Normally open contact
Not used

DIP SWITCH SETTINGS

=ON    =OFF

=Factory Setting

8

Auto On

Manual On

ON Mode

7

Disabled

Enabled

Audible Alert

4

High

Low, 50%

PIR Sensitivty

9

1 2 3 4 5

6 7 8

Time

Delay

Walk-Through

ON

ON Mode

Not Used

Audible Alerts

PIR Sensitivity

Switch 9 is not used

5 6

Trigger

Mode

Initial

O

ccupanc

y

M

aintain

O

ccupanc

y

Re-trigger

Option C

Both Both Both

Standard

Both

Either

Either

Option A

Either Either

PIR

Option B

PIR

PIR

PIR

Test/20 min

5 minutes

1 2

Time Delay

15 minutes

30 minutes

3

Disabled

Enabled

Walk-Through

Trigger

Mode

ON/OFF 

Button

Button  

Hinges

Tabs

DIP Switches

PIR Lens

Fig. 1: Detection LEDs 

   Red = PIR 

   Green = Ultrasonic

Ultrasonic Cones

Ultrasonic Sensitivity 

Adjustment Trimpot

ADJUSTMENTS

Sensor Adjustment

Remove the wall plate. Remove the button cap by firmly squeezing together the top sides of the button assembly. Gently pull it away 

from the unit. 
When the adjustments are completed, replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the 

top of the button while pressing it into the unit. Reinstall the cover plate.

Light Level Adjustment

The light level can be set with loads 

ON

 or 

OFF

. To enable light level control and set the threshold: 

1.  Make sure the room is lit appropriately.
2.  Put the sensor into TEST mode. You have 5 minutes to complete the procedure.
3.  Press and hold the 

ON/OFF

 button for 3 seconds, until you hear a beep.

4.  Step away from the sensor. After 25 seconds a beep sounds, indicating that the threshold level is set. This threshold is retained, 

even if power is lost, until it is re-set or disabled. 

To disable light level control, press and hold the 

ON/OFF

 button for 7 seconds, until a double beep tone sounds.

WARNING:

 TURN THE POWER OFF AT THE 

CIRCUIT BREAKER BEFORE WIRING.

Summary of Contents for Wattstopper DW-100-24

Page 1: ...can override this function by pressing the ON OFF button See Light Level Adjustment Turning ON the Load ON Mode The DW 100 24 can be programmed for either Auto ON or Manual ON mode In either mode the load can be turned ON or OFF using the ON OFF button Manual ON DIP 8 ON With the ON Mode DIP Switch in the ON position the occupant must press the ON OFF button to turn ON the load The sensor keeps th...

Page 2: ...em the area occupied Both requires motion detection by the PIR and the Ultrasonic Either requires motion detection by only one technology PIR requires motion detection by the PIR Initial Occupancy The method that activates a change from Standby area unoccupied and load OFF to Occupied area occupied and load may turn ON Maintain Occupancy The method indicating that the area is still occupied and th...

Page 3: ...itivity Switch 9 is not used 5 6 Trigger Mode Initial Occupancy Maintain Occupancy Re trigger Option C Both Both Both Standard Both Either Either Option A Either Either PIR Option B PIR PIR PIR Test 20 min 5 minutes 1 2 Time Delay 15 minutes 30 minutes 3 Disabled Enabled Walk Through Trigger Mode ON OFF Button Button Hinges Tabs DIP Switches PIR Lens Fig 1 Detection LEDs Red PIR Green Ultrasonic U...

Page 4: ...ights turn ON verify that the correct On Mode is selected in DIP Switches 8 and 9 2 Check to see if light level control is enabled cover the sensor lens with your hand If the lights come ON adjust the light level setting 3 If lights still do not turn ON call 800 879 8585 for technical support Lights do not turn ON with motion LED does not flash 1 Press and release each button Make sure that the co...

Reviews: