![LEGRAND Trimod HE 10 Installation And Maintenance Manual Download Page 19](http://html.mh-extra.com/html/legrand/trimod-he-10/trimod-he-10_installation-and-maintenance-manual_1872203019.webp)
Trimod HE®
Installa
tion and main
tenanc
e manual
19
4.1
Visual check
On delivery of the UPS, carefully inspect the packaging and the product for any damage that might have occurred during
transport. Check there is no damage to the indicator on the outer label reading "Shock Watch".
If there is possible or ascertained damaged immediately inform:
- the transporter;
- the LEGRAND Technical Support Service.
Check the equipment corresponds with the material indicated in the delivery documentation. The packaging protecs the
Trimod HE UPS from mechanical and environmental damage.
Follow the instructions in Chapter 10 when storing the UPS.
4.1.1 Equipment and supplied accessories check
The equipment and the relative supplied accessories must be a perfect state of repair.
Check that:
- the shipping data (address of the recipient, no. of packages, order no, etc.) correspond to what is contained in the
delivery documentation;
- the Trimod HE technical rating plate data on the label applied to the UPS correspond with the material purchased,
described in the delivery documentation;
- the documentation accompanying the equipment includes the installation manual and the user manual.
Should any of these be different from what they should be, immediately inform the LEGRAND Technical Support Service
before commissioning the equipment.
4.2
Unpacking
To remove the packaging material, comply with the icons on the outside of the box and observe the following procedure:
1. cut the wrapping material and open the plastic packaging safety holds;
2. open the top of the box;
3. remove the upper protection;
4. remove the four protective corners;
5. remove the packaging container pulling it upwards;
6. remove the pallet and the front/rear bracket from the UPS by undoing the four fixing
screws present;
7. examine the UPS for any damage. Immediately inform the shipper and the supplier
in the case of apparent damage.
Keep the packaging material for any future shipment of the UPS.
The package can be fully recycled: should you wish to dispose of it, comply with the
legislation in force.
4.3
Check of the content
The content of the supply is subject to thorough checking before the shipment; nonetheless it is always advisable to
check that it is complete and in order on receiving the material.
The following list is general:
- 1 Trimod HE UPS (empty cabinet);
- 1 envelope of accessories containing washers for the contact with the earthing, set of screws for fitting the panels, two
eight-pole terminal strips, a serial cable and fuses (the latter are only included for models with internal batteries);
- 1 envelope of accessories containing one or more EC15 connectors according to the model and connecting jumpers for
the terminal strip (ONLY for Trimod HE 10, 15, 20 and 30 TM);
- 1 front closing panel;
- 2 base strips for side closing;
- end user manual;
- acceptance report;
- quickstart and installation manual.
Should there be defects and/or missing material, immediately inform the LEGRAND Technical Support Service before
commissioning the equipment.
CAUTION
The quickstart and the installation manual are only to be used and consulted by SKILLED TECHNICIANS.
INDICATION
The power modules and any battery drawers to install must be bought separately.
4. Unpacking and moving
Summary of Contents for Trimod HE 10
Page 1: ...Trimod HE Installation and maintenance manual Item LE10273AA 03 18 01 CT ...
Page 2: ...2 EN ENGLISH 3 Trimod HE ...
Page 15: ...Trimod HE Installation and maintenance manual 15 Trimod HE 30 TT Trimod HE 30 TM ...
Page 16: ...16 3 Models Trimod HE 40 Trimod HE 60 ...
Page 57: ...Trimod HE Installation and maintenance manual 57 Notes ...
Page 58: ...58 Notes ...
Page 59: ...Trimod HE Installation and maintenance manual 59 ...