224 Legrand PDU User Guide
Note: If you have not configured the System SNMP Notification Action to specify the SNMP destination(s),
see
Editing or Deleting a Rule/Action
(on page 213).
Front Panel Settings
You can set up the default mode of the front panel display, and front panel functions for outlet switching or
actuator control.
Note that available front panel settings are model dependent.
Outlet switching -- available on outlet-switching capable models only. That is, Legrand Switched PDUs.
Actuator control -- available on all models.
Default front panel mode setup -- available on all models.
To configure the front panel settings:
1. Choose Device Settings > Front Panel.
2. Configure the following:
To configure the default view of the LCD display, select one mode below.
Note: The default view is shown in the automatic mode. See
Automatic and Manual Modes
(on page
Mode
Data entered
Automatic mode
The LCD display cycles through both the
inlet and overcurrent protector information.
This is the default.
Overcurrent protector information is
available only when you Legrand PDU has
overcurrent protectors.
Inlet overview
The LCD display cycles through the inlet
information only.
To enable the front panel outlet-switching function, select the "Outlet switching" checkbox.
To enable the front panel actuator-control function, select the "Peripheral actuator control" checkbox.
Now you can turn on or off outlets/actuators by operating the front panel. See
Power Control
(on
page 66) and
Peripherals
(on page 67).
Configuring the Serial Port
You can change the bit rate of the serial port labeled CONSOLE on the Legrand PDU. The default bit rate for
console operation is 115200 bps.
The Legrand PDU supports using the following devices via the serial interface:
A computer for console management.
A Raritan serial access product -- see
Connection to Raritan Serial Access Products
(on page 496)
You can set diverse bit-rate settings for console operations. Usually the Legrand PDU can detect the device
type, and automatically apply the preset bit rate.
The Legrand PDU will indicate the detected device in the Port State section of the Serial Port page.
To change the serial port's baud rate settings:
1. To configure serial port settings, choose Device Settings > Serial Port.
2. Click the Console Baud Rate field to select the baud rate intended for console management.