background image

Instant Heat 2 Ducted

Instruction Manual 

Cat No. R622D1

1

  Specifications

Cat No

R622D1

Supply Voltage

230-240V a.c.   50Hz 

Power Rating

630W max

Protection Class

Class I

Maximum Airflow Rate

93m

3

/hr (3m duct)

Ducting size

Ø100mm

Projection into Ceiling

195mm

Required Ceiling Depth

220mm min

Ceiling Cut-out Size

330 x 170 mm

Protrusion from Ceiling

80mm

2

  Installation

The infrared lamps heat by direct radiation rather than by heating the air in 
the room. So the Instant Heat 2 ducted should be located directly over the 
drying area. HPM Instant Heat 2 ducted must not be installed where there is a 
possibility of water splashing on to the lamps. Locate in accordance with the 
requirements of Wiring Rules AS/NZS 3000 relating to damp situations. This 
means that no part of the Instant Heat 2 may be located directly above any part 
of the bath or shower recess or enclosure. For unenclosed showers refer to 
Wiring Rules conditions.

Note: Steam will only be removed if there is sufficient flow of air through the room. 
Ensure adequate inlets exist through windows, vents or under the door. Air-flow 
path from inlets to fan should ideally pass over the steam sources. See over – ‘Getting 
the most from your Instant Heat 2 Ducted’. Regulations concerning the discharge of 
air have to be fulfilled. The Instant Heat has a free air discharge of 93m³/hr and care 
should be taken that air flow throughout meets specific requirements in building 
regulations. Local building codes may require venting to the outside. Ducting can 
be fitted and vented to the outside using exterior grille provided as shown in Fig.1 
and Fig.2. Vertical ducting with roof vents will result in reduced fan performance, 
increased noise and condensation/dripping.

Fig.1

Fig.2

Read through these instructions completely before commencing installation. 
Retain for future use.

3

  Location

The Instant Heat is for ceiling mounting only, with 
the lowest point to be at least 2.2 metres above floor 
level. It is not intended to be installed in wardrobes 
or within 300mm of sides of walls, as per Figure 3. 
There is a danger of combustion if placed too close 
to curtains or other flammable materials. 

Additional Instant Heats may only be installed if at 
least 1.2m clearance between them is observed.

Fig.3

Instant Heat 2 may be installed in the ceiling cavity 
between joists using the built-in clip fasteners. 
Correct installation requires the cavity to have a 
minimum height of 220mm for safe operation. The 
clearances between Instant Heat and surrounding 
joists and above ceiling shown in Fig.4 and Fig.5 
shall be observed. Thermal insulation or similar 
material shall not be placed on top of the Instant 
Heat, and adjacent material to the side shall be 
kept clear to a minimum distance of 300mm. 
Joists, beams and rafters shall not be cut or 
notched to install the Instant Heat.

After determining the location of the Instant Heat 
2 Ducted use the template to mark out and cut an 
opening 330mm x 170mm. If adequate support is not 
available for the instant heat, it may be necessary to 
provide extra strengthening.

4

  Ceiling preparation

height clearance

75mm side clearance

220m

m

Joist

Joist

Joist

300m

m

300m

m

Fig.4

Fig.5

20mm min

Thermal 
Insulation

300mm

300mm

Wall

Roof Vent