2

WIRING DIRECTIONS

Each Wattstopper BZ series power pack can supply power for 8 CI-300 

sensors. When using more sensors than this, multiple power packs are 

required.
Refer to the wiring diagram for the following procedures:
Connect the 

low voltage

•  RED wire (+24VDC) from power pack to the 

+24V

 terminal on the sensor.

•  BLACK wire (Return) from power pack to 

Common

 terminal on the sensor.

•  BLUE wire from power pack to 

Control Out

 terminal on sensor.

To add a manual switch

 such as the LVS-1 Momentary Toggle Switch, or  

RS2-3 Low Voltage Momentary Switch to the above applications–connect:

•  Wire from one side of switch to +24 terminal on sensor.
•  Wire from other side of switch to Man Switch terminal on sensor.

Wiring the Isolated Relay:

 (The Isolated Relay is rated for 1A@30VAC/VDC)

 Connect the wires necessary to the application that requires this output:

•  Relay Common (must be used for proper operation).
•  N.O. (Normally Open)–Closed when occupancy is detected.
•  N.C. (Normally Closed)–Open when occupancy is detected.

Care should be taken to separate high voltage power from low voltage (Class 2) control wiring.
All connections to sensor are low voltage, Class 2.

WARNING:

 TURN THE POWER OFF AT THE 

CIRCUIT BREAKER BEFORE WIRING.

CI-300

Passive Infrared

Occupancy Sensor

Appliance

Control

88T9

E101196

+24VDC/VAC

Connect to Watt Stopper 

Class 2 Power Packs

For Indoor Use Only

LISTED

www.legrand.us/wattstopper

Relay Com.

N.O.
N.C.

Control Out.

Man. Switch

+24V

Common

v5

Wiring 

terminals

Load #1

Load #2
(Optional)

CI-300

Rear Housing

Depluggable 

Terminal

Front Cover

Ceiling

Spring Clips (2)

Blue

Control Out

+24V

Common

Low Voltage

Class 2

Line 

Voltage

Line
Neutral

Feed Through

Power Pack

Black

Red

#1

#2

Line Voltage

Switches

Standard wiring with local off switch

LVS-1

Load

Rear Housing

Depluggable 

Terminal

Front Cover

Ceiling

Spring Clips (2)

Blue

Control Out

Black

+24V

Low Voltage

Class 2

Line Voltage

Line
Neutral

Feed Through

Power Pack

Man.Switch

Red

CI-300

Common

Man.Switch

+24V

Jumper

Back

of

LVS-1

For low voltage

momentary switch set

DIP switches #7 ON

Manual-On wiring with low voltage momentary switch

MOUNTING THE SENSOR DIRECTLY TO CEILING

1.  Attach the plastic spring clips to the edge of the sensor in the slots provided.
2.  Cut a 3.5” to 4” round hole in the acoustic ceiling tile at the mounting location.  

A 3.5” hole is recommended for a secure fit.

3.  Pull the low voltage wire from the power pack to the sensor through the hole.
4.  Connect the low voltage wires to the appropriate terminals on the sensor.
5.  Push the sensor up through the hole until the Spring Clips hold the sensor  

securely in place.

6.  Snap the front cover onto the sensor. Using an Octagonal J-Box
7.  Pull the low voltage wires from the power pack into the J-Box through the conduit 

knockout.

5HDU

KRXVLQJ

'HSOXJJDEOHWHUPLQDO

)URQW

FRYHU

&HLOLQJ

6SULQJFOLSV

Ceiling Mount

Summary of Contents for Wattstopper CI-300

Page 1: ...temperatures may cause false activations Mount the sensor to the ceiling The CI 300 sensors are designed for a ceiling height of about 8 10 feet Mounting above or below this range will significantly affect the coverage patterns Be aware that as you decrease the mounting height you decrease the range and increase the sensitivity to smaller motions Conversely when you increase the height you increas...

Page 2: ...er Class 2 Power Packs For Indoor Use Only LISTED www legrand us wattstopper Relay Com N O N C Control Out Man Switch 24V Common v5 Wiring terminals Load 1 Load 2 Optional CI 300 Rear Housing Depluggable Terminal Front Cover Ceiling Spring Clips 2 Blue Control Out 24V Common Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Black Red 1 2 Line Voltage Switches Standard wiring wi...

Page 3: ...is optional The sensors are factory preset to allow for quick installation in most applications Verification of proper wiring or coverage or customizing the sensor s settings can be done using the following procedures To make adjustments open the Front Cover by pulling on the cover tab There is a 30 second warm up period when power is first applied Before making adjustments make sure the office fu...

Page 4: ...hanged DIP SWITCH SETTING The CI 300 has 7 DIP switches under the cover Time Delay Switches 1 2 3 The sensor will hold the lights ON as long as occupancy is detected The time delay countdown starts when no motion is detected After no motion is detected for the length of the time delay the sensor will turn the lights OFF Walk Through Switch 4 Walk through mode turns the lights OFF three minutes aft...

