LEGRAND LEXIC AstroRex DY64 Manual Download Page 6

Program 
type

Execution

Char- 
acte- 
ristics

ON/OFF 
times

Weekday assi-
gnments

Active peri-
od 
START date

Active peri-
od
END date

Application, objectives, examples

EXCEP- 

TION

EVERY 

YEAR

MON TO 

SUN

P

p

Day, month, 

- - - - 

from 

0:00:00 

hours

Day, month, 

- - - - 

to  

24:00:00 

hours

An exception program is to completely replace any existing  
weekly or annual program on each day during a specific period 
of each year. 
Example: the irrigation pump of an orchard is to be switched 
on from 17:00:00 to 18:00:00 on each day in the period from 
20.March ---- to 10.April ----.

INDIVI- 

DUAL

P

P

Day, month, 

- - - - 

from 

0:00:00 

hours

Day, month, 

- - - - 

to  

24:00:00 

hours

An exception program is to completely replace any existing  
weekly or annual program on certain days during a specific peri-
od of each year.
Example: the irrigation pump of an orchard is to be switched on 
from 17:00:00 to 18:00:00 on each Monday and Friday in the 
period from 11 April ---- to 15 May ----.

PROG 

ON

P

p

Day, month, 

- - - - 

from ON 

time

Day, month, 

- - - - 

to  

OFF time

A channel is to be switched on continuously from the ON time 
on the START date to the OFF time on the END date every 
year. This exception program is to completely replace any  
existing weekly or annual program for this channel.
Example: instead of the normal times for illumination of a  
public building, the illumination is to be switched on from 
17:00:00 on the national holiday 3 October ---- until 07:00:00 the 
next morning 4 October ----.

PROG  

OFF

P

p

Day, month, 

- - - - 

from ON 

time

Day, month, 

- - - - 

to  

OFF time

An output is to be switched off continuously from the ON time 
on the START date to the OFF time on the END date every 
year. This exception program is to completely replace any  
existing weekly or annual program for this channel.
Example: in order to save power, certain equipment in a factory 
is to be switched off during the Christmas holiday period of each 
year. i.e. from 18:00:00 on 23 December ---- to 6:00:00  
on 27 December ----.

ONCE

MON TO 

SUN

P

p

Day, month, 

year 
from 

0:00:00 

hours

Day, month, 

year 

to  

24:00:00 

hours

On each day during a specific period of a specified year, an 
exception program is to completely replace any existing weekly 
or annual program.
Example: during the Christmas holidays of the year 2005, the 
heating in an apartment is to be switched each day from 7:00:00 
to 23:00:00, instead of in the normal cycle. This  
exception period is to begin on 24 December 2005 and end  
on 06 January 2006.

INDIVI- 

DUAL

P

P

Day, month, 

year 
from 

0:00:00 

hours

Day, month, 

year 

to  

24:00:00 

hours

On certain weekdays during a specific period of a specific year, 
an exception program is to completely replace any existing  
weekly or annual program. 
Example: in December 2005, the heating system of a  
department store is to be switched on from  8:00:00 to 18:00:00 
each Sunday, because the store opens on Sundays in the  
period 4 December 2005 to 18 December 2005.

PROG 

ON

P

p

Day, month, 

year 

from ON 

time

Day, month, 

year 

to  

OFF time

A channel is to be switched on continuously from the ON time 
on the START date to the OFF time on the END date of a  
specific year. This exception program is to completely replace 
any existing weekly or annual program for this channel.
Example: the alarm system of an office building is to be  
switched on continuously during the vacation period 19:00:00 on 
15 July 2005 to 06:00:00 on 7 August 2005.

PROG  

OFF

P

p

Day, month, 

year 

from ON 

time

Day, month, 

year 

to  

OFF time

A channel is to be switched off continuously from the ON time 
on the START date to the OFF time on the END date of a spe-
cific year. This exception program is to completely replace any 
existing weekly or annual program for this channel.
Example: in 2005, the normal recess gong in a school is to be 
switched off during the summer holidays 00:00:00 on 28 July 
2005 to 24:00:00 on 10 September 2005.

Summary of Contents for LEXIC AstroRex DY64

Page 1: ...ised opening and repair by other persons will invali date all claims for liability replacement or warranty services When operated from the mains voltage the time switch may not be used to switch safe...

Page 2: ...to 30 minutes the time switch will switch 30 minutes before sunrise and 30 minutes before sunset Offset Setting 2 D Factory setting 8 E 52 N The MINUS key is used to adjust the westward longitude valu...

Page 3: ...at 23 00 hours PROGRAM WEEK This menu item is provided for the simple input of programs which are to be repeated weekly such as switching of lights and boilers A weekly program consists of an ON time...

Page 4: ...annel switches only as defined in the exception program Option INDIVIDUAL the exception program is active from 00 00 hours on the start date to 24 00 hours on the end date During this period the outpu...

Page 5: ...itch on the outside lights of a church from 17 00 00 to 24 00 00 on each Sunday in the period 1 December to 31 December An existing weekly program is to be supplemented with additional switching times...

Page 6: ...ing the Christmas holiday period of each year i e from 18 00 00 on 23 December to 6 00 00 on 27 December ONCE MON TO SUN P p Day month year from 0 00 00 hours Day month year to 24 00 00 hours On each...

Page 7: ...together The exception program is overriding within its defined period of activity YEAR program The various weekly and annual programs are ORed together The various annual programs are ORed together...

Page 8: ...ASSIVE 7 Reset Note A reset clears the entire memory which means that all previously set data will be lost Press and hold all four keys together for about 2 seconds then release them After a reset the...

Page 9: ...ograms for this channel specifies otherwise 9 Control input with delaytime 0 23h 59min 59s Setting the delaytime Control input 0 23h 59min 59s Switched output Changing the lithium battery module Impor...

Page 10: ...long term accuracy it is advisable to activate synchronisation on 50 60 Hz mains with frequency adjustment Instead of its STANDARD function the output of channel 1 is switched on and off cyclically Th...

Page 11: ...iami New York 75 W 40 N San Francisco 122 W 38 N 116 E 40 N Chongqing 107 E 30 N Harbin 127 E 46 N Hong Kong 114 E 22 N Shenyang 123 E 42 N 104 E 36 N Xi an 109 E 34 N Manila 73 E 34 N Kabul 5 00 3 30...

Reviews: