2

IMPORTANT INSTALLATION INFORMATION

To ensure a successful installation and startup of a wireless system, the following steps must be taken by the 

installing contractor. 

Failure to document all device address and locations may delay completion of startup 

and result in additional startup charges.
Key Requirement:

 Document 

every

 Device’s MAC Address (at least the last 4 alphanumeric characters). An 

additional MAC address label is included for the installer to use on a floor plan map. The last four characters are 

repeated in a larger font, in bold. Keep this document so that the commissioning tech has access at a later date.

SETTING UP A ROOM NETWORK BY PAIRING DEVICES

Pair wireless devices to a room controller to create an individual room network and enable Plug N’ Go operation.
Device pairing can be done by using Push-to-Pair (PtP) mode on the room controller and all other wireless devices, or by using the  

DLM Config App. 
To pair devices in a network, they must all have the same wireless channel and Network ID. By default the channel is 15 and the 

Network ID is 1. Using Push-to-Pair mode, the Network ID for all devices being paired is migrated to a new number, so that only those 

device communicate with each other. The channel number will remain at 15.

NOTE: 

LMCS-100 software, version 4.7 or later can also be used to pair devices. However, LMCS-100 requires use of an LMBR-650. 

Using LMCS, it is possible to change the channel as well as Network ID.

DEVICE PAIRING USING PUSH-TO-PAIR MODE

Push-to-Pair in a room with a single LMRC-611 Room Controller

NOTE: 

Once you enter PtP mode on the room controller, a three minute timer begins. If the Config button on any device in the room is 

pressed, the timer resets and begins the three minute countdown again. If no Config button is pressed within three minutes, the 

room controller will exit PtP mode.

1. 

Enter PtP mode

 

on the room controller.

 Press the Config button three times (within three seconds) until the LED on the room 

controller flashes green. 

2. 

Enter PtP mode on the LMSW-605.

 Using a pointed tool, press the Config button three times. As with the room controller, the 

LED on the switch will flash green.

3. 

Pair the LMSW-605. 

Press the Config button on the LMSW-605 one more time to pair it to the room controller. The load connected 

to the room controller will toggle once (if the load is OFF, it will turn ON; if ON, it will turn OFF) to indicate that pairing was 

successful. Also, the LMSW-605’s blinking LED will turn to solid green as another indicator of a successful pairing. 

NOTE: If there are any wireless sensors, dimmers, or additional switches in the room, repeat steps 2 and 3

 for each of 

those devices so that all devices are paired together in the same network. For each device, the load will toggle during step 

3 and its config LED will turn solid green.

4. 

Exit PtP mode. 

From any device, press the Config button 3 times. After a few seconds, the LED on each Room controller, switch 

or sensor currently in PtP mode will flash white and reboot, leaving the default network and migrating to the new network. Then, 

the LED on the room controller will flash blue and the pairing process finishes.The default Network ID on all devices will change to 

a new number, based on the last four digits of the Mac address on the room controller, and now those devices will communicate 

only with each other and not any devices which have not been paired. 

Sensor Params

LMPX-600

LMPC-600

Mode             Auto On

Blink              On

Load Type     Dim

LMRC-611MCC

LMSW-605

Wireless

Scene Switch 

Wireless

Sensor and/or

Photosensor 

IPv6 Mesh for 

networking of DLM 

rooms and devices 

over 6LoWPAN

Bluetooth low energy

communication for

mobile App support

DLM Configuration App

on a mobile device

LMBR-650

For networking and

managing rooms,

floors, and building

(not needed for

stand-alone rooms)

WIRELESS ROOM CONNECTION

HYBRID ROOM CONNECTION

Ceiling Mount

Occupancy Sensor

LMBC-650

Wireless

Network Bridge

LMBR-650

Border Router

LMSW-605

Wireless

Scene Switch

Line

Voltage

Room

Controller

(LMRC-112)

B

Line Voltage

Switched with

0-10 Volt control

Dimming Ballast

LED Driver, etc.

Load

Examples

(any relay)

A

Switched

etc.

B

Class 1 Dimming

(Class 2 also available)

DLM Configuration App

on a mobile device

Note: 

the DLM config app

can only connect with the 

LMBC-650 to update firwmare.

You need an LMBR-650 and 

LMCS to commision a Hybrid

room.

Sensor Params

LMPX-600

LMPC-600

Mode             Auto On

Blink              On

Load Type     Dim

Distance Recommendations:

30’ max between LMSW-605 and mobile device
60’ max. between LMSW-605 and room controller 

or bridge
10’ minimum and 100’ maxmimum between 

LMBR-650 and room controller or bridge

Examples of labels