![LEGRAND Wattstopper DT-305 Manual Download Page 1](http://html1.mh-extra.com/html/legrand/wattstopper-dt-305/wattstopper-dt-305_manual_1870522001.webp)
Wattstopper
®
360° Dual Technology • Low Voltage Occupancy Sensor (version 3)
with Manual On feature
Double technologie à 360° • Détecteur de présence basse tension (v3)
avec les fonctionnalité de marche manuelle
Doble tecnología de 360° • Sensor de presencia de bajo voltaj (v3)
con función de encendido manual
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 23948 – 07/18 rev. 5
Catalog Number • Numéro de Catalogue • Número de Catálogo: DT-305
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
DT-305 -U is BAA and TAA compliant (Product produced in the U.S.)
UNIT DESCRIPTION
The Wattstopper DT-305 360° Dual Technology occupancy
sensors combine advanced passive infrared (PIR) and ultrasonic
technologies into one unit. The combination of these technologies
helps to eliminate false triggering problems even in difficult
applications.
The DT-305 turns lighting systems on and off based on
occupancy. The DT-305 provides numerous operating modes that
can be combined to create the ideal custom control. The sensors
can be configured to turn lighting on, and hold it on as long as
either or both technologies detect occupancy. After no movement
is detected for a user specified time (30 seconds to 30 minutes)
the lights are switched off. A “walk-through” mode can turn lights
off after only 3 minutes, if no activity is detected after 30 seconds
of an occupancy detection.
The DT-305 operates on 24V, supplied by Wattstopper Power
Packs.
SPECIFICATIONS
Voltage ......................................................18–28VDC/VAC half rectified
Current Consumption @24VDC/VAC ..................16mA (DC), 69mA (AC)
Power Supply ..................................................Wattstopper Power Packs
Isolated Relay Rating ...................................................1A @30VDC/VAC
Operating Temperature .................................... 32° to 131°F (0° to 55°C)
Time Delay Adjustment ................................... 30 seconds to 30 minutes
Walk-Through Mode ..........................3 minutes if no activity after 30 sec
Test Mode ....................................................5 sec. upon DIP switch reset
PIR Coverage (Typical) ................................................................1300 ft²
Sensitivity Adjustment ....................High or Low (DIP switch setting)
Ultrasonic Coverage (Typical) ......................................................1300 ft²
Sensitivity Adjustment ................................ Min. to Max. (trimpot)
Frequency ..........................................................................40kHz
UL & CUL Listed for use with Wattstopper Power Packs
COVERAGE PATTERN
The DT-305 provides a 360° coverage pattern. The coverage shown represents walking motion at a mounting height of 8-12 feet. For
building spaces with lower levels of activity or with obstacles and barriers, coverage size may decrease. The coverage for PIR ONLY
trigger mode varies with mount height. Refer to pattern below for details. Ultrasonic coverage is roughly the same for 8-12 foot mount
heights. Refer to PIR and Ultrasonic trigger mode coverage for details.
Side View
8’ (2.4m)
10’ (3m)
12’ (3.7m)
0
40’
(12.2m)
30’
(9.1m)
20’
(6.1m)
10’
(3m)
40’
(12.2m)
30’
(9.1m)
20’
(6.1m)
10’
(3m)
0
PIR Only Coverage
Top View
36 ft
(10.97m)
36 ft x 36 ft
(10.97m x 10.97m)
PIR
Coverage
Ultrasonic
Coverage
Drawings not to scale, representative of PIR and
Ultrasonic Trigger Mode major motion coverage.
8-12 foot Mounting Height