Page 5: ...o not turn OFF automatically 1 The sensor technology PIR may be experiencing activations from outside the controlled area or from some type of interference see Unwanted Sensor Activations below 2 Check all sensor and power pack wire connections 3 Disconnect power pack s blue wire If the lights do not turn off replace power pack Reconnect blue wire If the lights turn off the problem may be in the s...

Page 6: ...nts À l inverse lorsque vous augmentez la hauteur vous augmentez la portée et diminuez la sensibilité aux petits mouvements À des hauteurs supérieures à 3 7 4 3 m 12 14 pi vous commencez à réduire la sensibilité de manière significative En règle générale chaque occupant doit être capable de voir clairement le détecteur Souvent l emplacement idéal d un CI 300 dans un bureau fermé est excentré Évite...

Page 7: ...pper Relay Com N O N C Control Out Man Switch 24V Common v5 Bornes de raccordement AVERTISSEMENT COUPER LE COURANT AU DISJONCTEUR PRINCIPAL AVANT D INSTALLER LE CÂBLAGE Câblage standard avec interrupteur d arrêt local Câblage de la marche manuelle avec un interrupteur instantané basse tension Charge 1 Charge 2 en option CI 300 Boîtier arrière Borne débranchable Couvercle frontal Plafond Clips à re...

Page 8: ... Couvercle frontal Plafond Vis Montage avec une boîte de jonction RÉGLAGE DU DÉTECTEUR L unité est préréglée pour un fonctionnement de base comme décrit dans ce guide LE RÉGLAGE EST OPTIONNEL Les détecteurs sont préréglés en usine afin de vous permettre de l installer rapidement dans la plupart des applications Pour vérifier que le câblage ou la portée sont corrects ou pour personnaliser les régla...

Page 9: ...ité des occupants Une fois la temporisation écoulée si aucun mouvement n est détecté pendant la période de redéclenchement de 30 secondes l interrupteur manuel doit être utilisé pour remettre la charge en MARCHE Automatique MARCHE ce mode se sert des déclenchements dus à la présence ainsi que de l activation de l interrupteur pour ACTIVER la charge Un interrupteur manuel fournit les fonctionnalité...

Page 10: ... Vérifiez que le disjoncteur de circuit a bien été réenclenché 2 Vérifiez tous les raccordements des fils du détecteur et du bloc d alimentation 3 Vérifiez que le capteur est raccordé à une tension de 24 V Si du 24 V est bien présent remplacez le détecteur Si vous ne trouvez pas de 24 V vérifiez la présence de haute tension au niveau du bloc d alimentation Si c est le cas remplacez le bloc d alime...

Page 11: ...r los paquetes de alimentación Wattstopper de 24 V CA o CA de media onda rectificada Los sensores CI 300 también tienen un relé aislado con contactos Normalmente abierto N A y Normalmente cerrado N C para acoplarse con el sistema de calefacción ventilación y aire acondicionado HVAC o el sistema de administración de energía EMS GUÍAS PARA LA COLOCACIÓN Según los obstáculos como muebles o divisiones...

Page 12: ...minal de 24 del sensor El cable del otro lado del interruptor a la terminal de interruptor man del sensor Cableado del relé aislado El relé aislado es apto para 1 A a 30 V CA V CC Conecte los cables necesarios para la aplicación que requiere esta salida Relé común se debe usar para el funcionamiento adecuado Normalmente abierto N A se cierra cuando se detecta una presencia Normalmente cerrado N C ...

Page 13: ...para que los tornillos de montaje se inserten en las ranuras de los orificios tipo bocallave 6 Apriete los dos tornillos para fijar el sensor a la caja de conexiones 7 Encastre la cubierta frontal en el sensor ORMDPLHQWR WUDVHUR 7HUPLQDO GHVHQFKXIDEOH XELHUWD IURQWDO LHOR UDVR EUD DGHUDV GH UHVRUWH Montaje en techo Alojamiento trasero Terminal desenchufable Caja de conexiones octágonal de 4 al men...

Page 14: ...rante el día cuando la luz ambiente en el área esté en el nivel deseado El nivel de luz no se puede activar mientras esté activo el modo de prueba Espere a que finalice el modo de prueba o seleccione cualquiera de las configuraciones adicionales de demora de tiempo antes de activar la función de nivel de luz El indicador LED de presencia PIR quizás aún responda cuando las luces se mantienen apagad...

Page 15: ...omo la activación mediante interruptor para encender la carga Un interruptor manual proporciona la siguiente funcionalidad adicional 1 La carga puede encenderse con la activación del interruptor manual y permanece encendida según la configuración de lógica de presencia La demora de tiempo del sensor funciona según lo programado Cuando la carga se apaga a causa de la falta de detección de presencia...

Page 16: ... algún tipo de interferencia consulte Activaciones no deseadas del sensor a continuación 2 Controle todas las conexiones de cables del sensor y de la fuente de alimentación 3 Desconecte el cable azul de la fuente de alimentación Si las luces no se apagan reemplace la fuente de alimentación Vuelva a conectar el cable azul Si las luces se apagan el problema puede estar en el sensor Para comprobar Vu...

Reviews: