2. INSTALLATION

The thermostat is typically mounted to an industry standard double gang 

junction box or trim ring about 5 feet above the floor. Example Legrand 

part numbers are shown in the chart below. 
Thermostats should be placed away from windows to avoid solar heating 

to improperly affect the units temperature sensitivity. Be certain that the 

thermostat will not be covered by objects such as a bathroom or closet 

door when open. The thermostat should not be mounted near the heating/

cooling equipment in a manner where direct airflow, or the waterfall effect 

of a heating or cooling unit would impact the measurement of the overall 

room.

2.1 Flush Mounting

2.2. Wall Mounting

The product may also be wall mounted using the included wall mount 

bracket. The bracket can mount over a double gang wall box pattern or 

secured appropriately to the wall using suitable fasteners.

2.3. Wiring

The WZ3TSTATHx Thermostat can connect to various different types of 

HVAC systems. It utilizes 4 different wiring harness to access specific 

features.

2.3.1 Harness 1 – Main Harness PN WATSTATH101

2.3.2 Harness 2 – Digital Wiring Harness PN WATSTATH201

Applicable Legrand Double Gang Boxes

New Work Plastic

S235RAC

New Work Steel Stud

S235S50AC

Screw Steel Stud

S235RACS

Old Work Plastic

S232W

Figure 4 – Wall Mounting

ORG
PPL
GRY
WHT

YEL

GRN

RED

BLK
BLU

BRN

Low Fan

Fan Power

Valve Power

Heat Valve

Cool Valve

Ground
24V AC

Common

High Fan

Med Fan

GRY

PPL
BLU
GRN

YEL

RED

ORG

BRN

Analog Input

0-10V VFD Fan

Digital Input 3
Digital Input 2
Digital input 1

12V DC

Ground

NOT USED

Header 1

Header 2

Not Used

Header 3

Header 4

GRN

RED

BLK

Ground

RS-485 B (+)

RS-485 A (-)

TER DAM R 24VAC

TER DAM NO Normal Open

TER DAM NO Normal Closed

Figure 5 – Wiring Harness Locations

Pin Number

Function

Color

1

Ground

Green

2

24 VAC

Red

3

Common

Black

4

High Fan

Blue

5

Medium Fan or Second Stage Heat

Brown

6

Cold Water Valve or Compressor Signal (Heat Pump)

Yellow

7

Hot Water Valve or Reversing Valve (Heat Pump)

White

8

Valve Power

Grey

9

Fan Power

Violet

10

Low Fan

Orange

Pin Number

Function

Color

1

Analog Input - Remote Thermistor

Grey

2

Analog Output - 0-10V VFD Fan

Purple

3

Digital Input 3 - External PIR/motion sensor

Blue

4

Digital Input 2 - Balcony Door/Window, 2 transitions 

to active

Green

5

Digital Input 1 - Entry Door, 2 transitions to active

Yellow

6

Not Used

Orange

7

VEE (12 Vdc)

Red

8

GND Ground

Brown

Figure 3 – Flush Mounting

Summary of Contents for Pass & Seymour WZ3TSTATH

Page 1: ...ture reference 1 Read these instructions 2 Keep these instructions 3 Heed all warnings 4 Follow the instructions 5 Do not use this apparatus in or near water 6 Clean only with a dry cloth 7 Do not blo...

Page 2: ...Digital Wiring Harness PN WATSTATH201 Applicable Legrand Double Gang Boxes New Work Plastic S235RAC New Work Steel Stud S235S50AC Screw Steel Stud S235RACS Old Work Plastic S232W Figure 4 Wall Mountin...

Page 3: ...85 B Red 3 GND Green Pin Number Function Color 1 Reserved no connection N A 2 TER_Dam R 24 VAC Red 3 TER Dam No Normally Open White 4 TER Dam No Normally Closed Black 2 3 5 Wiring Diagrams 2 3 5 1 Dia...

Page 4: ...nued 2 3 5 3 Diagram 3 HpO Single Stage Heat 24VAC Maestro App Type 3F HpO 1SH 2 3 5 4 Diagram 4 HpB Second Stage Heat 24VAC Maestro App Type 2F HpB 2SH 2 3 5 5 Diagram 5 HpO Second Stage Heat 24VAC M...

Page 5: ...Wiring Diagrams continued 2 3 5 6 Diagram 6 VFD Heat Cool Maestro App Type VFD HC 2 3 5 7 Diagram 7 3 Fan Cool Maestro App Type 3F C 2 3 5 8 Diagram 8 2 Pipe Cool with Electric Heat Maestro App Type 3...

Page 6: ...2 3 5 Wiring Diagrams continued 2 3 5 9 Diagram 9 VRF Maestro App Type VRF 2 3 5 10 Diagram 10 Damper...

Page 7: ...ode button until the indicator above the temperature readout says Heat Using the Up and down arrows modify the set point as desired 3 1 6 Change Set point Cool Set point Cool is set by pressing the mo...

Page 8: ...F LEM Guest Selectable Temperature Control Limits rented occupied Low 85 F LEM Guest Selectable Temperature Control Limits rented occupied High 72 F Check in temperature 72 F Default Thermostat Dorma...

Reviews: