2. INSTALLATION
The thermostat is typically mounted to an industry standard double gang
junction box or trim ring about 5 feet above the floor. Example Legrand
part numbers are shown in the chart below.
Thermostats should be placed away from windows to avoid solar heating
to improperly affect the units temperature sensitivity. Be certain that the
thermostat will not be covered by objects such as a bathroom or closet
door when open. The thermostat should not be mounted near the heating/
cooling equipment in a manner where direct airflow, or the waterfall effect
of a heating or cooling unit would impact the measurement of the overall
room.
2.1 Flush Mounting
2.2. Wall Mounting
The product may also be wall mounted using the included wall mount
bracket. The bracket can mount over a double gang wall box pattern or
secured appropriately to the wall using suitable fasteners.
2.3. Wiring
The WZ3TSTATHx Thermostat can connect to various different types of
HVAC systems. It utilizes 4 different wiring harness to access specific
features.
2.3.1 Harness 1 – Main Harness PN WATSTATH101
2.3.2 Harness 2 – Digital Wiring Harness PN WATSTATH201
Applicable Legrand Double Gang Boxes
New Work Plastic
S235RAC
New Work Steel Stud
S235S50AC
Screw Steel Stud
S235RACS
Old Work Plastic
S232W
Figure 4 – Wall Mounting
ORG
PPL
GRY
WHT
YEL
GRN
RED
BLK
BLU
BRN
Low Fan
Fan Power
Valve Power
Heat Valve
Cool Valve
Ground
24V AC
Common
High Fan
Med Fan
GRY
PPL
BLU
GRN
YEL
RED
ORG
BRN
Analog Input
0-10V VFD Fan
Digital Input 3
Digital Input 2
Digital input 1
12V DC
Ground
NOT USED
Header 1
Header 2
Not Used
Header 3
Header 4
GRN
RED
BLK
Ground
RS-485 B (+)
RS-485 A (-)
TER DAM R 24VAC
TER DAM NO Normal Open
TER DAM NO Normal Closed
Figure 5 – Wiring Harness Locations
Pin Number
Function
Color
1
Ground
Green
2
24 VAC
Red
3
Common
Black
4
High Fan
Blue
5
Medium Fan or Second Stage Heat
Brown
6
Cold Water Valve or Compressor Signal (Heat Pump)
Yellow
7
Hot Water Valve or Reversing Valve (Heat Pump)
White
8
Valve Power
Grey
9
Fan Power
Violet
10
Low Fan
Orange
Pin Number
Function
Color
1
Analog Input - Remote Thermistor
Grey
2
Analog Output - 0-10V VFD Fan
Purple
3
Digital Input 3 - External PIR/motion sensor
Blue
4
Digital Input 2 - Balcony Door/Window, 2 transitions
to active
Green
5
Digital Input 1 - Entry Door, 2 transitions to active
Yellow
6
Not Used
Orange
7
VEE (12 Vdc)
Red
8
GND Ground
Brown
Figure 3 – Flush Mounting