LEGRAND Wattstopper CU-250 Installation Instructions Download Page 4

800.879.8585

www.legrand.us/wattstopper

No. 24302 – 09/16  rev. 1

© Copyright 2016 Legrand All Rights Reserved.

© Copyright 2016 Tous droits réservés Legrand.

© Copyright 2016 Legrand Todos los derechos reservados.

Wattstopper warranties its products to be free 

of defects in materials and workmanship for a 

period of five (5) years. There are no obligations 

or liabilities on the part of Wattstopper for 

consequential damages arising out of, or in 

connection with, the use or performance of this 

product or other indirect damages with respect 

to loss of property, revenue or profit, or cost of 

removal, installation or reinstallation.

Wattstopper garantit que ses produits sont 

exempts de défauts de matériaux et de fabrication 

pour une période de cinq (5) ans. Wattstopper 

ne peut être tenu responsable de tout dommage 

consécutif causé par ou lié à l’utilisation ou 

à la performance de ce produit ou tout autre 

dommage indirect lié à la perte de propriété, de 

revenus, ou de profits, ou aux coûts d’enlèvement, 

d’installation ou de réinstallation.

Wattstopper garantiza que sus productos 

están libres de defectos en materiales y mano 

de obra por un período de cinco (5) años. No 

existen obligaciones ni responsabilidades por 

parte de Wattstopper por daños consecuentes 

que se deriven o estén relacionados con el 

uso o el rendimiento de este producto u otros 

daños indirectos con respecto a la pérdida 

de propiedad, renta o ganancias, o al costo 

de extracción, instalación o reinstalación.

WARRANTY INFORMATION

INFORMATIONS RELATIVES À LA GARANTIE

INFORMACIÓN DE LA GARANTÍA

TEST MODE

To test the detection coverage:

1.  Press and hold the 

ON/OFF

 button. After 10 seconds the lighted switch turns off. The load turns 

ON

 if it was not already 

ON

. The 

sensor is now in a TEST mode that lasts 5 minutes. (You can end the TEST mode sooner by pressing the 

ON/OFF

 button for 

another 10 seconds).
During the TEST mode, the controlled load turns 

ON

 for 5 seconds each time the sensor that initiated the TEST mode detects 

occupancy.

2.  Move out of the coverage area or stand very still. The controlled load turns 

OFF

 after 5 seconds if no motion is detected.

3.  Move into the coverage area for the unit that initiated the TEST mode. The controlled load turns 

ON

 for 5 seconds each time 

the sensor detects motion. After 5 seconds expire without motion detection, the load turns 

OFF

. The controlled load turns 

ON

 

automatically with the next motion detection and stays 

ON

 for 5 seconds.

4.  Repeat as necessary to ensure that the desired coverage areas are within detection range.
5.  Increase or decrease the ultrasonic sensitivity level as needed.

You can do this test for each CU-250 in your multi-way configuration. So that you can determine the actual coverage area for each 

multi-way switch individually, only the CU-250 that is in TEST mode will control the load.

TROUBLESHOOTING

Lighted switch is OFF, no load response to ON/OFF button press:

•  Make certain that the circuit breaker is 

ON

 and functioning.

Lighted switch is ON, no load response to ON/OFF button press:

•  Check the light bulb and/or motor switch on the fan mechanism.

Lighted switch is OFF, no load response to ON/OFF button press:

•  Make certain that the circuit breaker is 

ON

 and functioning.

Lighted switch is ON, no load response to ON/OFF button press:

•  Check the light bulb and/or motor switch on the fan mechanism.

Load will not turn OFF automatically:

•  Press 

ON/OFF

 button. If the controlled load turns 

OFF

, go to next step.

•  The time delay can be set from 15 seconds to 30 minutes. Check the time delay setting for each CU-250 in your multi-way 

configuration. Ensure that all CU-250s have the same time delay setting.

•  Ensure the front of the sensor is not blocked.
•  Ensure that there is no movement within the coverage area for all the sensors related to the load for the set time delay. Air currents 

can cause false detection. Make sure the sensor is at least 6 feet (2 meters) away from air supply ducts, open windows, fans and 

exhaust fans. Reduce the ultrasonic sensitivity level slightly to eliminate false detection.

If load does not respond properly after following troubleshooting, turn OFF  

power to the circuit then check wire connections or call technical support.

COVER PLATES

Wattstopper CU wall switches fit behind industry standard decorator style switch cover plates.