PROFESSIONAL FLUSH MOUNTED SMOKE ALARM

INSTALLATION INSTRUCTIONS

Installation:

WARNING:

 In the interests of safety, a licensed electrician, in accordance with 

the relevant requirements of AS/NZS 3000, must install this smoke alarm and 

all wiring.
This alarm must be wired to a continuous 230-240V a.c. 50Hz circuit. Ensure 

any switching device cannot inadvertently override the unit.

NOTE: 

See overleaf for recommended locations of alarms

n    

There are four terminals in the supply terminal block, marked I, N, A and                         

E/LOOP. It is important that the alarm be wired correctly to ensure correct 

operation. Incorrect wiring to the smoke alarm will damage the unit and 

invalidate the warranty. See wiring diagrams.

n     

A maximum length of 300 metres of wire can be used in interconnecting 

smoke alarms. Spacing between interconnected smoke alarms must not 

exceed 30m per alarm. Minimum wire cross section 1.00mm

2

n    

Interconnected smoke alarms must be connected to the same final 

sub-circuit.

n    

Do not use any wire that could later be confused with the normal house 

wires for the interconnect wire. For example, green/yellow earth wire.

n    

Do not connect AC power wires to I interconnect terminal. This may damage 

smoke alarms.

n     

Do not connect the I interconnect wire to any device, except the 

I interconnect terminal of another 643084, 643085 or 643087 smoke alarm 

or interface 643086. Otherwise, smoke alarms will be damaged.

n    

Smoke alarms should be interconnected only within the confines of a 

single-family living unit. If smoke alarms are interconnected between 

different units, there may be excessive nuisance alarms. Residents may not 

be aware that smoke alarms are being tested or that it is a nuisance alarm 

caused by cooking, etc.

INSTALLER PLEASE NOTE:

Before you connect the mains power, check wiring polarity.

n

  If the alarm ‘chirps ’ press the Test button to check the battery condition. 

n

  If ‘chirps ’ persist return smoke alarm to your supplier.

n

  This smoke alarm is intended for ceiling mount only.

WIRING INSTRUCTIONS:

n  

This smoke alarm can be interconnected with other 643084, 643085 or 

643087 smoke alarms. Interconnection with other brands or models may 

cause damage or result in a shock or fire risk.

n  

Up to a limit of 20 smoke alarms may be interconnected.

n  

Not interconnectable with HPM 645/3 ionisation smoke alarm

Specifications:

Cat No.: 

643087

Supply Voltage: 

230-240V a.c.

Frequency: 50Hz

Backup Battery: 

3V Lithium battery (non replaceable)

Temperature Range: 

+0°C to ~ +40°C

Humidity Range: 

10-95% at 20

o

C

Siren Sound Level: 

85 dB at 3 metres

Unit Size: 

Ø110 x 77mm

Ceiling Cut-out Size:  

Ø 90mm

Protrusion from ceiling:   Ø 25mm

Depth into ceiling:  

52 mm

Maxiumum Lifespan: 

10 years

IMPORTANT: 

READ ALL INSTRUCTIONS BEFORE INSTALLATION.

NO USER SERVICEABLE PARTS INSIDE THIS SMOKE ALARM.

Do not attempt to repair the smoke alarm yourself.

Not to be used with non-pure sinusoidal power sources.