The likelihood of such shock can be reduced if such grounds are removed during installa-
tion and maintenance (applicable to equipment and remote battery supplies not having a
grounded supply circuit).
CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin and
eyes. It may be toxic.
• This UPS has dangerous high voltages on its input and output connections. Contact with these
voltages may be life threatening.
• In case of emergency, immediately turn off the equipment and disconnect the power cord from
the AC power supply to disable the UPS.
• Do not allow any liquid or any foreign object to enter the UPS.
• The UPS is intended for indoor installation in a ventilated, controlled indoor environment with
a range of temperature between 0°C (+32°F) and +40°C (+104°F) and non-condensing humidity
between 20% and 80%.
• Do not install the UPS in locations with sparks, smoke and hazardous gas or where there is water
and excessive humidity. Dusty, corrosive, and salty environments can damage the UPS.
• Do not plug the UPS input into its own output.
• Do not attach a power strip or surge suppressor to the UPS.
• Do not cover the cooling vents and keep a clearance of 20 cm beyond the UPS rear panel. Avoid
exposing it to direct sunlight or installing it near heat emitting appliances.
• Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
• Do not place the UPS near equipments that generate strong electromagnetic fields and/or near
equipments that are sensible to electromagnetic fields.
WARNING
All the UPSs are category C2 products according to the EN 62040-2. In a residential en-
vironment, these equipments may cause radio interference, in which case the user may be re-
quired to take additional measures.
DAKER DK Plus
1 kVA - 3 kVA
Summary of Contents for DAKER DK Plus Series
Page 1: ...DAKER DK Plus 1 kVA 3 kVA Manuel d installation Installation manual ...
Page 7: ...38 3 Installation 3 1 Package content Check for the following package content ...
Page 8: ...EN 39 3 2 Tower configuration setup 3 2 1 UPS DAKER DK Plus 1 kVA 3 kVA ...
Page 9: ...40 3 2 2 UPS battery cabinet optional 3 Installation S1 ...
Page 11: ...42 3 Installation ...