Chapter 8: Using the Command Line Interface
535
Displayed information:
Without the parameter "details," only the reading, state, threshold,
deassertion hysteresis and assertion timeout settings of the
specified inlet sensor are displayed.
With the parameter "details," more sensor information is displayed,
including resolution and range.
If the requested sensor type is not supported, the "Sensor is not
available" message is displayed.
Additional sensors supported by specific models:
Specific PX3 models support some or all of the following sensors. The
CLI command(s) listed above can be also applied to the following sensors.
Note that the measurement unit of current values in CLI is A, not mA.
Sensor type
Description
peakCurrent Peak
current sensor
reactivePower Reactive power sensor
displacementPowerFa
ctor
Displacement power factor sensor
residualCurrent RCM
current
sensor
For Type A, it is the sensor that detects
residual AC current.
For Type B, it is the sensor that detects
both residual AC and DC current.
residualDCCurrent RCM
DC
current
sensor - detects residual
DC current only.
Available only on PDUs with RCM Type B.
Note: For information on RCM Type A and B sensors, see
RCM Current
Sensor
(on page 797).
Summary of Contents for Raritan PX3-3000 Series
Page 5: ......
Page 90: ...Chapter 4 Connecting External Equipment Optional 69 ...
Page 424: ...Chapter 6 Using the Web Interface 403 ...
Page 447: ...Chapter 6 Using the Web Interface 426 ...
Page 448: ...Chapter 6 Using the Web Interface 427 Continued ...
Page 885: ...Appendix K RADIUS Configuration Illustration 864 Note If your PX3 uses PAP then select PAP ...
Page 890: ...Appendix K RADIUS Configuration Illustration 869 14 The new attribute is added Click OK ...
Page 891: ...Appendix K RADIUS Configuration Illustration 870 15 Click Next to continue ...
Page 921: ...Appendix L Additional PX3 Information 900 ...